Mechanical | Original | A | 5/14/2007 | RUSSELL | RUSSELL | Revised gas pipe routing to events center | | Mechanical | 257773 |
Mechanical | Original | A | 5/4/2007 | RUSSELL | RUSSELL | Revised site gas piping | | Mechanical | 257772 |
Water Division | Original | A | 3/7/2007 | SHELLEY | SHELLEY | 2/15/07 - jmb | | Water Division | 257807 |
Out to Review | Original | A | 3/6/2007 | JOHNJ | JOHNJ | RBD SET IS AT HEATHERS DESK OTHER SET CHRIS HAS FROM GE, CHRIS NEEDS PRICE BEAKDOWN FOR THE MOOSE EXIBIT -VS- THE MOOSE LLS VAULT, A LIST WAS GIVEN TO CHRIS FOR EXACT PRICING | | Out to Review | 257780 |
Water Division | Original | D | 3/6/2007 | JOHNJ | JOHNJ | | | Water Division | 257808 |
Water Division | Original | A | 3/6/2007 | JOHNJ | JOHNJ | 2/15/07 JMB | | Water Division | 257806 |
Waste Water Div | Original | A | 3/6/2007 | JOHNJ | JOHNJ | 2/15/07 JMB | | Waste Water Div | 257805 |
Finished Bin | Original | / | 3/6/2007 | | ANGELA | Location = Finished Bin by ANGELA | | Finished Bin | 257757 |
Plumbing | Original | A | 3/6/2007 | DARYL | DARYL | | | Plumbing | 257796 |
Out to Review | Original | A | 3/5/2007 | MINDY | MINDY | Chris Thessing 433-0234 | | Out to Review | 257779 |
Finished Bin | Original | / | 3/2/2007 | | SHELLEY | Location = Finished Bin by SHELLEY | | Finished Bin | 257756 |
Plan Coordinator | Original | / | 3/2/2007 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 257791 |
Electrical | Original | A | 3/2/2007 | SHELBY | SHELBY | | | Electrical | 257750 |
Electrical | Original | / | 3/2/2007 | | SHELBY | Location = Electrical by SHELBY | | Electrical | 257748 |
Apps & Permits | Original | A | 3/2/2007 | DEVSERVICE | DEVSERVICE | Inv#9045522380 Pd 3-2-07 rlp 3-2-07 | | Apps & Permits | 257729 |
Electrical | Original | / | 3/1/2007 | SHELLEY | SHELLEY | Given to SHELBY by SHELLEY | | Electrical | 257747 |
Electrical | Original | / | 2/26/2007 | | SHELLEY | Location = Electrical by SHELLEY | | Electrical | 257746 |
Plan Coordinator | Original | / | 2/26/2007 | | DARYL | Location = Plan Coordinator by DARYL | | Plan Coordinator | 257790 |
Plumbing | Original | D | 2/26/2007 | DARYL | DARYL | See 13 Feb notes as updated. | | Plumbing | 257803 |
Plumbing | Original | / | 2/26/2007 | SHELLEY | SHELLEY | Given to DARYL by SHELLEY | | Plumbing | 257794 |
Plumbing | Original | / | 2/26/2007 | | SHELLEY | Location = Plumbing by SHELLEY | | Plumbing | 257793 |
Plan Coordinator | Original | / | 2/26/2007 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 257789 |
Mechanical | Original | A | 2/26/2007 | RUSSELL | RUSSELL | | | Mechanical | 257771 |
Mechanical | Original | / | 2/23/2007 | SHELLEY | SHELLEY | Given to RUSSELL by SHELLEY | | Mechanical | 257770 |
Mechanical | Original | / | 2/23/2007 | | SHELLEY | Location = Mechanical by SHELLEY | | Mechanical | 257769 |
Plan Coordinator | Original | / | 2/23/2007 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 257788 |
Construction | Original | A | 2/23/2007 | TIMC | TIMC | | | Construction | 257738 |
