Out to Review | Original | / | 6/24/2009 | SHELBY | SHELBY | Jim 970 566 2280 | | Out to Review | 418022 |
Electrical | Original | A | 6/24/2009 | SHELBY | SHELBY | Splice 13 pages | | Electrical | 418021 |
Mechanical | Original | A | 6/24/2009 | DALEH | DALEH | splice for change to multiple mechanical sheets | | Mechanical | 417985 |
Construction | Original | A | 6/24/2009 | SHELLEY | SHELLEY | Splice OK | | Construction | 417972 |
Plumbing | Original | A | 6/24/2009 | TCRIPPEN | TCRIPPEN | new splice pages moving offices a round | | Plumbing | 417969 |
Scanned/Finished Bin | Original | / | 4/22/2009 | | SHARON | Location = Scanned/Finished Bin by SHARON | | Scanned/Finished Bin | 408394 |
Water Division | Original | N | 4/22/2009 | NELIDA | NELIDA | 2/09/09 mt | | Water Division | 408366 |
Waste Water Div | Original | A | 4/22/2009 | NELIDA | NELIDA | 2/9/09 mt | | Waste Water Div | 408365 |
Gas/Elec. Utils | Original | N | 4/22/2009 | NELIDA | NELIDA | 2/09/09 mt | | Gas/Elec. Utils | 408364 |
Construction | Original | A | 2/10/2009 | MICHAELA | MICHAELA | | | Construction | 399506 |
Out to Review | Original | / | 2/10/2009 | SHELBY | SHELBY | Missy 214 749 0626 | | Out to Review | 399505 |
Electrical | Original | A | 2/10/2009 | SHELBY | SHELBY | $50.00 APR Fee | | Electrical | 399504 |
Mechanical | Original | A | 2/10/2009 | DALEH | DALEH | re approved two changed mechanical sheets | | Mechanical | 399490 |
Zoning/Planning | Original | A | 2/10/2009 | CSZONING | CSZONING | PER CPC DP 97-327-A2MN08. | jgagliardi | Zoning/Planning | 399524 |
Plumbing | Original | A | 2/9/2009 | TCRIPPEN | TCRIPPEN | ok added plan fee 50.00 | | Plumbing | 399464 |
Out to Review | Original | / | 12/17/2008 | NELIDA | NELIDA | brandon 214-749-0626 | | Out to Review | 394082 |
Finished Bin | Original | / | 12/11/2008 | | SHARON | Location = Finished Bin by SHARON | | Finished Bin | 393301 |
Mechanical | Original | A | 12/11/2008 | RUSSELL | RUSSELL | | | Mechanical | 393300 |
Hazmat/High Pile | Original | A | 12/11/2008 | SHARON | SHARON | 12/04/08 kay | | Hazmat/High Pile | 393289 |
Fire | Original | A | 12/11/2008 | SHARON | SHARON | 12/11/08 jrm | | Fire | 393288 |
Zoning/Planning | Original | D | 12/11/2008 | SHARON | SHARON | 12/04/08 lw | | Zoning/Planning | 393282 |
Zoning/Planning | Original | / | 12/2/2008 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 391852 |
Plan Coordinator | Original | / | 12/2/2008 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 391822 |
Electrical | Original | D | 12/2/2008 | SHELBY | SHELBY | For connected load summary calculate load based on 2005 NEC----Confirm with Utility that a peak demand meter was the source of demand history---For one line diagram legend note E-4 verify all information prior to review---Verify loading of all panels all pages prior to review (note 16.470 sheet E 2.4 etc as indicated on sheets)---Panel HR SCCR insufficient for SCA | | Electrical | 391821 |
Electrical | Original | / | 12/1/2008 | SHARON | SHARON | Plan Reviewer = SHELBY by SHARON | | Electrical | 391636 |
Electrical | Original | / | 11/25/2008 | | SHARON | Location = Electrical by SHARON | | Electrical | 391036 |
Gas/Elec. Utils | Original | D | 11/25/2008 | SHARON | SHARON | 11/24/08 | | Gas/Elec. Utils | 391035 |
Water Division | Original | D | 11/25/2008 | SHARON | SHARON | 11/24/08 | | Water Division | 391034 |
Waste Water Div | Original | D | 11/25/2008 | SHARON | SHARON | 11/24/08 | | Waste Water Div | 391033 |
Health Dept. | Original | A | 11/25/2008 | SHARON | SHARON | 11/24/08 ld | | Health Dept. | 391032 |
