Scanned/Finished Bin | Original | / | 6/12/2009 | | SHARON | Location = Scanned/Finished Bin by SHARON | | Scanned/Finished Bin | 416424 |
To Be Scanned Bin | Original | / | 6/12/2009 | | SHARON | Location = To Be Scanned Bin by SHARON | | To Be Scanned Bin | 416394 |
Mechanical | Original | A | 6/12/2009 | TCRIPPEN | TCRIPPEN | | | Mechanical | 416374 |
Plan Coordinator | Original | / | 6/12/2009 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 416372 |
Plumbing | Original | N | 6/12/2009 | TCRIPPEN | TCRIPPEN | no plumbing work being done travel distance is approx 200 fee per Tammy 1-314-415-2400 | | Plumbing | 416370 |
Plumbing | Original | / | 6/12/2009 | SHELBY | SHELBY | Plan Reviewer = TCRIPPEN by SHELBY | | Plumbing | 416281 |
Plumbing | Original | / | 6/12/2009 | | SHELBY | Location = Plumbing by SHELBY | | Plumbing | 416280 |
Electrical | Original | A | 6/12/2009 | SHELBY | SHELBY | $50.00 third review | | Electrical | 416279 |
Electrical | Original | / | 6/12/2009 | SHARON | SHARON | Plan Reviewer = SHELBY by SHARON | | Electrical | 416246 |
Electrical | Original | / | 6/11/2009 | | MINDY | Location = Electrical by MINDY | | Electrical | 416144 |
Resubmittal 2 | Original | / | 6/11/2009 | MINDY | MINDY | Resubmittal #2 | | Resubmittal 2 | 416143 |
Out to Review | Original | / | 6/8/2009 | KIM | KIM | MICHAEL HERRERA FROM SHAMROCK DELIVERY 303-220-1700 | | Out to Review | 415563 |
Plan Coordinator | Original | / | 6/5/2009 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 415201 |
Electrical | Original | D | 6/5/2009 | SHELBY | SHELBY | Panel A panel schedule shows incorrect main breaker----Provide lighting demolition plan to verify compliance with 90.1 ASHRAE ----Show complete one line (Utility transformer to new panel)-------------Needs complete re review------------------ | | Electrical | 415200 |
Electrical | Original | / | 6/4/2009 | SHARON | SHARON | Plan Reviewer = SHELBY by SHARON | | Electrical | 414919 |
Electrical | Original | / | 6/3/2009 | | MINDY | Location = Electrical by MINDY | | Electrical | 414870 |
Plan Coordinator | Original | / | 6/3/2009 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 414860 |
Construction | Original | A | 6/3/2009 | SHELLEY | SHELLEY | | | Construction | 414859 |
Construction | Original | / | 6/3/2009 | SHARON | SHARON | Plan Reviewer = SHELLEY by SHARON | | Construction | 414854 |
Construction | Original | / | 6/3/2009 | MINDY | MINDY | All new pages submitted - needs to go back through Construction also. | | Construction | 414752 |
Resubmittal 1 | Original | / | 6/3/2009 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 414751 |
Out to Review | Original | / | 5/26/2009 | MARY | MARY | don..shamerock delivery...303-220-1700 | | Out to Review | 413445 |
Finished Bin | Original | / | 5/18/2009 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 412305 |
Hazmat | Original | N | 5/18/2009 | CSFIRE | CSFIRE | | csfdit | Hazmat | 412302 |
Fire | Original | A | 5/18/2009 | CSFIRE | CSFIRE | SUBMITTED BY: MILAM, JONATHAN R | csfdit | Fire | 412301 |
Fire | Original | / | 5/18/2009 | | SHARON | Location = Fire by SHARON | | Fire | 412144 |
Plan Coordinator | Original | / | 5/15/2009 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 412082 |
Electrical | Original | D | 5/15/2009 | SHELBY | SHELBY | Provide complete one line---For one line diagram note one (E300) and general note 2 (E100) verify prior to review---Clearly show new load VS existing load ---Provide IECC calculation(2003)---Needs complete re review | | Electrical | 412081 |
Electrical | Original | / | 5/15/2009 | SHARON | SHARON | Plan Reviewer = SHELBY by SHARON | | Electrical | 412070 |
Electrical | Original | / | 5/7/2009 | | SHARON | Location = Electrical by SHARON | | Electrical | 410626 |
Plan Coordinator | Original | / | 5/7/2009 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 410621 |
Mechanical | Original | D | 5/7/2009 | RUSSELL | RUSSELL | Declare if space is part of Mall smoke evac. and add notes as req'd and if not, make declaration that space is not part of Mall smoke evac., schedule existing AHU to verify O.A. reqmts. | | Mechanical | 410620 |
Mechanical | Original | / | 5/6/2009 | SHARON | SHARON | Plan Reviewer = RUSSELL by SHARON | | Mechanical | 410578 |
Mechanical | Original | / | 5/6/2009 | | SHARON | Location = Mechanical by SHARON | | Mechanical | 410571 |
Plan Coordinator | Original | / | 5/6/2009 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 410558 |
Plumbing | Original | D | 5/6/2009 | TCRIPPEN | TCRIPPEN | provide rest room information with travel distance from back of store to bath rooms | | Plumbing | 410557 |
Plumbing | Original | / | 5/6/2009 | SHARON | SHARON | Plan Reviewer = TCRIPPEN by SHARON | | Plumbing | 410496 |
Plumbing | Original | / | 5/5/2009 | | SHARON | Location = Plumbing by SHARON | | Plumbing | 410295 |
Plan Coordinator | Original | / | 5/5/2009 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 410293 |
Construction | Original | A | 5/5/2009 | SHELLEY | SHELLEY | | | Construction | 410292 |
Construction | Original | / | 5/5/2009 | SHARON | SHARON | Plan Reviewer = SHELLEY by SHARON | | Construction | 410152 |
Construction | Original | / | 5/4/2009 | | MINDY | Location = Construction by MINDY | | Construction | 410069 |
Plan Coordinator | Original | / | 5/4/2009 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 410056 |
Floodplain | Original | A | 5/4/2009 | TIMC | TIMC | | | Floodplain | 410055 |
Enumeration | Original | A | 5/4/2009 | TIMC | TIMC | | | Enumeration | 410054 |