Fire | Original | A | 4/23/2003 | TERESA | TERESA | 4-15-03 SMC (plan #20030400) | | Fire | 182991 |
Zoning/Planning | Original | A | 4/23/2003 | TERESA | TERESA | 4-17-03 DMT | | Zoning/Planning | 182999 |
Out to Review | Original | A | 4/17/2003 | TIMC | TIMC | | | Out to Review | 182996 |
Construction | Original | A | 4/17/2003 | TIMC | TIMC | | | Construction | 182987 |
Out to Review | Original | A | 4/17/2003 | RUSSELL | RUSSELL | Paul Rue | | Out to Review | 182995 |
Plumbing | Original | A | 4/17/2003 | RUSSELL | RUSSELL | | | Plumbing | 182997 |
Electrical | Original | A | 4/10/2003 | JERRY | JERRY | as corrected | | Electrical | 182990 |
Out to Review | Original | A | 4/2/2003 | JERRY | JERRY | terry's office | | Out to Review | 182994 |
Plumbing | Original | D | 3/31/2003 | RUSSELL | RUSSELL | Shower stall installation of prefab or site build unit ?, if site built provide floor slope per '97 UPC, is curb recessed ?, how providing ?, dishwasher shall be connected by air gap fitting, water connection at therapy tub to a fill faucet ? thermostatic mixing valve ?, hard pipe connection to tub ? backflow protection required ?, floor sink size to be adequate to prevent flooding or splashing when draining therapy tub, handicapped shower unit shall have valve and controls located per '97 UPC section 412.11 | | Plumbing | 182998 |
Mechanical | Original | N | 3/31/2003 | RUSSELL | RUSSELL | None shown (issue no permit) | | Mechanical | 182992 |
Construction | Original | D | 3/31/2003 | TIMC | TIMC | Specify if laundry rooms are existing or new. Meet 1-hr seperation requirements if new. Walk-thru ok. | | Construction | 182989 |
Construction | Original | / | 3/31/2003 | TIMC | TIMC | | | Construction | 182986 |
Out to Review | Original | A | 3/26/2003 | ANGELA | ANGELA | paul from nakai arch. picked up plans. | | Out to Review | 182993 |
Construction | Original | D | 3/26/2003 | TIMC | TIMC | Occupancy classification incorrect. Recalculate allowable area based on new classification and mixed use. No further review. | | Construction | 182988 |
Zoning/Planning | Original | D | 3/20/2003 | ANGELA | ANGELA | dmt 3-20-03 | | Zoning/Planning | 183001 |
Zoning/Planning | Original | D | 3/19/2003 | CSZONING | CSZONING | This appears to be a Human Service Establishment or Facility. The latter requires a conditional use with the development plan (DP). The DP is 96-279, which is expired. Financial Assurance associated with this DP still needs to be collected. Off-street parking, exterior lighting and other site improvements may need to be reviewed. Contact the main planning office at 30 S. Nevada for a pre-application meeting to discuss these issues with the Sr. Planners who may have worked on this project previously to determine whether a conditional use is required, whether the expired development plan requires an amendment or if this is a straight site review requiring parking calculations per code to be met. Current submittal does not provide parking calculations. See attached pre-application. DMT (Denise Tortorice 385-5099). | | Zoning/Planning | 183000 |