Required Departments: 6
|
|
|
Log Entries: 11
|
|
Hazmat/High Pil | Original | N | 12/20/2005 | MINDY | MINDY | 12/19/04 vc | | Hazmat/High Pil | 232374 | Fire | Original | A | 12/20/2005 | CSFIRE | CSFIRE | 12/19/04 vc | | Fire | 232373 | Electrical | Original | A | 12/9/2005 | GARYL | GARYL | | | Electrical | 232372 | Out to Review | Original | A | 12/8/2005 | GARYL | GARYL | GARYL | | Out to Review | 232378 | Out to Review | Original | A | 12/8/2005 | GARYL | GARYL | | | Out to Review | 232377 | Mechanical | Original | A | 12/7/2005 | BOB | BOB | OK AS NOTED, SHELL BLDG. | | Mechanical | 232375 | Plumbing | Original | N | 12/7/2005 | BOB | BOB | NONE SHOWN. DO NOT ISSUE PERMIT | | Plumbing | 232379 | Construction | Original | A | 12/5/2005 | TIMC | TIMC | | | Construction | 232369 | Out to Review | Original | A | 11/29/2005 | SHELLEY | SHELLEY | brian burns, 265-5545 | | Out to Review | 232376 | Construction | Original | D | 11/23/2005 | TIMC | TIMC | What is the building type of construction, plans show both IIA and IIB. Is remodeled occupany going to be a B or an A occupancy? Redo allowable area calculations if its an A occpauncy. No further review performed. No walk-thru. | | Construction | 232371 | Construction | Original | D | 11/16/2005 | ROGER | ROGER | Plans indicate change of use, revise to reflect no change of use at this time. Also refernce 97 UBC and have "Not for Construction" Stamp. | | Construction | 232370 |
|
| |
|