Health Dept. | Original | A | 10/4/2006 | SHELLEY | SHELLEY | 10/4/06 - lsp | | Health Dept. | 248132 |
Fire | Original | A | 10/4/2006 | CSFIRE | CSFIRE | 9/22/06 - vlc | | Fire | 248131 |
Out to Review | Original | A | 10/3/2006 | GARYL | GARYL | KEN 930-7245 | | Out to Review | 248138 |
Electrical | Original | A | 10/3/2006 | GARYL | GARYL | | | Electrical | 248125 |
Plumbing | Original | A | 9/28/2006 | KYE | KYE | | | Plumbing | 248140 |
Out to Review | Original | A | 9/28/2006 | JERRY | JERRY | KEN 930-7245 | | Out to Review | 248137 |
Electrical | Original | D | 9/28/2006 | JERRY | JERRY | IECC CALCULATIONS,FIXTURE SCHEDULE AND FIXTURE COUNT TO MATCH AND COMPLY WITH IECC--KITCHEN TO COMPLY WITH 210.8(B)(2) | | Electrical | 248128 |
Out to Review | Original | A | 9/25/2006 | GARYL | GARYL | KEN WITH YOW | | Out to Review | 248136 |
Electrical | Original | D | 9/25/2006 | GARYL | GARYL | EE STATED ON PRINT THAT IECC IS NOT REQUIRED, MY NOTE...WHERE DID THEY GET THIS INFORMATION FROM? | | Electrical | 248127 |
Plumbing | Original | D | 9/22/2006 | DARYL | DARYL | Just pending health dept approvals | | Plumbing | 248145 |
Plumbing | Original | / | 9/22/2006 | DARYL | DARYL | | | Plumbing | 248139 |
Enumeration | Original | A | 9/15/2006 | MARLENE | MARLENE | | | Enumeration | 248129 |
Plumbing | Original | D | 9/14/2006 | KYE | KYE | 1. Is floor sink new? If so show drain and vent. 2. Show DWV connections for 3 compartment per Section 704.3, 2000 UPC. 3. See Chapter 8, 2000 UPC for indirect waste receptor size and indirect waste line length requirements for traps and vents. 4. Show new water piping with connection to exinting points. 5. Will need Health Dept. approval. 6. Is grease trap existing? | | Plumbing | 248144 |
Mechanical | Original | A | 9/14/2006 | RUSSELL | RUSSELL | | | Mechanical | 248133 |
Construction | Original | A | 9/14/2006 | TIMC | TIMC | | | Construction | 248123 |
Out to Review | Original | A | 9/14/2006 | GARYL | GARYL | KEN WITH YOW | | Out to Review | 248135 |
Electrical | Original | D | 9/14/2006 | GARYL | GARYL | NEED IECC CALC'S AND WORKSHEETS, KITCHEN RECEPTACLES MUST COMPLY WITH NEC 210.8 (B) (2) | | Electrical | 248126 |
Enumeration | Original | D | 9/14/2006 | MARLENE | MARLENE | Provide existing suite numbers on first floor. | | Enumeration | 248130 |
Construction | Original | D | 9/13/2006 | RICH | RICH | provide current code criteria, type 1A bldg | | Construction | 248124 |
Out to Review | Original | A | 9/13/2006 | MINDY | MINDY | Ken w/ YOW | | Out to Review | 248134 |