Water Division | Original | A | 10/13/2006 | KYE | KYE | See plan 40853 | | Water Division | 9414 |
Waste Water Div | Original | A | 10/13/2006 | KYE | KYE | See plan 40853 | | Waste Water Div | 9413 |
Plumbing | Original | A | 10/13/2006 | KYE | KYE | | | Plumbing | 9408 |
Out to Review | Original | A | 10/11/2006 | LARRY | LARRY | John Hil 499-2812 | | Out to Review | 9406 |
Plumbing | Original | D | 10/11/2006 | LARRY | LARRY | Not all previous comments addressed. Update full sheets 8-1/2 x 11 sketches not acceptable | | Plumbing | 9412 |
Plumbing | Original | / | 10/11/2006 | LARRY | LARRY | | | Plumbing | 9407 |
Out to Review | Original | A | 10/5/2006 | LARRY | LARRY | john hill | | Out to Review | 9405 |
Plumbing | Original | D | 10/5/2006 | KYE | KYE | Missing rissers on underground drain drawing. Not showing all fixrue units for upper floors on risers shown. | | Plumbing | 9411 |
Out to Review | Original | A | 9/22/2006 | KYE | KYE | John Hill 499 2812 | | Out to Review | 9404 |
Plumbing | Original | D | 9/22/2006 | KYE | KYE | P400F.B:1. Some floor sinks marked as such, others just show as waste up. 2. Rough for rest room CP103T is unclear, is W/C on a carrier with lav trap arm connected to vent? 4. Need continuation of mens rest room G114 DWV. 5. Does trench drain to loading dock go to storm drain? P400F.C: 1. Fixtures for kitchen area are not shown, please provide or remove DWV and show as future. 2. No drain line indicated for men's lavs room G008. 3. There does not appear to be provisions to drain the elevator shafts per the elevator code. 4. Sheet P400F showa two 4" waste up at point indicated. 5. There does not appear to be a drain riser at grid 20 column M for restrooms 1203/1204. | | Plumbing | 9410 |
Plumbing | Original | D | 9/22/2006 | KYE | KYE | P401F.A: 1. There does not appear to be provisions to drain the elevator shafts per the elevator code. 2. Provide details for Decontamination shower holding tank and buried valve. 3. Need Minimum 3-1/2" end of line clean out at sink in room 1416. 4. No riser shown for sink in room 1450. 5. No drain shown for rooms TIT 1429, 1428. P401F.B 1. Sheet not included in set. P401F.C: 1. No roof drain risers shown for this area. 2. No drain risers shown to drain upper floors in this area. TG104: 1. Provide roof drain and overflow information. P407: 1. Provide scupper and down spout information. | | Plumbing | 9409 |