Plumbing | Original | A | 1/23/2009 | TCRIPPEN | TCRIPPEN | new splice page 3/4 water line OK | | Plumbing | 397358 |
Out to Review | Original | / | 11/10/2008 | MARY | MARY | p/u by plumbing contractor Larry | | Out to Review | 389107 |
Scanned/Finished Bin | Original | / | 11/10/2008 | | SHARON | Location = Scanned/Finished Bin by SHARON | | Scanned/Finished Bin | 389104 |
To Be Scanned Bin | Original | / | 11/7/2008 | | KIM | Location = To Be Scanned Bin by KIM | | To Be Scanned Bin | 389061 |
Plumbing | Original | A | 11/7/2008 | TCRIPPEN | TCRIPPEN | | | Plumbing | 389060 |
Out to Review | Original | / | 11/7/2008 | SHELBY | SHELBY | Tony 491 1198 | | Out to Review | 389057 |
Electrical | Original | A | 11/7/2008 | SHELBY | SHELBY | | | Electrical | 389056 |
Mechanical | Original | A | 11/7/2008 | DALEH | DALEH | approved as noted | | Mechanical | 389050 |
Construction | Original | A | 11/3/2008 | MICHAELA | MICHAELA | | | Construction | 388096 |
Out to Review | Original | / | 11/3/2008 | MINDY | MINDY | 491 1198 | | Out to Review | 388093 |
Finished Bin | Original | / | 10/31/2008 | | SHARON | Location = Finished Bin by SHARON | | Finished Bin | 387981 |
Fire | Original | A | 10/31/2008 | SHARON | SHARON | 10/29/08 jrm | | Fire | 387980 |
Fire | Original | / | 10/28/2008 | | MINDY | Location = Fire by MINDY | | Fire | 387330 |
Plan Coordinator | Original | / | 10/28/2008 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 387328 |
Plumbing | Original | D | 10/28/2008 | RUSSELL | RUSSELL | Provide information on shower valve to meet compliance with '03 IPC sections 424.2 & 424.3, backflow protection req'd at coffee maker, provide materials list for DWV & water piping, provide water piping analysis, gpms, psi, losses and longest length per Apendix E, cold water to dishwasher ?, size cw serving 2 WC's or WC & urinal, must vent S-2 unless structural conditions prohibit venting or a window prohibits venting of S-2 | | Plumbing | 387327 |
Plumbing | Original | / | 10/27/2008 | SHARON | SHARON | Plan Reviewer = RUSSELL by SHARON | | Plumbing | 387107 |
Plumbing | Original | / | 10/27/2008 | | SHARON | Location = Plumbing by SHARON | | Plumbing | 386992 |
Mechanical | Original | D | 10/27/2008 | DALEH | DALEH | see notes 24 and 25 to be added on sheet m0.1 indicate on sheet m1.1 what ducts are being supplied by what rtu ef-2 diffuser cfm's show different from schedule cfm schedule existing rtu's walk through o.k. return red lines with next review | | Mechanical | 386989 |
Mechanical | Original | / | 10/27/2008 | SHARON | SHARON | Plan Reviewer = DALEH by SHARON | | Mechanical | 386960 |
Mechanical | Original | / | 10/24/2008 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 386816 |
Electrical | Original | D | 10/24/2008 | GARYL | GARYL | NEED IECC WORKSHEETS AND CALCULATIONS | | Electrical | 386815 |
Electrical | Original | / | 10/23/2008 | MINDY | MINDY | Plan Reviewer = GARYL by MINDY | | Electrical | 386698 |
Electrical | Original | / | 10/22/2008 | | SHARON | Location = Electrical by SHARON | | Electrical | 386463 |
Construction | Original | D | 10/22/2008 | STEPHEN | STEPHEN | Provide new detail for "floating wall". Detail connection of partition wall at structure to allow floor slab to move up or down 11/2" (3" total). OR -- provide soils report indicating provisions for floor slab movement is not required.
Doors 100, 100-1, and 124-1 provide sign on egress side stating "This door to remain unlocked when building is occupied". | | Construction | 386457 |
Construction | Original | / | 10/21/2008 | SHARON | SHARON | Plan Reviewer = STEPHEN by SHARON | | Construction | 386294 |
Construction | Original | / | 10/21/2008 | | NELIDA | Location = Construction by NELIDA | | Construction | 386259 |
Floodplain | Original | A | 10/21/2008 | TIMC | TIMC | | | Floodplain | 386258 |
Enumeration | Original | A | 10/21/2008 | MARLENE | MARLENE | | | Enumeration | 386257 |
Out to Review | Original | / | 10/21/2008 | KIM | KIM | WALKING PLANS | | Out to Review | 386253 |