Construction | Original | A | 6/7/2007 | RICH | RICH | approved splice to B1 model changes at master bath , B3 model opt | | Construction | 244399 |
Construction | Original | / | 6/7/2007 | RICH | RICH | | | Construction | 244397 |
Mechanical | Original | A | 6/7/2007 | RUSSELL | RUSSELL | Revised mechanical, added bathroom | | Mechanical | 244422 |
Mechanical | Original | A | 2/16/2007 | RUSSELL | RUSSELL | | | Mechanical | 244421 |
Apps & Permits | Original | A | 8/2/2006 | ANGELA | ANGELA | brett veltman approved phase one only for this permit. which is building 2, 17 bay garage building, 7 bay garage building and mail kiosk. | | Apps & Permits | 244392 |
Apps & Permits | Original | D | 8/2/2006 | ANGELA | ANGELA | utility receipt in hand. | | Apps & Permits | 244393 |
Zoning/Planning | Original | A | 8/2/2006 | ANGELA | ANGELA | buv 8-1-06 | | Zoning/Planning | 244443 |
Health Dept. | Original | A | 8/1/2006 | ANGELA | ANGELA | SS 7-25-06 | | Health Dept. | 244417 |
City Engr. | Original | A | 8/1/2006 | ANGELA | ANGELA | LSM 8-1-06 | | City Engr. | 244394 |
Out to Review | Original | A | 8/1/2006 | JEREMY | JEREMY | Rick Taylor | | Out to Review | 244437 |
Zoning/Planning | Original | D | 8/1/2006 | JEREMY | JEREMY | BRET V 7-25-06 SEE PLANS FOR COMMENTS | | Zoning/Planning | 244445 |
Fire | Original | A | 8/1/2006 | CSFIRE | CSFIRE | VLC 7-17-06 | | Fire | 244411 |
Hazmat/High Pil | Original | N | 8/1/2006 | JEREMY | JEREMY | VLC 7-17-06 | | Hazmat/High Pil | 244416 |
Traffic Engr. | Original | A | 8/1/2006 | JEREMY | JEREMY | SLS 7-25-06 | | Traffic Engr. | 244439 |
Health Dept. | Original | D | 8/1/2006 | JEREMY | JEREMY | CN 7-31-06 | | Health Dept. | 244418 |
City Engr. | Original | D | 8/1/2006 | JEREMY | JEREMY | LAM 7-31-06 | | City Engr. | 244395 |
Construction | Original | A | 7/27/2006 | TIMC | TIMC | | | Construction | 244398 |
Construction | Original | / | 7/26/2006 | SHELLEY | SHELLEY | revised for construction, put on Tim C desk | | Construction | 244396 |
Out to Review | Original | A | 7/26/2006 | JAN | JAN | Rick Taylor | | Out to Review | 244436 |
Out to Review | Original | A | 7/26/2006 | JOHNJ | JOHNJ | TO FINISH BIN {READY FOR REVISIONS BY CONTRACTOR} BRETT VELTMAN HAS DISCUSSED THIS PROJECT WITH JOHN IN DETAIL. THE CONTRACTOR NEEDS TO MEET WITH JOHN J ON HOW AND WHEN TO BREAK THESE PLANS DOWN INTO 3 DIFFERENT SETS FOR {PHASES} AS THE PLANS WILL NOT BE APPROVED BY ZONING FOR THE ENTIRE PROJECT BUT WILL BE APPROVED IN PHASES. JOHN HAS A PHASE SITE PLAN AT DESK. THANKS JOHN | | Out to Review | 244435 |
Mechanical | Original | A | 7/7/2006 | RUSSELL | RUSSELL | Approved as noted on plans, put in Fire Bin | | Mechanical | 244420 |
Construction | Original | D | 7/5/2006 | TIMC | TIMC | Please have engineer of record review trusses submitted: Trusses have not been designed to the correct live and dead loadings per design loads stated on sheet S1.1. Specify all girder # plys and bottom cord size and type on framing plans. No walk-thru. | | Construction | 244403 |
Out to Review | Original | A | 6/14/2006 | JAN | JAN | Rich Costa 290-5067 | | Out to Review | 244434 |
Mechanical | Original | D | 6/14/2006 | DALEH | DALEH | need stamped approved res checks from construction prior to mech. review need room by room heat loss heat gain calculation sheets (Wright soft , Ellite etc....) need manufacturers data sheets on all equipment (A.H.U. , COIL , BLOWER DATA ) no walk thru | | Mechanical | 244425 |
Construction | Original | D | 6/9/2006 | TIMC | TIMC | Energy code cert./calc's need to be revised to 03' IECC (Rescheck). Floor and roof trusses must be labeled on floor/roof framing plans that indicate all framing information, truss manufacturer layouts are not permitted. Need to add additional notes to the 2-hr Fire Wall detail shown on sheet A-35. No walk-thru. | | Construction | 244402 |
Mechanical | Original | / | 6/9/2006 | ANGELA | ANGELA | skip Zoning please , per architect.. straight to construction. | | Mechanical | 244419 |
Out to Review | Original | A | 6/8/2006 | GARYL | GARYL | TOMMY 720-234-4728 | | Out to Review | 244433 |
Electrical | Original | A | 6/8/2006 | GARYL | GARYL | CORRECTIONS MADE | | Electrical | 244406 |
Out to Review | Original | A | 5/31/2006 | SHELLEY | SHELLEY | rick taylor, 303-783-9684 | | Out to Review | 244432 |
Electrical | Original | D | 5/30/2006 | GARYL | GARYL | OEP PANEL DESCRIPTION ON E3.5 SHOW 2P60 FOR FURNACE, PANEL FEEDER CALCS SHOW MOTOR ONLY. 10 A/C UNITS SHOWN FOR 8 UNITS NEED EXPLANATION. WHAT IS THE MAIN BREAKER SIZE OF PANEL(S) EP? CALLED GM SPENCER, LEFT CELL PHONE-NO REPLY . SENT TO FINISHED BIN , SEE ATTACHED | | Electrical | 244408 |
