Mechanical | Original | A | 1/23/2007 | RUSSELL | RUSSELL | Revised mechanical ductwork & gas piping | | Mechanical | 248173 |
Water Division | Original | A | 10/4/2006 | ANGELA | ANGELA | aj 10-03-06 | | Water Division | 248182 |
Construction | Original | A | 9/29/2006 | RICH | RICH | approved rich | | Construction | 248164 |
Out to Review | Original | A | 9/29/2006 | JEREMY | JEREMY | Doug Carr 635-2142 | | Out to Review | 248178 |
Hazmat/High Pil | Original | N | 9/28/2006 | JEREMY | JEREMY | CTH 9-29-06 | | Hazmat/High Pil | 248171 |
Fire | Original | A | 9/28/2006 | CSFIRE | CSFIRE | CTH 9-28-06 | | Fire | 248170 |
Plumbing | Original | A | 9/18/2006 | KYE | KYE | | | Plumbing | 248179 |
Mechanical | Original | A | 9/18/2006 | RUSSELL | RUSSELL | | | Mechanical | 248172 |
Construction | Original | D | 9/18/2006 | TIMC | TIMC | Provide letter from soils engineer to use >1 year old soils report. All else ok. Walk-thru ok. | | Construction | 248166 |
Construction | Original | / | 9/18/2006 | TIMC | TIMC | | | Construction | 248163 |
Enumeration | Original | A | 9/13/2006 | MARLENE | MARLENE | Building # 2 - Sports Center | | Enumeration | 248168 |
Out to Review | Original | A | 8/21/2006 | HEATHER | HEATHER | doug carr 635-2142 | | Out to Review | 248177 |
Electrical | Original | A | 8/17/2006 | GARYL | GARYL | ------------FINISHED BIN 8/17---------------- | | Electrical | 248167 |
Plumbing | Original | D | 8/17/2006 | LARRY | LARRY | Show waste, water and vent to outside of building Floor drains require trap primers Domestic water does not comply with 610.12.1 | | Plumbing | 248180 |
Mechanical | Original | D | 8/17/2006 | RUSSELL | RUSSELL | See plans for comment | | Mechanical | 248174 |
Construction | Original | D | 8/14/2006 | TIMC | TIMC | Provide copy of soils report. Provide letter from engineer to use >1 year old soils report. Provide energency lights and signs in A occupancy. Specify location of panic hardware from lecture hall. Provide 18" vertical grab bar in HC restroom stalls. Provide 90 minute doors at tunnel per 3104.1 and 715.3. Address other comments as noted on plans. No walk-thru. | | Construction | 248165 |
Enumeration | Original | D | 8/1/2006 | JEREMY | JEREMY | PER MK 7-25-06 | | Enumeration | 248169 |
Water Division | Original | D | 7/31/2006 | WATERSVC | WATERSVC | BLZ +07-31-06; CS Fire Department approval of the RBD plans set is required prior to Water RBD approval by Utilities Development Services. +
Water civil construction plans must be approved by Utilities Development Services and included in the RBD plan set. +Please call 719.668.8259 to schedule appointments or for general information.
Plumbing plans must specify a Reduced Pressure Backflow Device. | | Water Division | 248183 |
Waste Water Div | Original | A | 7/31/2006 | CSUREVIEW | CSUREVIEW | BLZ +07-31-06 | | Waste Water Div | 248181 |
Out to Review | Original | A | 7/31/2006 | JAN | JAN | GE johson walking elec | | Out to Review | 248176 |
Out to Review | Original | A | 7/28/2006 | SHELLEY | SHELLEY | monday plan check | | Out to Review | 248175 |