| Plumbing | Original | D | 11/6/2026 | SHANEN | SHANEN | All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. Construction review comments must be addressed to verify compliance with section 403.1. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Use table E103.3(2) public occupancy load values. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2379584 |
| CO Springs DRE | Original | A | 11/6/2026 | SSADLER | SSADLER | Approved for commercial interior finish. Use is compatible with the approved development plan. No exterior changes | | CO Springs DRE | 2379392 |
| CSU Contract Admin. | Original | A | 11/5/2026 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved and applicable development fees/charges paid - master meter configuration. JMD | jdemello | CSU Contract Admin. | 2379183 |
| City Engr | Original | N | 11/5/2026 | JDAGNILLO | JDAGNILLO | | | City Engr | 2379182 |
| CSU Electric | Original | A | 11/5/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CG | cgraves | CSU Electric | 2378988 |
| Stormwater | Original | N | 11/5/2026 | GHUNTLEY | GHUNTLEY | Interior finish, does not require SWENT | | Stormwater | 2378877 |
| CSU Water | Original | N | 11/5/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2378841 |
| CSU Waste Water | Original | N | 11/5/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2378837 |
| Zoning/Planning | Original | / | 11/5/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2378773 |
| CSU Gas | Original | A | 11/5/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas meter, service line location. Contact Field Engineering at 719-668-4985 (Gas) for service line approval form or with any questions. AM | amagoon | CSU Gas | 2378772 |
| Electrical | Original | D | 11/5/2026 | BERTHA | BERTHA | Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide service load summary
Provide cord reel detail complying with 314.23(H) NEC
Recessed lighting must be shown on the lighting schedule and comply with C402.5.10 2021 IECC
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4 2021 IECC
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10 2021 IECC
Controlled receptacles must be shown on the plan per C405.11 2021 IECC and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Comply with Colorado Model Electric Ready Solar Ready Code Electric Ready Requirements
Panel Schedule – provide two or three pole breaker space for each piece of combustion equipment indicating an equivalent electrical heating load or future heat pump.
Floor Plan - provide receptacle or junction box located near each piece of combustion equipment with no physical obstructions.
Confirm the junction box, receptacle, and dedicated panel breaker spaces are clearly labeled for their intended future use.
Complete re-review necessary . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2378691 |
| Electronic Plan | Original | / | 11/5/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2378682 |
| Construction | Original | D | 11/4/2026 | DOUGC | DOUGC | Rated construction // Accessibility // IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2378668 |
| Electronic Plan | Original | / | 11/4/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2378375 |
| Enumeration | Original | A | 10/26/2026 | AMY | AMY | This is suite 170. | | Enumeration | 2375140 |
| Electronic Plan | Original | / | 10/26/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2375112 |
| | Original | / | 10/26/2026 | SYSTEM | SYSTEM | Plan Review fees paid 10/26/2026 for plan submitted 10/26/2026. Submit Date updated to now. Plan now open for review. | | | 2375079 |
| Energy | Original | / | 10/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2375030 |
| Floodplain | Original | N | 10/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6222412005) | | Floodplain | 2375029 |