Out to Review | Original | / | 1/15/2009 | SHELBY | SHELBY | Brent 499 1377 | | Out to Review | 396570 |
Electrical | Original | A | 1/15/2009 | SHELBY | SHELBY | | | Electrical | 396569 |
Out to Review | Original | / | 1/5/2009 | MARY | MARY | BRENT - ALTHOUSE - 499-1377 | | Out to Review | 395545 |
Finished Bin | Original | / | 12/31/2008 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 395409 |
Plan Coordinator | Original | / | 12/31/2008 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 395403 |
Electrical | Original | D | 12/31/2008 | SHELBY | SHELBY | Need engineer to clearly indicate that the area encompassed in this scope of work is not a classified area per NEC.If engineer cannot specify clearly and without ambiguity that area is not classified per NEC then engineer must specify classification. Wiring method for the area must follow NEC for that engineer specified classification.------For note bottom right of page E-1,engineer must verify information prior to review,engineer must verify the accuracy of the information supplied, independent verification of the document is is not to be substituted for verification prior to review. | | Electrical | 395397 |
Electrical | Original | / | 12/15/2008 | SHELBY | SHELBY | Plan Reviewer = SHELBY by SHELBY----From Brent 499 1377 | | Electrical | 393665 |
Electrical | Original | / | 12/15/2008 | | SHELBY | Location = Electrical by SHELBY | | Electrical | 393663 |