Mechanical | Original | A | 2/12/2009 | DALEH | DALEH | splice for change to duct and wall layout | | Mechanical | 399948 |
Scanned/Finished Bin | Original | / | 10/28/2008 | | SHARON | Location = Scanned/Finished Bin by SHARON | | Scanned/Finished Bin | 387325 |
To Be Scanned Bin | Original | / | 10/28/2008 | | MINDY | Location = To Be Scanned Bin by MINDY | | To Be Scanned Bin | 387307 |
Fire | Original | A | 10/28/2008 | MINDY | MINDY | 09/26/08 jrm | | Fire | 387306 |
Zoning/Planning | Original | A | 10/28/2008 | MINDY | MINDY | 09/24/08 law | | Zoning/Planning | 387305 |
Finished Bin | Original | / | 9/26/2008 | | MARY | Location = Finished Bin by MARY | | Finished Bin | 382630 |
Mechanical | Original | A | 9/26/2008 | DALEH | DALEH | approved as noted | | Mechanical | 382622 |
Plumbing | Original | A | 9/26/2008 | TCRIPPEN | TCRIPPEN | | | Plumbing | 382603 |
Out to Review | Original | / | 9/26/2008 | MARY | MARY | BRUCE 471-7676 | | Out to Review | 382569 |
Mechanical | Original | / | 9/26/2008 | | SHARON | Location = Mechanical by SHARON | | Mechanical | 382452 |
Plan Coordinator | Original | / | 9/26/2008 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 382447 |
Construction | Original | A | 9/26/2008 | SHELLEY | SHELLEY | | | Construction | 382445 |
Construction | Original | / | 9/26/2008 | SHARON | SHARON | Plan Reviewer = SHELLEY by SHARON | | Construction | 382434 |
Construction | Original | / | 9/24/2008 | | MARY | Location = Construction by MARY | | Construction | 382176 |
Resubmittal 1 | Original | / | 9/24/2008 | MARY | MARY | Resubmittal #1 FOR CONSTRUCTION ONLY | | Resubmittal 1 | 382171 |
Out to Review | Original | / | 9/19/2008 | JEANNINE | JEANNINE | | | Out to Review | 381291 |
Floodplain | Original | A | 9/19/2008 | JEANNINE | JEANNINE | | | Floodplain | 381290 |
Floodplain | Original | / | 9/19/2008 | | MARLENE | Location = Floodplain by MARLENE | | Floodplain | 381289 |
Enumeration | Original | A | 9/19/2008 | MARLENE | MARLENE | | | Enumeration | 381288 |
Out to Review | Original | / | 9/19/2008 | KIM | KIM | bruce smith 471-7676 | | Out to Review | 381283 |
Finished Bin | Original | / | 9/16/2008 | | SHARON | Location = Finished Bin by SHARON | | Finished Bin | 380691 |
Zoning/Planning | Original | D | 9/16/2008 | SHARON | SHARON | 09/15/08 BAD | | Zoning/Planning | 380690 |
Fire | Original | D | 9/16/2008 | SHARON | SHARON | 09/15/08 JM | | Fire | 380689 |
Fire | Original | / | 9/12/2008 | | SHARON | Location = Fire by SHARON | | Fire | 379976 |
Plan Coordinator | Original | / | 9/12/2008 | | DEAN | Location = Plan Coordinator by DEAN | | Plan Coordinator | 379967 |
Electrical | Original | A | 9/12/2008 | DEAN | DEAN | | | Electrical | 379966 |
Electrical | Original | / | 9/11/2008 | SHARON | SHARON | Plan Reviewer = DEAN by SHARON | | Electrical | 379759 |
Electrical | Original | / | 8/29/2008 | | SHARON | Location = Electrical by SHARON | | Electrical | 377935 |
Plan Coordinator | Original | / | 8/29/2008 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 377927 |
Plumbing | Original | D | 8/29/2008 | TCRIPPEN | TCRIPPEN | provide cut sheet for tank less water heater 2.2 gpms required for faucet per the IPC 110 degrees min. required are in coming water is 46 degrees your temperature rise must be 64 degrees at 2.2 gpms | | Plumbing | 377926 |
Plumbing | Original | / | 8/29/2008 | SHARON | SHARON | Plan Reviewer = TCRIPPEN by SHARON | | Plumbing | 377858 |
Plumbing | Original | / | 8/29/2008 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 377845 |
Plan Coordinator | Original | / | 8/29/2008 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 377841 |
Mechanical | Original | D | 8/29/2008 | RUSSELL | RUSSELL | It appears several areas short O.A. reqmts when co2 sensors not used per '05 RBC amendment RBC 304.4.34 section 403.3.3.1, If using RBC 304.4.28 section 403.3, all systems to follow this amendment using ASHRAE standard 62-2001 addendum N when accompanied with the approved ASHRAE spread sheet, co2 sensors to be set at 800 ppm, label floor palns on sheet MP2.01, O.A. ventilation cfms don't match between VAV schedule and ventilation table | | Mechanical | 377840 |
Mechanical | Original | / | 8/27/2008 | SHARON | SHARON | Plan Reviewer = RUSSELL by SHARON | | Mechanical | 377569 |
Mechanical | Original | / | 8/26/2008 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 377107 |
Plan Coordinator | Original | / | 8/26/2008 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 377099 |
Construction | Original | D | 8/26/2008 | SHELLEY | SHELLEY | Revise code study either to reflect original construction or to change type of construction, etc as outlined on A0.11; North 1/3rd of building does not show up on RBD records?; Occupant loads need to be revised per gross requirement of Table 1004.1.2; west mezzanine does not qualify as a mezzanine, needs to be addressed as an additional story; exiting issues from "2nd" floor; exit passageway cannot be used to access storage under stairs; clarify if existing stair from upper floor is an exit enclosure; site plan and zoning approval required for retaining wall and canopy; See plans for all comments. No walk. | | Construction | 377097 |
Construction | Original | / | 8/25/2008 | SHARON | SHARON | Plan Reviewer = SHELLEY by SHARON | | Construction | 377040 |
Construction | Original | / | 8/21/2008 | | MINDY | Location = Construction by MINDY | | Construction | 376553 |
Plan Coordinator | Original | / | 8/20/2008 | | MINDY | Location = Plan Coordinator by MINDY | | Plan Coordinator | 376450 |
Construction | Original | / | 8/20/2008 | | MINDY | Location = Construction by MINDY | | Construction | 376291 |
Plan Coordinator | Original | / | 8/20/2008 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 376278 |
Floodplain | Original | D | 8/20/2008 | JEANNINE | JEANNINE | Require approval of Enumerations. | | Floodplain | 376277 |
Floodplain | Original | / | 8/20/2008 | | MARLENE | Location = Floodplain by MARLENE | | Floodplain | 376275 |
Enumeration | Original | D | 8/20/2008 | MARLENE | MARLENE | Provide Site Plan and Legal Description. If multiple tenants are in this bldg, show which suite is being finished. | | Enumeration | 376274 |