Out to Review | Original | A | 3/26/2007 | MINDY | MINDY | | | Out to Review | 257856 |
Out to Review | Original | A | 3/26/2007 | DARYL | DARYL | | | Out to Review | 257855 |
Plumbing | Original | A | 3/26/2007 | DARYL | DARYL | | | Plumbing | 257797 |
Mechanical | Original | A | 3/26/2007 | DALEH | DALEH | | | Mechanical | 257847 |
Out to Review | Original | A | 3/20/2007 | MINDY | MINDY | Dave Buesser 448-9800 | | Out to Review | 257854 |
Finished Bin | Original | / | 3/19/2007 | | SHELLEY | Location = Finished Bin by SHELLEY | | Finished Bin | 257833 |
Plan Coordinator | Original | / | 3/19/2007 | | DARYL | Location = Plan Coordinator by DARYL | | Plan Coordinator | 257864 |
Plumbing | Original | D | 3/19/2007 | DARYL | DARYL | 1. P10.1.1--Still need indirect waste receptor for backflow preventer. 2. P11.1.1--Pump size is listed as 100gpm and also 115gpm. Also pipe is sized for one pump and 4 pumps are listed. 3. P11.1.1 --Need sump piping diagram to verify proper venting etc. 4. P13.5.1 -- Stop and waste undergound is an unprotected cross connection 5. In general please try to avoid horizontal dry vents below flood rim as per section 905.3 UPC 2000 | | Plumbing | 257870 |
Plumbing | Original | / | 3/19/2007 | SHELLEY | SHELLEY | Given to DARYL by SHELLEY | | Plumbing | 257868 |
Plumbing | Original | / | 3/19/2007 | | SHELLEY | Location = Plumbing by SHELLEY | | Plumbing | 257867 |
Plan Coordinator | Original | / | 3/19/2007 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 257863 |
Mechanical | Original | D | 3/19/2007 | DALEH | DALEH | revise refrigerant calculations example shown on mechanical sheet | | Mechanical | 257849 |
Mechanical | Original | / | 3/16/2007 | SHELLEY | SHELLEY | Given to DALEH by SHELLEY | | Mechanical | 257845 |
Mechanical | Original | / | 3/15/2007 | MINDY | MINDY | For OT | | Mechanical | 257844 |
Plan Coordinator | Original | / | 3/13/2007 | | MINDY | Location = Plan Coordinator by MINDY | | Plan Coordinator | 257862 |
Water Division | Original | A | 3/13/2007 | MINDY | MINDY | 03/13/07 ai | | Water Division | 257875 |
Waste Water Div | Original | A | 3/13/2007 | MINDY | MINDY | 03/13/07 aj | | Waste Water Div | 257874 |
Mechanical | Original | / | 3/13/2007 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 257843 |
Electric Div. | Original | A | 3/7/2007 | ELECTD | ELECTD | BLZ +3-7-07; APPROVED subject to: +All utility service plans and installation shall be in accordance with City Codes and all applicable Utilities’ rules, regulations and line extension service standards. +If it is necessary to relocate or alter any existing facilities, then the relocation or alteration of these facilities shall be at the Applicant’s expense, and if required, Applicant shall grant an easement for such facilities. +Applicant must grant easements or utility rights-of-way as required for any existing and/or proposed facilities; and all proposed improvements shall not encroach upon any utility easement. +All improvements, structures and trees must not be located under overhead lines, over or within 3 feet of any underground distribution utility facilities and shall not violate any provision of the NESC or any applicable Natural Gas Codes or policies of the Utilities. +The landscaping shall be designed to provide the required access clearances for utility facilities. +Any p | | Electric Div. | 257827 |
Out to Review | Original | A | 3/7/2007 | SHELLEY | SHELLEY | chris thessing | | Out to Review | 257853 |
Plan Coordinator | Original | / | 3/7/2007 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 257861 |
Construction | Original | A | 3/7/2007 | TIMC | TIMC | | | Construction | 257825 |
Construction | Original | / | 3/7/2007 | SHELLEY | SHELLEY | Given to TIMC by SHELLEY | | Construction | 257823 |
Traffic Engr. | Original | A | 3/7/2007 | SHELLEY | SHELLEY | 3/6/07 - ss | | Traffic Engr. | 257872 |
Construction | Original | / | 3/6/2007 | | JOHNJ | Location = Construction by JOHNJ | | Construction | 257822 |
Out to Review | Original | A | 3/6/2007 | JOHNJ | JOHNJ | CHRIS THESSING 433-0234 IS LOOKING AT WILL PUT BACK IN CONSTRUCTION AFTER | | Out to Review | 257852 |
Construction | Original | / | 3/6/2007 | | MINDY | Location = Construction by MINDY | | Construction | 257821 |
Zoning/Planning | Original | A | 3/6/2007 | MINDY | MINDY | 03/05/07 DMT | | Zoning/Planning | 257879 |
Apps & Permits | Original | A | 3/2/2007 | DEVSERVICE | DEVSERVICE | Inv#9045522380 Pd 3-2-07 rlp 3-2-07 | | Apps & Permits | 257816 |
Zoning/Planning | Original | / | 2/28/2007 | | SHELLEY | Location = Zoning/Planning by SHELLEY | | Zoning/Planning | 257878 |
Traffic Engr. | Original | / | 2/28/2007 | JAN | JAN | plans resubmitted for corrections 2-28-07 | | Traffic Engr. | 257871 |
Plan Coordinator | Original | / | 2/28/2007 | | JAN | Location = Plan Coordinator by JAN | | Plan Coordinator | 257860 |
Plumbing | Original | / | 2/28/2007 | JAN | JAN | | | Plumbing | 257866 |
Mechanical | Original | / | 2/28/2007 | JAN | JAN | | | Mechanical | 257842 |
Construction | Original | / | 2/28/2007 | JAN | JAN | | | Construction | 257820 |
Zoning/Planning | Original | / | 2/28/2007 | JAN | JAN | | | Zoning/Planning | 257877 |
Out to Review | Original | A | 1/18/2007 | HEATHER | HEATHER | dale geist 491-3411 | | Out to Review | 257851 |
Hazmat/High Pil | Original | N | 1/17/2007 | SHELLEY | SHELLEY | 1/16/07 - vlc | | Hazmat/High Pil | 257838 |
Fire | Original | A | 1/17/2007 | CSFIRE | CSFIRE | 1/16/07 - vlc | | Fire | 257835 |
Health Dept. | Original | A | 1/10/2007 | HEALTHDEPT | HEALTHDEPT | Water feature is limited to animals only, therefore no review by the Health Department is necassary. +Plans are approved.
