Waste Water Div | Original | A | 7/21/2005 | JAN | JAN | Duane Hanson 7-21-05 | | Waste Water Div | 223733 |
Zoning/Planning | Original | A | 7/21/2005 | JAN | JAN | Palmer Lake - Della | | Zoning/Planning | 223734 |
Out to Review | Original | A | 7/8/2005 | OWEN | OWEN | al fritz 332-4088 | | Out to Review | 223727 |
Elevators | Original | A | 7/6/2005 | SEAN | SEAN | Tom Evancich 6/24/05 | | Elevators | 223710 |
Fire | Original | A | 7/6/2005 | SEAN | SEAN | Approved for PLVFD per letter from Jeff Edwards, Palmer Lake Fire Marshal. Installation of required water tanks will require separate plans and permits. | | Fire | 223712 |
Mechanical | Original | A | 7/5/2005 | KYE | KYE | | | Mechanical | 223717 |
Mechanical | Original | D | 6/23/2005 | KYE | KYE | Provide mechanical make up air to laundry room interlocked with equipment. Exhausting 1,920 cfm, transfer grill only open to an enclosed hallway. | | Mechanical | 223721 |
Plumbing | Original | A | 6/23/2005 | KYE | KYE | | | Plumbing | 223730 |
Plumbing | Original | / | 6/22/2005 | ANGELA | ANGELA | | | Plumbing | 223729 |
Mechanical | Original | / | 6/22/2005 | ANGELA | ANGELA | | | Mechanical | 223716 |
Health Dept. | Original | A | 6/20/2005 | HEALTHDEPT | HEALTHDEPT | Plans are approved as corrected. Please contact CN at (719) 578-3289 for questions or concerns. | | Health Dept. | 223714 |
Out to Review | Original | A | 6/20/2005 | JEREMY | JEREMY | builder for revisions to plan in building | | Out to Review | 223726 |
Electrical | Original | A | 6/17/2005 | JERRY | JERRY | | | Electrical | 223708 |
Plumbing | Original | D | 6/15/2005 | KYE | KYE | Only need Health Dept. approval, rest ok providing size of water heater does not increase from 720 MBH. | | Plumbing | 223732 |
Mechanical | Original | D | 6/15/2005 | KYE | KYE | Still need cut sheets/info for dryers and fireplace. Added note "only damper required is a SMOKE DAMPER at the transfer grill to the laundry room". | | Mechanical | 223720 |
Construction | Original | A | 6/6/2005 | TIMC | TIMC | | | Construction | 223703 |
Electrical | Original | / | 6/1/2005 | ANGELA | ANGELA | revised plan 06-01-05 | | Electrical | 223707 |
Plumbing | Original | / | 6/1/2005 | ANGELA | ANGELA | | | Plumbing | 223728 |
Mechanical | Original | / | 6/1/2005 | ANGELA | ANGELA | | | Mechanical | 223715 |
Construction | Original | / | 6/1/2005 | ANGELA | ANGELA | | | Construction | 223702 |
Out to Review | Original | A | 5/12/2005 | KEN | KEN | al fritts | | Out to Review | 223725 |
Electrical | Original | D | 5/10/2005 | GARYL | GARYL | energy code calculations | | Electrical | 223709 |
Plumbing | Original | D | 5/9/2005 | KYE | KYE | P2.01 1. Showing a third dryer with no gas pipe, electric? P2.02 1. Gas note refers to sheet M2.03. Not included in set. P2.03 Greasea interceptor appears undersized, complete attached sizing formula and return. Drain dishwasher and 3 compartment sink per detail. Kitchen equipment sheets are not in set. Are clothes washing machines domestic size or commercial? If commercial provide cut sheets showing GPM dishcharge. Health Dept. approval required prior to plumbing sign off. | | Plumbing | 223731 |
Mechanical | Original | D | 5/9/2005 | KYE | KYE | M2.02 1. Provide hood info to include: Manufactured or site built? UL listing if manufactured. Sixes of: hoods, openings, all associated ductwork. 2. Provide Rtu info including: Total Cfm, outside air Cfm complying with Table 403.3, 2003 IMC, add note to provide a balance report confirming outside air quantity and kitchen performance. 3. Provide fireplace vent details, fireplace is 50 MBH, 12" appears considerably oversized. | | Mechanical | 223719 |
Mechanical | Original | D | 5/9/2005 | KYE | KYE | M2.01 1. Laundry is incidental use enclosed by smoke barrier, S/A duct has opening into room, requires smoke dampers at duct penetrations. 2. Provide cut sheets for dryers showing vent size, cfm, and vent length allowed. 3. Provide symbol schedule, unsure if dampers are smoke or fire. 4. Electrical equipment rooms unless sprinkled require fire dampers at wall and/or ceiling penetrations. 5. Elevator " " " " " " " " " " 6. Architect showing a 1-hr wall around banquet room, fire dampers required for wall penetrations. 7. Unclear where banquet room ceiling is rated, could require radiation dampers in diffusers. 8. Provide a diffuser schedule. 9. Is duct labeled "Relief air" a high combustion air duct? if so must terminate within 12" of the ceiling. | | Mechanical | 223718 |
Construction | Original | D | 5/5/2005 | TIMC | TIMC | Elevator machinery room is required to be rated the same as the hostway rating regardless of sprinklers, 1-hr rating required. Missing panic hardware on many exit doors. Address other comments as noted on plans. No walk-thru. | | Construction | 223706 |
Out to Review | Original | A | 4/28/2005 | JAN | JAN | Al Fritts 332-4088 | | Out to Review | 223724 |
Construction | Original | D | 4/27/2005 | TIMC | TIMC | Structural must be designed to same code, 03' IBC, as architectural is. No review performed on Structural sheets. Show all grab bar and fixture heights and dim's. Provide an exiting/fire wall code sheet specifying why walls are being rated, if electrical rooms are sprinklered, and showing location of existing area seperation walls (fire walls now). Exiting and fire walls have not been reviewed. No further review by other departments can be performed at this time because my review is incomplete due to items listed above. Address other comments as noted on plans. No walk-thru. | | Construction | 223705 |
Out to Review | Original | A | 4/25/2005 | SHELLEY | SHELLEY | al fritts. | | Out to Review | 223723 |
Out to Review | Original | A | 4/22/2005 | ANGELA | ANGELA | out to Al Fritts 332-4088 | | Out to Review | 223722 |
Construction | Original | D | 4/19/2005 | TIMC | TIMC | A-2 are only allowed 1 story in VB construction (use sprinklers per chapter 5 for height increase). Must provide sprinkler system per section 903.3.1.1 to use for area and height increase. Specify all variables and provide allowable area calc's per section 506. No further review performed. No walk-thru. | | Construction | 223704 |
Floodplain | Original | A | 3/31/2005 | JEANNINE | JEANNINE | | | Floodplain | 223713 |
Enumeration | Original | N | 3/31/2005 | MARLENE | MARLENE | This property is in Palmer Lake. | | Enumeration | 223711 |