Monday Plancheck | Original | / | 11/21/2008 | | SHARON | Location = Monday Plancheck by SHARON | | Monday Plancheck | 390704 |
Electrical | Original | / | 11/21/2008 | | MINDY | Location = Electrical by MINDY | | Electrical | 390656 |
Plan Coordinator | Original | / | 11/21/2008 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 390646 |
Plumbing | Original | D | 11/21/2008 | TCRIPPEN | TCRIPPEN | remove old sheets from field set pending waste water rest looks ok | | Plumbing | 390645 |
Plumbing | Original | / | 11/21/2008 | SHARON | SHARON | Plan Reviewer = TCRIPPEN by SHARON | | Plumbing | 390635 |
Plumbing | Original | / | 11/20/2008 | | SHARON | Location = Plumbing by SHARON | | Plumbing | 390613 |
Plan Coordinator | Original | / | 11/20/2008 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 390607 |
Mechanical | Original | D | 11/20/2008 | RUSSELL | RUSSELL | All mechanical sheet okay, need refrigeration for meat cooler, snack bar freezer & cooler to to approve drawings | | Mechanical | 390606 |
Mechanical | Original | / | 11/20/2008 | SHARON | SHARON | Plan Reviewer = RUSSELL by SHARON | | Mechanical | 390466 |
Mechanical | Original | / | 11/18/2008 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 390131 |
Plan Coordinator | Original | / | 11/18/2008 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 390125 |
Construction | Original | D | 11/18/2008 | MICHAELA | MICHAELA | Remove redlines from both sets of plans and submit separately with plan Per PPRBC sect. 1608 indicate design loads for Pg and Pf Provide roof dead loads Provide assumed min. soil bearing pressure for new column pads on page S-3 Open hole inspection required Walk-through OK | | Construction | 390124 |
Construction | Original | / | 11/17/2008 | SHARON | SHARON | Plan Reviewer = MICHAEL by SHARON | | Construction | 389979 |
Construction | Original | / | 11/17/2008 | | MINDY | Location = Construction by MINDY | | Construction | 389972 |
Plan Coordinator | Original | / | 11/17/2008 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 389968 |
Floodplain | Original | A | 11/17/2008 | JEANNINE | JEANNINE | | | Floodplain | 389967 |
Floodplain | Original | / | 11/17/2008 | | MARLENE | Location = Floodplain by MARLENE | | Floodplain | 389961 |
Enumeration | Original | A | 11/17/2008 | MARLENE | MARLENE | | | Enumeration | 389960 |
Enumeration | Original | / | 11/17/2008 | | MINDY | Location = Enumeration by MINDY | | Enumeration | 389954 |
Resubmittal 1 | Original | / | 11/17/2008 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 389953 |
Out to Review | Original | / | 10/9/2008 | MINDY | MINDY | Brandon 214 749 0626 | | Out to Review | 384686 |
Finished Bin | Original | / | 10/6/2008 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 383872 |
Hazmat/High Pile | Original | D | 10/6/2008 | MINDY | MINDY | 10/03/08 kay | | Hazmat/High Pile | 383871 |
Fire | Original | D | 10/6/2008 | MINDY | MINDY | 10/01/08 jrm | | Fire | 383870 |
Zoning/Planning | Original | D | 10/6/2008 | MINDY | MINDY | 9/30/08 lw | | Zoning/Planning | 383869 |
Zoning/Planning | Original | / | 9/29/2008 | | SHARON | Location = Zoning/Planning by SHARON | | Zoning/Planning | 382785 |
Plan Coordinator | Original | / | 9/29/2008 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 382784 |
Electrical | Original | D | 9/29/2008 | SHELBY | SHELBY | PROVIDE EMERGENCY LIGHTING IN PATIENT CARE AREAS PER 517.25,517.45,700.12 NEC---COMPLY 517.13 NEC---LABEL ALL ELECTRICAL EQUIPMENT (PANEL AND CIRCUIT)---FOR NOTE 16.145 PAGE E-2.3 VERIFY ALL INFORMATION PRIOR TO REVIEW---COMPLY422.51 NEC---FOR NOTE ON ONE LINE DIAGRAM LEGEND VERIFY ALL INFORMATION PRIOR TO REVIEW---CONFIRM METERING BY PEAK DEMAND METER---PROVIDE PANEL SCHEDULE FOR PANELS HR,HAC---FOR NOTE 2 ON CONNECTED LOAD TABLE MINIMUM DEMAND NOT NEC COMPLIANT | | Electrical | 382783 |
