Plumbing | Original | A | 10/6/2008 | TCRIPPEN | TCRIPPEN | hub drain to grease waste | | Plumbing | 384007 |
Plumbing | Original | A | 9/4/2008 | TCRIPPEN | TCRIPPEN | new splice page added new grease interceptor and drains | | Plumbing | 378689 |
Mechanical | Original | A | 8/8/2008 | DALEH | DALEH | splice for change to mechanical sheet | | Mechanical | 374411 |
Finished Bin | Original | / | 7/28/2008 | | NELIDA | Location = Finished Bin by NELIDA | | Finished Bin | 372276 |
Scanned/Finished Bin | Original | / | 7/22/2008 | | KIM | Location = Scanned/Finished Bin by KIM | | Scanned/Finished Bin | 371332 |
Water Division | Original | A | 7/22/2008 | KIM | KIM | 4/14/08 MW | | Water Division | 371331 |
Waste Water Div | Original | A | 7/22/2008 | KIM | KIM | MW 4/14/08 | | Waste Water Div | 371330 |
Plumbing | Original | A | 7/22/2008 | TCRIPPEN | TCRIPPEN | added plan fee 50.00 | | Plumbing | 371329 |
Mechanical | Original | A | 7/22/2008 | TCRIPPEN | TCRIPPEN | | | Mechanical | 371147 |
Plumbing | Original | D | 7/22/2008 | TCRIPPEN | TCRIPPEN | pending waste water rest OK | | Plumbing | 371145 |
Health Dept. | Original | A | 7/18/2008 | healthdept | healthdept | Approved as corrested in plan review dadted 7/17/08. Min hw req at 100 deg F rise:17 kw or 67 gph rec. rate. Please contact Matthew Garcia at (719) 578-3143 with comments or questions. | | Health Dept. | 370800 |
Out to Review | Original | / | 5/29/2008 | RONW | RONW | Hank = 471-7566 | | Out to Review | 361420 |
Construction | Original | A | 5/29/2008 | RONW | RONW | revised using net area Table 1004.1.2., 2003 ibc = 50 max. o.l. (B-occ. = okay) | | Construction | 361419 |
Out to Review | Original | / | 5/21/2008 | SHELBY | SHELBY | JERRY 473 7077 | | Out to Review | 360145 |
Electrical | Original | A | 5/21/2008 | SHELBY | SHELBY | corrections made | | Electrical | 360144 |
Electrical | Original | / | 5/21/2008 | | SHELBY | Location = Electrical by SHELBY | | Electrical | 360143 |
Out to Review | Original | / | 5/6/2008 | KIM | KIM | HENRY PIERCE 471-7566 | | Out to Review | 357183 |
Finished Bin | Original | / | 5/6/2008 | | SHARON | Location = Finished Bin by SHARON | | Finished Bin | 357100 |
Fire | Original | A | 5/6/2008 | SHARON | SHARON | 05/05/08 JM | | Fire | 357099 |
Fire | Original | / | 5/5/2008 | | SHARON | Location = Fire by SHARON | | Fire | 356879 |
Plan Coordinator | Original | / | 5/5/2008 | | GARYL | Location = Plan Coordinator by GARYL | | Plan Coordinator | 356866 |
Electrical | Original | D | 5/5/2008 | GARYL | GARYL | NEED IECC WORKSHEETS AND CALCULATION | | Electrical | 356865 |
Electrical | Original | / | 5/5/2008 | SHARON | SHARON | Plan Reviewer = JERRY by SHARON | | Electrical | 356836 |
Plumbing | Original | A | 5/2/2008 | TCRIPPEN | TCRIPPEN | plans do not show 3-compartment sink , provide water pipe criteria for sizing , materials not specified shall be minimum code for drain wastes vents and potable water | | Plumbing | 356585 |
Plumbing | Original | / | 4/24/2008 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 354359 |
Plan Coordinator | Original | / | 4/24/2008 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 354358 |
Mechanical | Original | D | 4/24/2008 | RUSSELL | RUSSELL | S.A. cfms at unit 107, location on co2 sensor in relationship to full height walls | | Mechanical | 354354 |
Mechanical | Original | / | 4/24/2008 | MINDY | MINDY | Given to RUSSELL by MINDY | | Mechanical | 354353 |
Mechanical | Original | / | 4/15/2008 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 354352 |
Health Dept. | Original | D | 4/15/2008 | MINDY | MINDY | 04/14/08 MG | | Health Dept. | 354351 |
Water Division | Original | D | 4/14/2008 | awerner | awerner | CS Fire Department approval of the RBD plans set is required prior to Water RBD approval by Utilities Development Services.
Water civil construction plans must be approved by Utilities Development Services and included in the RBD plan set. Please call 719.668.8259 to schedule appointments or for general information.
Plumbing plans must specify a Reduced Pressure Backflow Device. | | Water Division | 354361 |
Waste Water Div | Original | D | 4/14/2008 | awerner | awerner | RBD review by Matthew Williams (668-7211). External grease interceptor required. Show proposed location of 3 compartment sink. | | Waste Water Div | 354360 |
Monday Plancheck | Original | / | 4/11/2008 | | MINDY | Location = Monday Plancheck by MINDY | | Monday Plancheck | 354355 |
Plan Coordinator | Original | / | 4/11/2008 | | RONW | Location = Plan Coordinator by RONW | | Plan Coordinator | 354357 |
Construction | Original | D | 4/11/2008 | RONW | RONW | Cafe with 108 o.l. = not B-occ. Revise to A-2 submital. See redlines | | Construction | 354347 |
Construction | Original | / | 4/11/2008 | MINDY | MINDY | Given to RONW by MINDY | | Construction | 354346 |
Construction | Original | / | 4/9/2008 | | MINDY | Location = Construction by MINDY | | Construction | 354345 |
Plan Coordinator | Original | / | 4/9/2008 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 354356 |
Floodplain | Original | A | 4/9/2008 | JEANNINE | JEANNINE | | | Floodplain | 354350 |
Floodplain | Original | / | 4/9/2008 | | MARLENE | Location = Floodplain by MARLENE | | Floodplain | 354349 |
Enumeration | Original | A | 4/9/2008 | MARLENE | MARLENE | | | Enumeration | 354348 |