Electrical | Original | A | 2/2/2004 | KYE | KYE | Per Terry Schneider, approved revisions. | | Electrical | 184800 |
Apps & Permits | Original | A | 5/23/2003 | TERESA | TERESA | | | Apps & Permits | 184793 |
Health Dept. | Original | A | 5/23/2003 | TERESA | TERESA | 5-22-03 DF | | Health Dept. | 184808 |
Traffic Engr. | Original | A | 5/23/2003 | TERESA | TERESA | 5-22-03 TR Need to escrow $6000 prior to CO for off site traffic improvements | | Traffic Engr. | 184816 |
Water Division | Original | A | 5/23/2003 | TERESA | TERESA | 5-23-03 PB | | Water Division | 184820 |
Waste Water Div | Original | A | 5/23/2003 | TERESA | TERESA | 5-22-03 PB | | Waste Water Div | 184817 |
Out to Review | Original | A | 5/22/2003 | SEAN | SEAN | Dave Singleton - Nunn | | Out to Review | 184813 |
City Engr. | Original | A | 5/22/2003 | SEAN | SEAN | RA 5/22/03 | | City Engr. | 184794 |
Elevators | Original | A | 5/22/2003 | SEAN | SEAN | | | Elevators | 184802 |
Electrical | Original | A | 5/22/2003 | TERRY | TERRY | | | Electrical | 184799 |
Plumbing | Original | A | 5/22/2003 | KYE | KYE | | | Plumbing | 184814 |
Mechanical | Original | A | 5/22/2003 | KYE | KYE | | | Mechanical | 184810 |
Construction | Original | A | 5/20/2003 | SEAN | SEAN | | | Construction | 184796 |
Fire | Original | A | 5/20/2003 | SEAN | SEAN | VLC 5/20/03 | | Fire | 184805 |
Out to Review | Original | A | 4/7/2003 | JAN | JAN | JACOB MCKINNELL 473-8446 LK ARCHITECTS | | Out to Review | 184812 |
Fire | Original | D | 4/1/2003 | ANGELA | ANGELA | smc 3-31-03 20020483 20030345 | | Fire | 184806 |
Plumbing | Original | D | 3/18/2003 | KYE | KYE | Need accurate occupancy load to calculate fixture count. Qouestion on solids interceptor shown with sink in county storage area. | | Plumbing | 184815 |
Mechanical | Original | D | 3/18/2003 | KYE | KYE | Shafting and damper problems for atrium, restroom exhaust, more. | | Mechanical | 184811 |
Electrical | Original | D | 3/18/2003 | TERRY | TERRY | EMERGENCY GENERATOR IS SMALLER THAN CALCULATED LOAD, NEED SHUT DOWN PROTECTION FOR CHILLER ROOM ELECTRICAL, SEVERAL RECEPS AND LIGHTS NOT CIRCUITED, WALK THROUGH OK | | Electrical | 184801 |
Elevators | Original | D | 3/13/2003 | DAVEL | DAVEL | no hoistway dampers | | Elevators | 184803 |
Waste Water Div | Original | D | 3/6/2003 | CSUREVIEW | CSUREVIEW | Need approved utility plan. | | Waste Water Div | 184819 |
Water Division | Original | D | 3/6/2003 | WATERSVC | WATERSVC | Need Fire Dept.'s approval of Regional Building set.
Need approved utility plan. | | Water Division | 184822 |
Electric Div. | Original | A | 3/6/2003 | TERESA | TERESA | 3-5-03 CW | | Electric Div. | 184798 |
Health Dept. | Original | D | 3/6/2003 | TERESA | TERESA | 3-5-03 Contact air quality for construction activity permit | | Health Dept. | 184809 |
Water Division | Original | D | 3/6/2003 | TERESA | TERESA | 3-5-03 MEF Need approved utility plan | | Water Division | 184821 |
Waste Water Div | Original | D | 3/6/2003 | TERESA | TERESA | 3-5-03 MEF Need approved utility plan | | Waste Water Div | 184818 |
City Engr. | Original | D | 3/5/2003 | CSENGINEER | CSENGINEER | Requires an Approved Grading and Erosion Control Plan. | | City Engr. | 184795 |
Zoning/Planning | Original | A | 3/5/2003 | ANGELA | ANGELA | dmt 3-3-3- per ar dp 02-187 a1 03 exzterior lighting per dp final ls is attached. | | Zoning/Planning | 184824 |
Zoning/Planning | Original | A | 3/3/2003 | CSZONING | CSZONING | PER AR DP 02-187-A1(03). FINAL LS PLAN IS ATTACHED. EXTERIOR LIGHTING TO BE PER DP. | | Zoning/Planning | 184823 |
Construction | Original | D | 2/28/2003 | SEAN | SEAN | see set. | | Construction | 184797 |
Enumeration | Original | A | 2/27/2003 | MINDY | MINDY | Car wash address is 2886. | | Enumeration | 184804 |
Floodplain | Original | A | 2/27/2003 | JEANNINE | JEANNINE | | | Floodplain | 184807 |