Mechanical | Original | A | 10/30/2006 | DALEH | DALEH | spliced in new 4m-2 | | Mechanical | 247313 |
Out to Review | Original | A | 9/19/2006 | ROGER | ROGER | Deb Reinhardt | | Out to Review | 247321 |
Construction | Original | A | 9/19/2006 | ROGER | ROGER | Approved changes | | Construction | 247300 |
Out to Review | Original | A | 9/19/2006 | RUSSELL | RUSSELL | | | Out to Review | 247320 |
Mechanical | Original | A | 9/19/2006 | RUSSELL | RUSSELL | | | Mechanical | 247312 |
Out to Review | Original | A | 9/19/2006 | KIM | KIM | Deb Reinhardt 632-5355 | | Out to Review | 247319 |
Electrical | Original | A | 9/15/2006 | GARYL | GARYL | CORRECTIONS MADE---FINISHED BIN 9/15/6------------ | | Electrical | 247304 |
Electrical | Original | / | 9/11/2006 | ANGELA | ANGELA | revised only for electrical, please do not send to mechanical, but put in finish bin when completed with review. | | Electrical | 247303 |
Out to Review | Original | A | 9/11/2006 | GARYL | GARYL | DEB 385-0137 | | Out to Review | 247318 |
Electrical | Original | D | 9/11/2006 | GARYL | GARYL | ALL CORRECTIONS MADE EXCEPT CHECKING IECC SHEETS, TOO LARGE FOR A WALK THRU | | Electrical | 247306 |
Electrical | Original | / | 9/11/2006 | GARYL | GARYL | | | Electrical | 247302 |
Enumeration | Original | A | 9/8/2006 | MARLENE | MARLENE | | | Enumeration | 247308 |
Out to Review | Original | A | 9/8/2006 | KIM | KIM | Deb Reinhardt 632-5355 | | Out to Review | 247317 |
Plumbing | Original | A | 9/8/2006 | KYE | KYE | | | Plumbing | 247322 |
Mechanical | Original | D | 8/31/2006 | RUSSELL | RUSSELL | See plans for comments | | Mechanical | 247314 |
Out to Review | Original | A | 8/30/2006 | DAVID | DAVID | | | Out to Review | 247316 |
Electrical | Original | D | 8/30/2006 | DAVID | DAVID | Note #8 sheet E3.0 show #14 gauge wire panel schedule shows a 20 amp circuit. 2. IECC worksheets fixture designations do not match the luminaire schedule in plans. 3. Show panels as existing on panel schedules (some show it some do not). | | Electrical | 247305 |
Enumeration | Original | D | 8/29/2006 | MARLENE | MARLENE | Provide floor plans showing existing Suite numbers. Clarify with Enumerations how many tenants/Suite numbers are required for 4th floor. | | Enumeration | 247309 |
Out to Review | Original | A | 8/29/2006 | RICH | RICH | ian | | Out to Review | 247315 |
Hazmat/High Pil | Original | N | 8/29/2006 | RICH | RICH | n/a rich | | Hazmat/High Pil | 247311 |
Fire | Original | N | 8/29/2006 | CSFIRE | CSFIRE | lsp rich | | Fire | 247310 |
Construction | Original | A | 8/29/2006 | RICH | RICH | approved rich | | Construction | 247299 |
Construction | Original | D | 8/24/2006 | RICH | RICH | building type 1A, remove handicapped restroom details that do not apply to scope of work, rich | | Construction | 247301 |
Enumeration | Original | A | 8/24/2006 | HEATHER | HEATHER | out to review with Ian | | Enumeration | 247307 |