Required Departments: 5
|
|
|
Log Entries: 13
|
|
Construction | Original | A | 3/12/2004 | SHELLEY | SHELLEY | 3/3/04 - timc | | Construction | 197736 | Fire | Original | A | 3/12/2004 | SHELLEY | SHELLEY | 3/11/04 - VLC | | Fire | 197740 | Fire | Original | / | 2/24/2004 | JOHNJ | JOHNJ | | | Fire | 197739 | Construction | Original | / | 2/24/2004 | JOHNJ | JOHNJ | | | Construction | 197735 | Plumbing | Original | A | 2/24/2004 | RUSSELL | RUSSELL | | | Plumbing | 197746 | Mechanical | Original | A | 2/24/2004 | RUSSELL | RUSSELL | | | Mechanical | 197742 | Out to Review | Original | A | 2/10/2004 | SHELLEY | SHELLEY | TED SCHENDT | | Out to Review | 197745 | Fire | Original | D | 2/10/2004 | SHELLEY | SHELLEY | 02/09/04 - smc | | Fire | 197741 | Electrical | Original | A | 1/22/2004 | JERRY | JERRY | | | Electrical | 197738 | Out to Review | Original | A | 1/21/2004 | JERRY | JERRY | jerry | | Out to Review | 197744 | Plumbing | Original | D | 1/20/2004 | RUSSELL | RUSSELL | Size piping and comb. waste & vent piping inadequate | | Plumbing | 197747 | Mechanical | Original | D | 1/20/2004 | RUSSELL | RUSSELL | See comments on drawings, for routing location of piping to be over Refigeration Machinery Room | | Mechanical | 197743 | Construction | Original | D | 1/12/2004 | TIMC | TIMC | Provide code study. Specify mezz use. Provide 1-hr rated ceiling in mach. room. Address other comments as noted on drawings. No walk-thru. | | Construction | 197737 |
|
| |
|