Construction | Original | / | 2/22/2007 | SHELLEY | SHELLEY | Given to TIMC by SHELLEY | | Construction | 257736 |
Construction | Original | / | 2/21/2007 | | ANGELA | Location = Construction by ANGELA | | Construction | 257735 |
Apps & Permits | Original | / | 2/21/2007 | ANGELA | ANGELA | requests overtime for construction and mechanical. | | Apps & Permits | 257728 |
Electrical | Original | / | 2/21/2007 | ANGELA | ANGELA | | | Electrical | 257745 |
Plumbing | Original | / | 2/21/2007 | ANGELA | ANGELA | | | Plumbing | 257792 |
Mechanical | Original | / | 2/21/2007 | ANGELA | ANGELA | | | Mechanical | 257768 |
Construction | Original | / | 2/21/2007 | ANGELA | ANGELA | | | Construction | 257734 |
Electric Div. | Original | A | 2/15/2007 | ELECTD | ELECTD | BLZ +2-15-07; APPROVED subject to: +All utility service plans and installation shall be in accordance with City Codes and all applicable Utilities’ rules, regulations and line extension service standards. +If it is necessary to relocate or alter any existing facilities, then the relocation or alteration of these facilities shall be at the Applicant’s expense, and if required, Applicant shall grant an easement for such facilities. +Applicant must grant easements or utility rights-of-way as required for any existing and/or proposed facilities; and all proposed improvements shall not encroach upon any utility easement. +All improvements, structures and trees must not be located under overhead lines, over or within 3 feet of any underground distribution utility facilities and shall not violate any provision of the NESC or any applicable Natural Gas Codes or policies of the Utilities. +The landscaping shall be designed to provide the required access clearances for utility facilities. +Any | | Electric Div. | 257741 |
Out to Review | Original | A | 2/15/2007 | ANGELA | ANGELA | patrick greer has red strap of ours as well 641-9504 | | Out to Review | 257778 |
Finished Bin | Original | / | 2/14/2007 | | SHELLEY | Location = Finished Bin by SHELLEY | | Finished Bin | 257755 |
Plan Coordinator | Original | / | 2/14/2007 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 257787 |
Electrical | Original | D | 2/14/2007 | SHELBY | SHELBY | CORRECTIONS NOT MADE (SEE COMMENTS PREVIOUS REVIEW)---MAKE CORRECTIONS ON ONE IECC CALCULATION FOR ENTIRE PLAN (CURRENTLY THREE IECC CALCULATIONS FOR DIFFERENT PARTS OF PLAN) | | Electrical | 257752 |
Electrical | Original | / | 2/14/2007 | SHELLEY | SHELLEY | Given to SHELBY by SHELLEY | | Electrical | 257744 |
Electrical | Original | / | 2/14/2007 | | SHELLEY | Location = Electrical by SHELLEY | | Electrical | 257743 |
Plan Coordinator | Original | / | 2/14/2007 | | DARYL | Location = Plan Coordinator by DARYL | | Plan Coordinator | 257786 |
Mechanical | Original | D | 2/14/2007 | DARYL | DARYL | M13.5.2 Show welded duct per detail 8 M14.5.1 Exhaust fans 4 anf 5 need be min of 150 cfm each. M14.5.2 Still need structural engineer letter for MUA.
