Out to Review | Original | A | 1/23/2007 | DALEH | DALEH | JACK DUNSTON | | Out to Review | 250180 |
Mechanical | Original | A | 1/23/2007 | DALEH | DALEH | | | Mechanical | 250175 |
Out to Review | Original | A | 1/19/2007 | HEATHER | HEATHER | jack duston 232-8760 | | Out to Review | 250179 |
Electrical | Original | A | 1/17/2007 | SHELBY | SHELBY | | | Electrical | 250166 |
Electrical | Original | / | 1/17/2007 | | SHELBY | Location = Electrical by SHELBY | | Electrical | 250165 |
Mechanical | Original | D | 1/17/2007 | DALEH | DALEH | need total developed length of gas pipe in order to verify if existing 1" is adequate verify input btu of new rtu see plans for additional comments | | Mechanical | 250177 |
Out to Review | Original | A | 1/16/2007 | MINDY | MINDY | Jack Duston 232-8760 | | Out to Review | 250178 |
Finished Bin | Original | / | 12/4/2006 | | SHELLEY | Location = Finished Bin by SHELLEY | | Finished Bin | 250172 |
Plan Coordinator | Original | / | 12/4/2006 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 250184 |
Electrical | Original | D | 12/4/2006 | SHELBY | SHELBY | NEED IECC CALCULATIONS---SHOW WIRE AND CONDUIT SIZES ON ONE LINE---DRAWINGS TO REFLECT ACTUAL FIELD CONDITIONS | | Electrical | 250167 |
Enumeration | Original | A | 12/1/2006 | SHELLEY | SHELLEY | Given to SHELBY by SHELLEY | | Enumeration | 250171 |
Electrical | Original | / | 11/30/2006 | | SHELLEY | Location = Electrical by SHELLEY | | Electrical | 250164 |
Plan Coordinator | Original | / | 11/30/2006 | | KYE | Location = Plan Coordinator by KYE | | Plan Coordinator | 250183 |
Plumbing | Original | A | 11/30/2006 | KYE | KYE | As corrected, provide 1-1/4" drain from water heater pan per Regional Building Code. | | Plumbing | 250186 |
Enumeration | Original | A | 11/30/2006 | SHELLEY | SHELLEY | Given to KYE by SHELLEY | | Enumeration | 250170 |
Plumbing | Original | / | 11/30/2006 | | SHELLEY | Location = Plumbing by SHELLEY | | Plumbing | 250185 |
Plan Coordinator | Original | / | 11/29/2006 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 250182 |
Mechanical | Original | D | 11/29/2006 | RUSSELL | RUSSELL | If weight of new RTU exceeds weight of removed unit, provide letter from structural engineer the structure is adequate or required engineering, provide size of existing gas piping, see '03 IECC for T-stat reqmts, all S.A. duct in R.A. plenum to be insulated with minimum R-4.2 per '03 IECC and '05 RBC amendments | | Mechanical | 250176 |
Mechanical | Original | / | 11/28/2006 | | SHELLEY | Location = Mechanical by SHELLEY | | Mechanical | 250174 |
Plan Coordinator | Original | / | 11/28/2006 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 250181 |
Fire | Original | N | 11/28/2006 | CSFIRE | CSFIRE | | | Fire | 250173 |
Construction | Original | A | 11/28/2006 | TIMC | TIMC | | | Construction | 250163 |
Enumeration | Original | A | 11/28/2006 | SHELLEY | SHELLEY | Given to TIMC by SHELLEY | | Enumeration | 250169 |
Enumeration | Original | A | 10/18/2006 | MARLENE | MARLENE | | | Enumeration | 250168 |