Mike McCarthy, 719-578-3131, EPCHD | | Health Dept. | 257839 |
Fire | Original | / | 1/4/2007 | | SHELLEY | Location = Fire by SHELLEY/mcs | | Fire | 257834 |
Electrical | Original | A | 1/4/2007 | GARYL | GARYL | MUST COMPLY WITH NEC 300.6 A-D | | Electrical | 257830 |
Electrical | Original | / | 1/4/2007 | SHELLEY | SHELLEY | Given to GARYL by SHELLEY/mcs | | Electrical | 257829 |
Electrical | Original | / | 1/3/2007 | | SHELLEY | Location = Electrical by SHELLEY | | Electrical | 257828 |
Plan Coordinator | Original | / | 1/3/2007 | | LARRY | Location = Plan Coordinator by LARRY | | Plan Coordinator | 257859 |
Plumbing | Original | D | 1/3/2007 | LARRY | LARRY | Provide drain for RPBFP Label non potable water Provide vents for floor drains Indicate pump capacity in GPM Provide detail of sump per 710.9 and 710.10 See plans for additional comments | | Plumbing | 257798 |
Plumbing | Original | A | 1/3/2007 | SHELLEY | SHELLEY | Given to LARRY by SHELLEY | | Plumbing | 257869 |
Plumbing | Original | / | 12/27/2006 | | SHELLEY | Location = Plumbing by SHELLEY | | Plumbing | 257865 |
Plan Coordinator | Original | / | 12/27/2006 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 257858 |
Mechanical | Original | D | 12/27/2006 | RUSSELL | RUSSELL | Toilet exhaust shall be minimum 75 cfm & how providing makeup air ?, how providing makeup air into areas being exhausted ? UH-2 has been omitted from schedule sheet , yet shown on hseet M10.1.1 ?, provide type and amount of refrigerant serving ACC-1 for compliance with '03 IMC Table 1103.1 | | Mechanical | 257848 |
Mechanical | Original | A | 12/27/2006 | SHELLEY | SHELLEY | Given to RUSSELL by SHELLEY | | Mechanical | 257846 |
Mechanical | Original | / | 12/22/2006 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 257841 |
Zoning/Planning | Original | / | 12/22/2006 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 257876 |
Plan Coordinator | Original | / | 12/21/2006 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 257857 |
Construction | Original | D | 12/21/2006 | TIMC | TIMC | Specify Pg and Pf design parameters. Walk-thru ok. | | Construction | 257826 |
Construction | Original | A | 12/19/2006 | SHELLEY | SHELLEY | Given to TIMC by SHELLEY | | Construction | 257824 |
Construction | Original | / | 12/13/2006 | | SHELLEY | Location = Construction by SHELLEY | | Construction | 257819 |
Traffic Engr. | Original | D | 12/13/2006 | SHELLEY | SHELLEY | 12/12/06 - ss - see plans for comments | | Traffic Engr. | 257873 |
Zoning/Planning | Original | D | 12/13/2006 | SHELLEY | SHELLEY | 12/12/06 - dmt - see plans for comments | | Zoning/Planning | 257880 |
Apps & Permits | Original | D | 12/5/2006 | DEVSERVICE | DEVSERVICE | requires utility receipt +rlp 12-05-06 | | Apps & Permits | 257817 |
Apps & Permits | Original | / | 12/5/2006 | | JEANNINE | Location = Apps & Permits by JEANNINE | | Apps & Permits | 257815 |
Floodplain | Original | A | 12/5/2006 | JEANNINE | JEANNINE | | | Floodplain | 257837 |
Floodplain | Original | / | 12/5/2006 | | MARLENE | Location = Floodplain by MARLENE | | Floodplain | 257836 |
Enumeration | Original | A | 12/5/2006 | MARLENE | MARLENE | | | Enumeration | 257832 |
Enumeration | Original | / | 12/5/2006 | | SHELLEY | Location = Enumeration by SHELLEY | | Enumeration | 257831 |
Health Dept. | Original | D | 12/5/2006 | SHELLEY | SHELLEY | 12/4/06 - nm - please contact Mike McCarthy @578-3131 for pool details | | Health Dept. | 257840 |
City Engr. | Original | A | 12/5/2006 | SHELLEY | SHELLEY | 12/4/06 - en | | City Engr. | 257818 |
Monday Plancheck | Original | / | 12/1/2006 | | JEREMY | Location = Monday Plancheck by JEREMY | | Monday Plancheck | 257850 |