Note: gas pipe sizing OK
Dale Hoke and I worked on this together | | Mechanical | 257775 |
Plumbing | Original | D | 2/13/2007 | DARYL | DARYL | 1. P2.1.2 Please show piping detail fdor double lavatory piping.--OK Appears as if we still have horizontal dry vents below flood rim.--not fixed 2.` P2.1.4 Undersized piping and horizontal dry vents below flood rims. ---2nd item not fixed 3. P3.1.2 Incorrect venting and are revision numbers correct?--1st item not fixed. | | Plumbing | 257802 |
Mechanical | Original | / | 2/13/2007 | SHELLEY | SHELLEY | Given to DALEH by SHELLEY | | Mechanical | 257767 |
Mechanical | Original | / | 2/13/2007 | | SHELLEY | Location = Mechanical by SHELLEY | | Mechanical | 257766 |
Plan Coordinator | Original | / | 2/13/2007 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 257785 |
Construction | Original | D | 2/13/2007 | TIMC | TIMC | Provide copy of energy code cert. Address other comments as noted on plans. No walk-thru. | | Construction | 257739 |
Construction | Original | / | 2/8/2007 | | SHELLEY | Location = Construction by SHELLEY | | Construction | 257733 |
Zoning/Planning | Original | A | 2/8/2007 | SHELLEY | SHELLEY | 2/6/07 - dmt | | Zoning/Planning | 257810 |
Zoning/Planning | Original | / | 1/31/2007 | | SHELLEY | Location = Zoning/Planning by SHELLEY | | Zoning/Planning | 257809 |
Plan Coordinator | Original | / | 1/31/2007 | | HEATHER | Location = Plan Coordinator by HEATHER | | Plan Coordinator | 257784 |
Out to Review | Original | A | 1/18/2007 | HEATHER | HEATHER | dale geist 491-3411 | | Out to Review | 257777 |
Hazmat/High Pil | Original | N | 1/17/2007 | SHELLEY | SHELLEY | 1/16/07 - vlc | | Hazmat/High Pil | 257762 |
Fire | Original | A | 1/17/2007 | CSFIRE | CSFIRE | 1/16/07 - vlc | | Fire | 257759 |
Health Dept. | Original | A | 1/10/2007 | HEALTHDEPT | HEALTHDEPT | Water feature is limited to animals only, therefore no review by the Health Department is necassary. +Plans are approved.
Mike McCarthy, 719-578-3131, EPCHD | | Health Dept. | 257763 |
Fire | Original | / | 12/26/2006 | | SHELLEY | Location = Fire by SHELLEY | | Fire | 257758 |
Plan Coordinator | Original | / | 12/26/2006 | | GARYL | Location = Plan Coordinator by GARYL | | Plan Coordinator | 257783 |
Electrical | Original | D | 12/26/2006 | GARYL | GARYL | "L" FIXTURE, "G" FIXTURE ON PAGE E3.1.2 AND ALL OF FIXTURES ON PAGE E4.1. NOT SHOWN ON IECC CALCULATIONS. ALSO TRACH LIGHTING MUST BE SHOWN AT THE WATTAGE PER FIXTURE OR 30W PER FOOT, THE GREATER SHALL BE USED IN IECC CALCULATIONS | | Electrical | 257751 |
Electrical | Original | A | 12/26/2006 | SHELLEY | SHELLEY | Given to GARYL by SHELLEY | | Electrical | 257749 |
Electrical | Original | / | 12/22/2006 | | MINDY | Location = Electrical by MINDY | | Electrical | 257742 |
Plan Coordinator | Original | / | 12/22/2006 | | LARRY | Location = Plan Coordinator by LARRY | | Plan Coordinator | 257782 |
Plumbing | Original | D | 12/22/2006 | LARRY | LARRY | Each L-1 shall have its own waste, vent and trap. Plumb three compartment sink and dishwasher per 704.3 Show how indirect drainage from water heater, domestic water service and fire service is being done. Horizontal dry vents on water closets is prohibited. All food prep sinks shall be inditect waste. Health, waste water and water approval prior to plumbing approval is required. See plans for addtional comments | | Plumbing | 257801 |
