City Engr. | Original | A | 5/10/2007 | SHELLEY | SHELLEY | 5/7/07 - en | | City Engr. | 275906 |
Water Division | Original | A | 5/10/2007 | SHELLEY | SHELLEY | 5/7/07 - jmb | | Water Division | 275958 |
Waste Water Div | Original | A | 5/10/2007 | SHELLEY | SHELLEY | 5/9/07 - jmb | | Waste Water Div | 275955 |
Apps & Permits | Original | A | 5/10/2007 | SHELLEY | SHELLEY | | | Apps & Permits | 275904 |
Finished Bin | Original | / | 5/9/2007 | | SHELLEY | Location = Finished Bin by SHELLEY | | Finished Bin | 275924 |
Gas/Elec. Utils | Original | A | 5/7/2007 | b.zook | b.zook | BLZ 5-7-07; APPROVED subject to: All utility service plans and installation shall be in accordance with City Codes and all applicable Utilities’ rules, regulations and line extension service standards. Applicant must grant easements or utility rights-of-way as required for any existing and/or proposed facilities. All improvements, structures and trees shall not violate any provision of the NESC or any applicable Natural Gas Codes or policies of the Utilities. The landscaping shall be designed to provide the required access clearances for utility facilities. Approval of these drawings shall not be construed as a limitation upon the authority of the Utilities to apply its standards. If there are any conflicts between the approved drawings and any provision of the Utilities’ standards, then the Utilities’ standards and policies shall apply. Contact Field Engineering prior to start of construction (South 668-5564, North 668-4985). | | Gas/Elec. Utils | 275932 |
Out to Review | Original | A | 5/7/2007 | JAN | JAN | Rob Anderson 338-3928 | | Out to Review | 275943 |
Fire | Original | A | 5/4/2007 | SHELLEY | SHELLEY | 5/4/07 - cth | | Fire | 275928 |
Hazmat/High Pile | Original | A | 5/2/2007 | STEVE | STEVE | | | Hazmat/High Pile | 275934 |
Fire | Original | / | 4/26/2007 | | SHELLEY | Location = Fire by SHELLEY | | Fire | 275927 |
Plan Coordinator | Original | / | 4/26/2007 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 275948 |
Construction | Original | A | 4/26/2007 | TIMC | TIMC | | | Construction | 275916 |
Construction | Original | / | 4/25/2007 | SHELLEY | SHELLEY | Given to TIMC by SHELLEY | | Construction | 275915 |
Construction | Original | / | 4/24/2007 | | SHELLEY | Location = Construction by SHELLEY | | Construction | 275914 |
Fire | Original | / | 4/24/2007 | CSFIRE | CSFIRE | | | Fire | 275926 |
Construction | Original | / | 4/24/2007 | SHELLEY | SHELLEY | 1st resubmittal | | Construction | 275913 |
Plumbing | Original | A | 4/24/2007 | DARYL | DARYL | | | Plumbing | 275951 |
Out to Review | Original | A | 4/18/2007 | HEATHER | HEATHER | Rob 338-3928 | | Out to Review | 275942 |
Construction | Original | / | 4/18/2007 | | HEATHER | Location = Construction by HEATHER | | Construction | 275912 |
Out to Review | Original | A | 4/17/2007 | MINDY | MINDY | At Mindy's desk, waiting for someone to pick up for corrections and duplication of plans | | Out to Review | 275941 |
Fire | Original | D | 4/17/2007 | CSFIRE | CSFIRE | VLC 4-17-07 Fire Dept will not approve plans with 2 building. Each building must have a separate plan. | | Fire | 275929 |
Fire | Original | / | 4/10/2007 | | SHELLEY | Location = Fire by SHELLEY | | Fire | 275925 |
Plan Coordinator | Original | / | 4/10/2007 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 275947 |
Electrical | Original | A | 4/10/2007 | SHELBY | SHELBY | | | Electrical | 275922 |
Electrical | Original | / | 4/9/2007 | SHELLEY | SHELLEY | Given to SHELBY by SHELLEY | | Electrical | 275921 |
Electrical | Original | / | 4/4/2007 | | SHELLEY | Location = Electrical by SHELLEY | | Electrical | 275920 |
Plan Coordinator | Original | / | 4/4/2007 | | DARYL | Location = Plan Coordinator by DARYL | | Plan Coordinator | 275946 |
Plumbing | Original | D | 4/4/2007 | DARYL | DARYL | 1. Please show water pressure regulator and backflow preventer as per CSU specs. 2. Seems be be a disagreement between floor drain size from P-1 to P-2 3. Please show water heaterplatform detail with expansion tank. | | Plumbing | 275952 |
Plumbing | Original | / | 4/4/2007 | SHELLEY | SHELLEY | Given to DARYL by SHELLEY | | Plumbing | 275950 |
Plumbing | Original | / | 4/3/2007 | | SHELLEY | Location = Plumbing by SHELLEY | | Plumbing | 275949 |
Plan Coordinator | Original | / | 4/3/2007 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 275945 |
