Enumeration | Original | A | 3/15/2007 | MARLENE | MARLENE | | | Enumeration | 271652 |
Out to Review | Original | A | 3/8/2007 | SHELBY | SHELBY | ELLEN 303 832 2666 EXT 235 | | Out to Review | 271662 |
Electrical | Original | A | 3/8/2007 | SHELBY | SHELBY | ADDITIONAL PLAN REVIEW OF $150.00 | | Electrical | 271648 |
Mechanical | Original | A | 2/22/2007 | RUSSELL | RUSSELL | | | Mechanical | 271658 |
Plumbing | Original | A | 2/22/2007 | DARYL | DARYL | | | Plumbing | 271670 |
Out to Review | Original | A | 2/22/2007 | MINDY | MINDY | Troy Valdez 637-8850 | | Out to Review | 271661 |
Fire | Original | A | 2/21/2007 | CSFIRE | CSFIRE | Plans were located in Fire prevention on 2/21/07. Approval date is 2/14/07 - by VLC | | Fire | 271655 |
Fire | Original | / | 2/6/2007 | | SHELLEY | Location = Fire by SHELLEY | | Fire | 271654 |
Plan Coordinator | Original | / | 2/6/2007 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 271667 |
Electrical | Original | D | 2/6/2007 | SHELBY | SHELBY | SHOW ALL SWITCHBOARDS TO BE RATED FOR AVAILABLE FAULT CURRENT---PANEL SCHEDULES FOR UPS SWITCHBOARDS---SHOW UNOBSTRUCTED ACCESS TO ELECTRICAL ROOM ON SHEET E-36---FOR NOTES 3&4 ON SHEET E 1 THERE ARE NO NEC TABLES 250.94 OR 250.95---IECC CALCULATION TO MATCH LIGHTING PAGES---DUAL LEVEL SWITCHING OR OCCUPANCY SENSORS REQUIRED IN KITCHEN AND BREAKROOM---SIZE EQUIPMENT GROUNDING CONDUCTOR SIZES ON FEEDER SCHEDULE TO COMPLY WITH 250.122(B) | | Electrical | 271649 |
Electrical | Original | / | 2/2/2007 | SHELLEY | SHELLEY | Given to JERRY by SHELLEY | | Electrical | 271647 |
Electrical | Original | / | 2/2/2007 | | SHELLEY | Location = Electrical by SHELLEY | | Electrical | 271646 |
Plan Coordinator | Original | / | 2/2/2007 | | DARYL | Location = Plan Coordinator by DARYL | | Plan Coordinator | 271666 |
Plumbing | Original | D | 2/2/2007 | DARYL | DARYL | 1. Floor sinks are required by each unit per 2005 PPRBC 3096.4.9. Fllor sinks are connected to sanitary drain. | | Plumbing | 271671 |
Plumbing | Original | / | 2/2/2007 | SHELLEY | SHELLEY | Given to DARYL by SHELLEY | | Plumbing | 271669 |
Plumbing | Original | / | 2/2/2007 | | SHELLEY | Location = Plumbing by SHELLEY | | Plumbing | 271668 |
Plan Coordinator | Original | / | 2/2/2007 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 271665 |
Mechanical | Original | D | 2/2/2007 | DALEH | DALEH | see sheet m-8 need calculations for continuos ventilation see sheet m-29 ref. types, structural letter see sheet m-30 cfm on AHU | | Mechanical | 271659 |
Mechanical | Original | / | 2/1/2007 | SHELLEY | SHELLEY | Given to DALEH by SHELLEY | | Mechanical | 271657 |
Mechanical | Original | / | 2/1/2007 | | SHELLEY | Location = Mechanical by SHELLEY | | Mechanical | 271656 |
Plan Coordinator | Original | / | 2/1/2007 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 271664 |
Construction | Original | A | 2/1/2007 | TIMC | TIMC | | | Construction | 271645 |
Construction | Original | / | 2/1/2007 | SHELLEY | SHELLEY | Given to TIMC by SHELLEY | | Construction | 271644 |
Plan Coordinator | Original | / | 1/31/2007 | | MARLENE | Location = Plan Coordinator by MARLENE | | Plan Coordinator | 271663 |
Enumeration | Original | D | 1/31/2007 | MARLENE | MARLENE | Assessors database shows 4 bldgs on this property. Please advise what floor at what address is moving where (to what address). Provide Legal Description and addresses on Site Plan. | | Enumeration | 271653 |
Enumeration | Original | / | 1/31/2007 | | MINDY | Location = Enumeration by MINDY | | Enumeration | 271651 |
Out to Review | Original | A | 1/31/2007 | MINDY | MINDY | RAPID RESPONSE PLAN | | Out to Review | 271660 |
Enumeration | Original | / | 1/31/2007 | | MINDY | Location = Enumeration by MINDY | | Enumeration | 271650 |