Mechanical | Original | D | 12/22/2006 | LARRY | LARRY | Show BTU/CFH for gas and indicate total developed length. Floor drain is not an approved indirect recpetor except for a water heater. EF-4 and 5 are only 70 CFM 403 reuqires 75 CFM per fixture. It appears EF-6 is not shown on plans? Provide refrigerant calcs per 1104.2 It appears the MAU is not on schedule? How is make up air temp being maintained? Provide structural engineer letter for equipment over 300 lbs or show on structural drawings (EF-1) Indicate permanent access for furnaces in event center. See plans for addtional comments. | | Mechanical | 257774 |
Plumbing | Original | A | 12/20/2006 | SHELLEY | SHELLEY | Given to LARRY by SHELLEY | | Plumbing | 257795 |
Mechanical | Original | / | 12/19/2006 | | SHELLEY | Location = Mechanical by SHELLEY | | Mechanical | 257765 |
Plan Coordinator | Original | / | 12/19/2006 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 257781 |
Construction | Original | D | 12/19/2006 | TIMC | TIMC | Provide emergency exit lights in Event Center. Proivde model energy code cet for event center. Provide side elevation of HC stall showig 18" vertical grab bar. Provide 2nd exit from Event Center events 1 and events 3 rooms. Provide panic hardware on door A-21 in Event Center. Specify Pg and Pf design parameters. Provide copy of soils report. Provide copy of premanufactured building shop drawings, for Event Center. Address other comments as noted on plans. No walk-thru. | | Construction | 257740 |
Construction | Original | A | 12/19/2006 | SHELLEY | SHELLEY | Given to TIMC by SHELLEY | | Construction | 257737 |
Construction | Original | / | 12/13/2006 | | SHELLEY | Location = Construction by SHELLEY | | Construction | 257732 |
Traffic Engr. | Original | D | 12/12/2006 | CSTRAFFIC | CSTRAFFIC | attach an approved DP prior to review | | Traffic Engr. | 257804 |
Zoning/Planning | Original | D | 12/12/2006 | CSZONING | CSZONING | attach the stamped approved AR DP 06-468 AND AR UP 06-469 to each resubmittal. RBD# 42539. Volume 3 | | Zoning/Planning | 257813 |
Zoning/Planning | Original | D | 12/12/2006 | CSZONING | CSZONING | attach the stamped approved AR DP 06-468 AND AR UP 06-469 to each resubmittal. RBD# 425397. Volume 2 | | Zoning/Planning | 257814 |
Zoning/Planning | Original | D | 12/11/2006 | CSZONING | CSZONING | attach the stamped approved AR DP 06-468 AND AR UP 06-469 to each resubmittal. | | Zoning/Planning | 257811 |
Zoning/Planning | Original | D | 12/11/2006 | CSZONING | CSZONING | attach the stamped approved AR DP 06-468 AND AR UP 06-469 to each resubmittal. RBD# 42536. | | Zoning/Planning | 257812 |
Apps & Permits | Original | D | 12/5/2006 | DEVSERVICE | DEVSERVICE | requires utility receipt rlp 12-05-06 | | Apps & Permits | 257730 |
Apps & Permits | Original | / | 12/5/2006 | | JEANNINE | Location = Apps & Permits by JEANNINE | | Apps & Permits | 257727 |
Floodplain | Original | A | 12/5/2006 | JEANNINE | JEANNINE | | | Floodplain | 257761 |
Floodplain | Original | / | 12/5/2006 | | MARLENE | Location = Floodplain by MARLENE | | Floodplain | 257760 |
Enumeration | Original | A | 12/5/2006 | MARLENE | MARLENE | | | Enumeration | 257754 |
Enumeration | Original | / | 12/5/2006 | | SHELLEY | Location = Enumeration by SHELLEY | | Enumeration | 257753 |
Health Dept. | Original | D | 12/5/2006 | SHELLEY | SHELLEY | 12/4/06 - NM - see stamp on plans | | Health Dept. | 257764 |
City Engr. | Original | A | 12/5/2006 | SHELLEY | SHELLEY | 12/4/06 - en | | City Engr. | 257731 |
Monday Plancheck | Original | / | 12/1/2006 | | JEREMY | Location = Monday Plancheck by JEREMY | | Monday Plancheck | 257776 |