Required Departments: 7
|
|
|
Log Entries: 13
|
|
Out to Review | Original | A | 1/3/2006 | TIMC | TIMC | | | Out to Review | 232817 | Hazmat/High Pil | Original | N | 1/3/2006 | TIMC | TIMC | | | Hazmat/High Pil | 232813 | Fire | Original | N | 1/3/2006 | CSFIRE | CSFIRE | | | Fire | 232812 | Electrical | Original | A | 1/3/2006 | TERRY | TERRY | done by Gary Laxson | | Electrical | 232809 | Mechanical | Original | A | 1/3/2006 | RUSSELL | RUSSELL | | | Mechanical | 232814 | Construction | Original | A | 12/29/2005 | TIMC | TIMC | | | Construction | 232807 | Plumbing | Original | A | 12/27/2005 | KYE | KYE | | | Plumbing | 232818 | Out to Review | Original | A | 12/23/2005 | OWEN | OWEN | Tuesday Plan Room 12-23-05 | | Out to Review | 232816 | Electrical | Original | D | 12/21/2005 | JERRY | JERRY | ENERGY CODE CALCULATIONS | | Electrical | 232810 | Mechanical | Original | D | 12/19/2005 | RUSSELL | RUSSELL | Exhaust fan shall be provided with a backdraft damper, O.A. short due to 75 cfm O.A. req'd for toilet room per '03 IMC Table 403.3, field label condensing unit as to unit/asrea served, verify SD in R.A. duct, provide statement on drawings if space is part of mall smoke evac or not, | | Mechanical | 232815 | Plumbing | Original | D | 12/19/2005 | KYE | KYE | | | Plumbing | 232819 | Construction | Original | D | 12/16/2005 | TIMC | TIMC | 2nd exit may not pass through the stock room unless a half height wall seperating the stock room and egress path is provided. Provide 18" vertical grab bar in HC restrooms. Walk-thru ok. | | Construction | 232808 | Enumeration | Original | A | 12/12/2005 | MARLENE | MARLENE | | | Enumeration | 232811 |
|
| |
|