Fire | Original | A | 7/6/2000 | JAN | JAN | SMC 7-6-00 | | Fire | 118986 |
Plumbing | Original | A | 7/3/2000 | RUSSELL | RUSSELL | Approved as noted | | Plumbing | 118992 |
Mechanical | Original | A | 7/3/2000 | RUSSELL | RUSSELL | Approved as noted | | Mechanical | 118987 |
Plumbing | Original | D | 6/27/2000 | RUSSELL | RUSSELL | Provide cleanout at sink as previously indicated + more | | Plumbing | 118994 |
Mechanical | Original | D | 6/27/2000 | RUSSELL | RUSSELL | Provide correct corresponding labeling of exhaust fans with ahu's, need 15 cfm per occupant per section 1202, '97 UBC + more | | Mechanical | 118989 |
Out to Review | Original | A | 6/27/2000 | DAVEL | DAVEL | jack thomas | | Out to Review | 118991 |
Construction | Original | A | 6/19/2000 | SEAN | SEAN | Approved as corrected. | | Construction | 118983 |
Out to Review | Original | A | 6/19/2000 | JAN | JAN | JACK THOMAS CHECKED OUT TO TAKE TO SEAN ON WALK THRU | | Out to Review | 118990 |
Electrical | Original | A | 6/6/2000 | JERRY | JERRY | | | Electrical | 118985 |
Plumbing | Original | D | 6/3/2000 | BOB | BOB | PROVIDE ... PLUMBING FIXTURE COUNT PER SECTION 413 OC 1997 UPC AS AMMENDED. 2) PROPER VENT SIZE. 3) CLEAN OUT. + MORE | | Plumbing | 118993 |
Mechanical | Original | D | 6/3/2000 | BOB | BOB | PROVIDE ... 1) FIRE/SMOKE & RADIATION DAMPERS + ACCESS & LABELING. 2) INFORMATION ON EXHAUST @ MODEL SHOP + MORE | | Mechanical | 118988 |
Construction | Original | D | 5/30/2000 | SEAN | SEAN | Elevator lobby required 1st floor. Provide 2 exits from large unoccupied space. Boxing yourself in. Walk through Ok. | | Construction | 118984 |