Electrical | Original | / | 5/30/2006 | GARYL | GARYL | PLAN TABLE | | Electrical | 244404 |
Mechanical | Original | D | 5/26/2006 | DALEH | DALEH | need to design with IECC 2003,IMC 2003, IFGC 2003, RBC 2005 EDITION how are you protecting the rated wall with side wall exhaust fans still need to perform complete re-review | | Mechanical | 244424 |
Construction | Original | D | 5/17/2006 | TIMC | TIMC | Show location of all the floor and roof trusses on floor/roof framing plans and label per truss manufacturer id's. Provide copies of all premanufactured trusses. Need to specify if the 2-hr rated wall at the garage/condo common wall, is either a Fire Wall, Fire Partition or Fire Barrier. If its a Fire Wall then you must meet the requirements of horizontal and vertical continuity, see section 705.1. Provide details to show how you are meeting these requirements. In addition you need to clearly indicate on code study that you are using a Fire Wall to seperate into different buildings. Provide energy code cert./calc's. No walk-thru. | | Construction | 244401 |
Out to Review | Original | A | 5/16/2006 | OWEN | OWEN | To Construction 5-16-06 | | Out to Review | 244431 |
Out to Review | Original | A | 5/16/2006 | MARLENE | MARLENE | Tommy | | Out to Review | 244430 |
Floodplain | Original | A | 5/16/2006 | MARLENE | MARLENE | | | Floodplain | 244413 |
Enumeration | Original | A | 5/16/2006 | MARLENE | MARLENE | | | Enumeration | 244409 |
Out to Review | Original | A | 5/16/2006 | OWEN | OWEN | To Enumeration 5-16-06 | | Out to Review | 244429 |
Out to Review | Original | A | 4/14/2006 | JEFFREY | JEFFREY | Rick - 303-783-9684 | | Out to Review | 244428 |
Fire | Original | D | 4/14/2006 | CSFIRE | CSFIRE | 04/12/06 | | Fire | 244412 |
Electrical | Original | D | 3/29/2006 | JERRY | JERRY | CIRCUIT NUMBERS,SHOW LOCATION OF ALL A/C'S AND A RECEPTACLE FROM THE UNIT IT SERVES,ID ALL GFCI RECEPTACLES | | Electrical | 244407 |
Electrical | Original | A | 3/28/2006 | JERRY | JERRY | JERRY | | Electrical | 244405 |
Plumbing | Original | A | 3/28/2006 | KYE | KYE | | | Plumbing | 244438 |
Mechanical | Original | D | 3/13/2006 | DARYL | DARYL | See notes in set | | Mechanical | 244423 |
Construction | Original | D | 2/8/2006 | TIMC | TIMC | See accessible unit questions. Provide a breakdown of qty of points accieved, per 95-105 requirements. Add in square footage of garages to allowable area calcs for building Type II. Mezz shown on plans does not meet mezz requirements, is actually a 4th floor. Use sprinklers for story increase. Provide blocking for 18" vertical grab bars in HC restrooms. Specify which HC units are type A and B and label according to 9-5-105 definitions. Specify fire barrier at garage to Condo wall. Provide copy of soils report. Specify design deads loads, and PG and Pf. Unit balconies are required to be designed to 100 psf. Provide calc's to use method #1 for energy code cert. Address other comments as noted on plans. No walk-thru. | | Construction | 244400 |
Traffic Engr. | Original | D | 1/20/2006 | CSTRAFFIC | CSTRAFFIC | Please provide a ck for $20,000 as agreed upon towards the cost of the Tutt and Bridlespur signal. Please address the other comments that Traffic Engineering has attached to the front of the plans. Any questions please feel free to contact me at 385-5908. Stacey | | Traffic Engr. | 244440 |
Zoning/Planning | Original | D | 1/19/2006 | CSZONING | CSZONING | ATTACH RECORDED PLAT. FA REQ'D FOR PVT STREETS AND PROJECT LS. | | Zoning/Planning | 244444 |
Water Division | Original | D | 1/18/2006 | SHELLEY | SHELLEY | 1/17/06 - blz | | Water Division | 244442 |
Waste Water Div | Original | D | 1/18/2006 | SHELLEY | SHELLEY | 1/17/06 - blz | | Waste Water Div | 244441 |
Gas/Elec. Utils | Original | D | 1/18/2006 | SHELLEY | SHELLEY | 1/17/06 - blz | | Gas/Elec. Utils | 244415 |
Out to Review | Original | A | 1/13/2006 | SHELLEY | SHELLEY | Monday plan check | | Out to Review | 244427 |
Out to Review | Original | A | 1/11/2006 | JEANNINE | JEANNINE | | | Out to Review | 244426 |
Floodplain | Original | D | 1/11/2006 | JEANNINE | JEANNINE | provide copy of final recorded plat | | Floodplain | 244414 |
Enumeration | Original | D | 1/10/2006 | MARLENE | MARLENE | Copy of Final Recorded Plat required. Contact Elaine Medina at Post Office 570-5415 for unit assignments. | | Enumeration | 244410 |