Mechanical | Original | A | 4/3/2007 | RUSSELL | RUSSELL | | | Mechanical | 275938 |
Mechanical | Original | / | 4/3/2007 | SHELLEY | SHELLEY | Given to RUSSELL by SHELLEY | | Mechanical | 275937 |
Mechanical | Original | / | 3/29/2007 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 275936 |
Plan Coordinator | Original | / | 3/29/2007 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 275944 |
Construction | Original | D | 3/29/2007 | TIMC | TIMC | Provide new copy of Comcheck that states its passing or not. Specify Pg and Pf design parameters. Address other comments as noted on drawings. No walk-thru. | | Construction | 275917 |
Construction | Original | / | 3/28/2007 | SHELLEY | SHELLEY | Given to TIMC by SHELLEY | | Construction | 275911 |
Zoning/Planning | Original | A | 3/27/2007 | CSZONING | CSZONING | Approved as submitted. | | Zoning/Planning | 275961 |
Construction | Original | / | 3/7/2007 | | JAN | Location = Construction by JAN returned to construction plan check | | Construction | 275910 |
Out to Review | Original | A | 3/7/2007 | JAN | JAN | Rob anderson walking zoning ( be right back) | | Out to Review | 275940 |
Electrical | Original | / | 3/7/2007 | | JAN | Location = Electrical by JAN | | Electrical | 275919 |
Electric Div. | Original | D | 3/6/2007 | ELECTD | ELECTD | BLZ +3-6-07; Show gas meter location on plans. | | Electric Div. | 275918 |
Water Division | Original | D | 3/6/2007 | WATERSVC | WATERSVC | BLZ +3-6-07; CS Fire Department approval of the RBD plans set is required prior to Water RBD approval by Utilities Development Services. +
Water civil construction plans must be approved by Utilities Development Services and included in the RBD plan set. +Please call 719.668.8259 to schedule appointments or for general information.
Plumbing plans must specify a Reduced Pressure Backflow Device. | | Water Division | 275960 |
Waste Water Div | Original | D | 3/6/2007 | CSUREVIEW | CSUREVIEW | BLZ +3-6-07; Wastewater civil construction plans must be approved by Utilities Development Services and included in the RBD plan set. +Please call 719.668.8259 to schedule appointments or for general information. | | Waste Water Div | 275957 |
Construction | Original | / | 3/6/2007 | | MINDY | Location = Construction by MINDY | | Construction | 275909 |
Traffic Engr. | Original | A | 3/6/2007 | MINDY | MINDY | 02/27/07 TR | | Traffic Engr. | 275954 |
Health Dept. | Original | A | 3/6/2007 | MINDY | MINDY | 03/05/07 NM | | Health Dept. | 275935 |
City Engr. | Original | D | 3/6/2007 | MINDY | MINDY | 03/05/07 EU | | City Engr. | 275907 |
Water Division | Original | D | 3/6/2007 | MINDY | MINDY | 03/05/07 BLZ | | Water Division | 275959 |
Waste Water Div | Original | D | 3/6/2007 | MINDY | MINDY | 03/05/07 BLZ | | Waste Water Div | 275956 |
Gas/Elec. Utils | Original | D | 3/6/2007 | MINDY | MINDY | 03/05/07 BLZ | | Gas/Elec. Utils | 275933 |
Monday Plancheck | Original | / | 3/2/2007 | | SHELLEY | Location = Monday Plancheck by SHELLEY | | Monday Plancheck | 275939 |
Construction | Original | / | 2/28/2007 | | SHELLEY | Location = Construction by SHELLEY | | Construction | 275908 |
Zoning/Planning | Original | D | 2/28/2007 | SHELLEY | SHELLEY | 2/28/07 - jmj | | Zoning/Planning | 275963 |
Traffic Engr. | Original | A | 2/27/2007 | CSTRAFFIC | CSTRAFFIC | Approved by TR and sent to RBD. | | Traffic Engr. | 275953 |
Zoning/Planning | Original | D | 2/26/2007 | CSZONING | CSZONING | The approved DP elevations do not indicate approval of balconies. Either modify your development plan or remove the proposed balcony from your construction drawings. Note: All else will be developed per the DP as there is not a separate site plan attached. | | Zoning/Planning | 275962 |
Apps & Permits | Original | D | 2/21/2007 | DEVSERVICE | DEVSERVICE | Need developer / owner to call Springs Utilities at 668-8115 to find out meter size information and to set up account/Invoice. +Need receipt showing payment of Utility Development fees. +Delivered to City Engineering 2/21/07. scm | | Apps & Permits | 275905 |
Apps & Permits | Original | / | 2/21/2007 | | JEANNINE | Location = Apps & Permits by JEANNINE | | Apps & Permits | 275903 |
Floodplain | Original | A | 2/21/2007 | JEANNINE | JEANNINE | | | Floodplain | 275931 |
Enumeration | Original | A | 2/21/2007 | MARLENE | MARLENE | | | Enumeration | 275923 |
Floodplain | Original | / | 2/21/2007 | | MARLENE | Location = Floodplain by MARLENE | | Floodplain | 275930 |