Electrical | Original | / | 9/26/2008 | SHARON | SHARON | Plan Reviewer = SHELBY by SHARON | | Electrical | 382559 |
Electrical | Original | / | 9/26/2008 | | SHARON | Location = Electrical by SHARON | | Electrical | 382558 |
Plan Coordinator | Original | / | 9/25/2008 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 382204 |
Plumbing | Original | D | 9/25/2008 | TCRIPPEN | TCRIPPEN | Sloan weu shows up as a water less urinal on the Internet theses are prohibited , your reel hoes will require vacuum breaker protection , vacuum breaker protection required on service sinks not check valves , your S-1 with hose will require vacuum breaker , all fixtures to be scheduled even those supplied by others clarify B34G and B35G rack washer and oven rack gas waste receptors needed prep. sink to be indirect waste SB38 , YH yard hydrant to have back flow protection at the exiting of the building and labeled NON-POTABLE water , your Y-2 drains into the ground and is capable of pulling water back into the system , wood ford 21P needs back flow protection , floor drains are designed for emergence use only , waste receptors must be used in place of floor drains if other than emergence ///// no walk through ///// | | Plumbing | 382198 |
Plumbing | Original | / | 9/24/2008 | SHARON | SHARON | Plan Reviewer = TCRIPPEN by SHARON | | Plumbing | 382014 |
Plumbing | Original | / | 9/16/2008 | | SHARON | Location = Plumbing by SHARON | | Plumbing | 380639 |
Plan Coordinator | Original | / | 9/16/2008 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 380629 |
Mechanical | Original | D | 9/16/2008 | RUSSELL | RUSSELL | Minimum velocity not met with duct size shown, O.A. issue with RTU-21 when exhausting 1800 cfm, need several existing RTU's scheduled to show O.A. % to verify adequate in remodeled/new areas, CO2 sensor(s) per '05 RBC amendments, ASHRAE standard 62-2001 addendum N required with an approved ASHRAE spread sheet, refrigerant quantities requires if condensers remotely located on roof, need to indicate interlocks with appropriate RTU's with new EF's, wrapping of top of hood with approved wrap when celing is located against hood, + more, see plans for additional comments | | Mechanical | 380628 |
Mechanical | Original | / | 9/16/2008 | SHARON | SHARON | Plan Reviewer = RUSSELL by SHARON | | Mechanical | 380408 |
Mechanical | Original | / | 9/15/2008 | | SHARON | Location = Mechanical by SHARON | | Mechanical | 380213 |
Plan Coordinator | Original | / | 9/15/2008 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 380204 |
Construction | Original | D | 9/15/2008 | MICHAELA | MICHAELA | Provide soil design loads Provide and reference soils report for new foundation work Comply with Sec. 1210 IBC for remodeled bathrooms Show 18" vertical grab bars at H.C. toilets Walk-through OK | | Construction | 380198 |
Construction | Original | / | 9/15/2008 | SHARON | SHARON | Plan Reviewer = MICHAEL by SHARON | | Construction | 380175 |
Construction | Original | / | 9/4/2008 | | SHARON | Location = Construction by SHARON | | Construction | 378521 |
Plan Coordinator | Original | / | 9/4/2008 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 378487 |
Floodplain | Original | D | 9/4/2008 | JEANNINE | JEANNINE | Require approved address. | | Floodplain | 378486 |
Enumeration | Original | D | 9/3/2008 | MARLENE | MARLENE | Provide site plan, and include legal description and tax ID number. | | Enumeration | 378352 |