Water Division | Original | A | 7/20/2007 | HEATHER | HEATHER | JMB 7-17-07 | | Water Division | 295079 |
Waste Water Div | Original | A | 7/20/2007 | HEATHER | HEATHER | JMB 7-17-07 | | Waste Water Div | 295077 |
Plumbing | Original | A | 7/16/2007 | TCRIPPEN | TCRIPPEN | | | Plumbing | 295074 |
Plumbing | Original | D | 7/16/2007 | DARYL | DARYL | Need water heater approved detail by construction. | | Plumbing | 295076 |
Plumbing | Original | / | 7/16/2007 | DARYL | DARYL | | | Plumbing | 295073 |
Mechanical | Original | A | 6/25/2007 | RUSSELL | RUSSELL | | | Mechanical | 295064 |
Construction | Original | A | 6/25/2007 | RICH | RICH | approved revised for added rtu units to roof , see attacted engineers letter | | Construction | 295048 |
Construction | Original | / | 6/25/2007 | RICH | RICH | | | Construction | 295046 |
Mechanical | Original | D | 6/25/2007 | DALEH | DALEH | all previous coments have been addressed i put the check mark on plans that were reviewed all o.k. need structural engineers letter stamped approved just waiting for health dept. approval | | Mechanical | 295065 |
Out to Review | Original | A | 6/25/2007 | ANGELA | ANGELA | out to Daniel 667-1972 | | Out to Review | 295070 |
Fire | Original | A | 6/25/2007 | MINDY | MINDY | 06/22/07 SMC | | Fire | 295058 |
Finished Bin | Original | / | 6/25/2007 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 295056 |
Out to Review | Original | A | 6/19/2007 | SHELBY | SHELBY | DANIEL 667 1972 | | Out to Review | 295069 |
Electrical | Original | A | 6/19/2007 | SHELBY | SHELBY | | | Electrical | 295052 |
Electrical | Original | / | 6/19/2007 | | SHELBY | Location = Electrical by SHELBY | | Electrical | 295051 |
Enumeration | Original | A | 6/19/2007 | MARLENE | MARLENE | | | Enumeration | 295054 |
Health Dept. | Original | A | 6/15/2007 | healthdept | healthdept | Approved as corrected in plan review dated 6/15/07. Min hw requirements at 100 deg F rise: 123 gph recovery rate OR 136,612 BTUs. Contact LP at (719)578-3132 with comments/questions. | | Health Dept. | 295060 |
Out to Review | Original | A | 6/11/2007 | HEATHER | HEATHER | Daniel 667-1972 | | Out to Review | 295068 |
Fire | Original | D | 5/30/2007 | SHELLEY | SHELLEY | 5/29/07 - smc | | Fire | 295059 |
Health Dept. | Original | D | 5/25/2007 | MINDY | MINDY | 05/07/07 NM | | Health Dept. | 295061 |
Fire | Original | / | 5/25/2007 | | MINDY | Location = Fire by MINDY | | Fire | 295057 |
Plan Coordinator | Original | / | 5/25/2007 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 295072 |
Electrical | Original | D | 5/25/2007 | SHELBY | SHELBY | IECC CALCULATION INCORRECT(TRACK LIGHTING MINIMUM OF 30 WATTS PER FOOT)---ALL KITCHEN RECEPTICLES COMPLY 210.8(B)(2) (PENDANT,DISHWASHER,ALL) | | Electrical | 295053 |
Electrical | Original | / | 5/24/2007 | SHELLEY | SHELLEY | Given to SHELBY by SHELLEY | | Electrical | 295050 |
Electrical | Original | / | 5/24/2007 | | SHELLEY | Location = Electrical by SHELLEY | | Electrical | 295049 |
Plan Coordinator | Original | / | 5/24/2007 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 295071 |
Plumbing | Original | D | 5/24/2007 | RUSSELL | RUSSELL | Need health and waste water approval prior to plumbing approval, verify with waste water size of greas interceptor, verify with health reqmts for water heater, cleanouts as indicated, pass-thru dishwasher requires Type II hood, verfiy if S-1 to go to grease waste or waste, | | Plumbing | 295075 |
Mechanical | Original | D | 5/24/2007 | RUSSELL | RUSSELL | Provide section thru hood showing relatiuonship with ceiling and if protection at top of hood required, shafting grease duct or using approved wrap, minimum 40" termination point of upblast fan to roof, structural engineers letter or engineering for 710# new makeup air unit on roof, cnnot have B vent in R.A. plenum, exhaust duct under positive pressue in R.A. plenum shall be installed without joints or isloated, need length back to meter to verify all gas piping sizes | | Mechanical | 295066 |
Mechanical | Original | / | 5/23/2007 | SHELLEY | SHELLEY | Given to RUSSELL by SHELLEY | | Mechanical | 295063 |
Mechanical | Original | / | 5/18/2007 | | SHELLEY | Location = Mechanical by SHELLEY | | Mechanical | 295062 |
Construction | Original | A | 5/18/2007 | SHELLEY | SHELLEY | | | Construction | 295047 |
Construction | Original | / | 5/17/2007 | SHELLEY | SHELLEY | Given to TIMC by SHELLEY | | Construction | 295045 |
Construction | Original | / | 5/15/2007 | | MINDY | Location = Construction by MINDY | | Construction | 295044 |
Zoning/Planning | Original | A | 5/15/2007 | MINDY | MINDY | 05/14/07 DW | | Zoning/Planning | 295084 |
Zoning/Planning | Original | A | 5/14/2007 | CSZONING | CSZONING | PER DP 05-29. CATHY'S DELI. | | Zoning/Planning | 295083 |
Zoning/Planning | Original | / | 5/8/2007 | | SHELLEY | Location = Zoning/Planning by SHELLEY | | Zoning/Planning | 295082 |
Water Division | Original | D | 5/8/2007 | SHELLEY | SHELLEY | 5/7/07 - blz | | Water Division | 295080 |
Waste Water Div | Original | D | 5/7/2007 | b.zook | b.zook | BLZ 5-7-07; Wastewater line will require a grease interceptor, please size and contact Jean at 668-8253 for approval. | | Waste Water Div | 295078 |
Monday Plancheck | Original | / | 5/4/2007 | | SHELLEY | Location = Monday Plancheck by SHELLEY | | Monday Plancheck | 295067 |
Zoning/Planning | Original | / | 5/2/2007 | | MARLENE | Location = Zoning/Planning by MARLENE | | Zoning/Planning | 295081 |
Enumeration | Original | D | 5/2/2007 | MARLENE | MARLENE | Provide Site Plan showing tenant space, and Legal Description. | | Enumeration | 295055 |