Required Departments: 6
|
|
|
Log Entries: 14
|
|
Plumbing | Original | A | 9/13/2006 | KYE | KYE | revised P-1, 2nd lav removed from mens restroom, not required by occupancy load, floor drain shown on first plan was not existing in existing restroom. | | Plumbing | 241980 | Plumbing | Original | / | 9/13/2006 | KYE | KYE | | | Plumbing | 241978 | Plumbing | Original | A | 5/23/2006 | KYE | KYE | | | Plumbing | 241979 | Mechanical | Original | A | 5/23/2006 | RUSSELL | RUSSELL | | | Mechanical | 241973 | Out to Review | Original | A | 5/22/2006 | GARYL | GARYL | KEN 332-2006 | | Out to Review | 241977 | Electrical | Original | A | 5/22/2006 | GARYL | GARYL | CORRECTIONS MADE | | Electrical | 241969 | Plumbing | Original | D | 5/11/2006 | KYE | KYE | P-1 1. DWV is unclear as shown and does not appear to be to code. P-2 1. Water detail shows drain pan and drain to mop sink, W/H is in mechanical room on floor, update note. | | Plumbing | 241981 | Out to Review | Original | A | 5/11/2006 | GARYL | GARYL | JIM CASSIO | | Out to Review | 241976 | Electrical | Original | D | 5/11/2006 | GARYL | GARYL | NEED 1-LINE ON EXISTINF SERVICE ANF WHERE PANEL IS POWERED FROM | | Electrical | 241970 | Mechanical | Original | D | 5/11/2006 | RUSSELL | RUSSELL | O.A> ventilation inadequate in myt/conf, room | | Mechanical | 241974 | Out to Review | Original | A | 5/11/2006 | RICH | RICH | JIM CASSIO | | Out to Review | 241975 | Hazmat/High Pil | Original | N | 5/11/2006 | RICH | RICH | LSP RI | | Hazmat/High Pil | 241972 | Fire | Original | N | 5/11/2006 | CSFIRE | CSFIRE | LSP RI | | Fire | 241971 | Construction | Original | A | 5/11/2006 | RICH | RICH | APPROVED RICH | | Construction | 241968 |
|
| |
|