Scanned/Finished Bin | Original | / | 1/20/2010 | | SHARON | Location = Scanned/Finished Bin by SHARON | | Scanned/Finished Bin | 442439 |
To Be Scanned Bin | Original | / | 1/19/2010 | | MINDY | Location = To Be Scanned Bin by MINDY | | To Be Scanned Bin | 442315 |
Fire | Original | A | 1/19/2010 | MINDY | MINDY | 01/12/10 dew | | Fire | 442314 |
Out to Review | Original | / | 1/13/2010 | MARY | MARY | chris w/ge...314-9867 | | Out to Review | 441872 |
Finished Bin | Original | / | 1/12/2010 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 441771 |
Hazmat | Original | A | 1/12/2010 | MINDY | MINDY | 12/11/09 kay | | Hazmat | 441770 |
Zoning/Planning | Original | A | 1/12/2010 | MINDY | MINDY | 12/09/09 dmt | | Zoning/Planning | 441769 |
Fire | Original | D | 1/12/2010 | CSFIRE | CSFIRE | SMOKE SYSTEM MATRICES NEED TO BE UPDATED TO REFLECT NEW WORK; SEVERAL NEW DAMPERS ON 6TH FLOOR ARE NOT INCLUDED IN MATRIX. 2009-0978-cn-1 for complete review comments | csfdit | Fire | 441735 |
Fire | Original | / | 1/8/2010 | | SHARON | Location = Fire by SHARON | | Fire | 441392 |
Plan Coordinator | Original | / | 1/8/2010 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 441388 |
Plumbing | Original | A | 1/8/2010 | TCRIPPEN | TCRIPPEN | | | Plumbing | 441387 |
Plumbing | Original | / | 1/8/2010 | SHARON | SHARON | Plan Reviewer = TCRIPPEN by SHARON | | Plumbing | 441385 |
Plumbing | Original | / | 1/8/2010 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 441368 |
Mechanical | Original | A | 1/8/2010 | DALEH | DALEH | spoke with engineer and lynn s. about smoke damper comments I approved it due to variance issued in 2007 in regards to smoke dampers | | Mechanical | 441364 |
Mechanical | Original | / | 1/7/2010 | SHARON | SHARON | Plan Reviewer = DALEH by SHARON | | Mechanical | 441278 |
Mechanical | Original | / | 1/7/2010 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 441209 |
Plan Coordinator | Original | / | 1/7/2010 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 441205 |
Electrical | Original | A | 1/7/2010 | SHELBY | SHELBY | | | Electrical | 441204 |
Electrical | Original | / | 1/6/2010 | MINDY | MINDY | Plan Reviewer = SHELBY by MINDY | | Electrical | 441192 |
Resubmittal 2 | Original | / | 12/31/2009 | MARY | MARY | Resubmittal #2 | | Resubmittal 2 | 440872 |
Electrical | Original | / | 12/31/2009 | | MARY | Location = Electrical by MARY | | Electrical | 440871 |
Construction | Original | A | 12/21/2009 | MICHAELA | MICHAELA | | | Construction | 440052 |
Out to Review | Original | / | 12/21/2009 | KIM | KIM | mark 243-7402 | | Out to Review | 440042 |
Finished Bin | Original | / | 12/21/2009 | | SHARON | Location = Finished Bin by SHARON | | Finished Bin | 439961 |
Plan Coordinator | Original | / | 12/21/2009 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 439942 |
Construction | Original | D | 12/21/2009 | SHELLEY | SHELLEY | Indicated fire partition on G002B does not meet any location criteria as specified in IBC 708; missing partition A3X for 1-hour fire partition. Walk ok. | | Construction | 439941 |
Construction | Original | / | 12/21/2009 | SHARON | SHARON | Plan Reviewer = SHELLEY by SHARON | | Construction | 439933 |
Construction | Original | / | 12/18/2009 | | MINDY | Location = Construction by MINDY | | Construction | 439919 |
Resubmittal 1 | Original | / | 12/18/2009 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 439918 |
Out to Review | Original | / | 12/16/2009 | NELIDA | NELIDA | Kristi Williams 471-7566 | | Out to Review | 439539 |
Finished Bin | Original | / | 12/14/2009 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 439294 |
Hazmat | Original | / | 12/11/2009 | | CSFIRE | Location = Hazmat by CSFIRE | csfdit | Hazmat | 439035 |
Fire | Original | D | 12/11/2009 | CSFIRE | CSFIRE | NEED MECHANICAL PLAN SHOWING ALL DAMPERS AND LABELS TO VERIFY SMOKE PURGE SYSTEM | csfdit | Fire | 439034 |
Zoning/Planning | Original | / | 12/4/2009 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 438286 |
Plan Coordinator | Original | / | 12/3/2009 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 438273 |
Electrical | Original | D | 12/3/2009 | SHELBY | SHELBY | Size transformer secondary system bonding jumper per 250.28 and 250.66 NEC for TCL6A and TNL6A. | | Electrical | 438272 |
Electrical | Original | / | 12/3/2009 | SHARON | SHARON | Plan Reviewer = SHELBY by SHARON | | Electrical | 438263 |
Electrical | Original | / | 12/3/2009 | | MINDY | Location = Electrical by MINDY | | Electrical | 438132 |
Mechanical | Original | D | 12/3/2009 | DALEH | DALEH | see plans for damper red lines see vav box schedule for red lines return all red lines with next review return sheets with rbd check mark and circled in red | | Mechanical | 438124 |
Mechanical | Original | / | 12/1/2009 | SHARON | SHARON | Plan Reviewer = DALEH by SHARON | | Mechanical | 437714 |
Mechanical | Original | / | 12/1/2009 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 437701 |
Plan Coordinator | Original | / | 12/1/2009 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 437700 |
Plumbing | Original | D | 12/1/2009 | TCRIPPEN | TCRIPPEN | schedule all fixtures and materials with manufacture and model numbers see question marks on page P101 provide water pipe size analysis on plans | | Plumbing | 437699 |
Plumbing | Original | / | 11/30/2009 | SHARON | SHARON | Plan Reviewer = TCRIPPEN by SHARON | | Plumbing | 437667 |
Plumbing | Original | / | 11/30/2009 | | SHARON | Location = Plumbing by SHARON | | Plumbing | 437662 |
Plan Coordinator | Original | / | 11/30/2009 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 437648 |
Construction | Original | D | 11/30/2009 | SHELLEY | SHELLEY | Modify occupant load to account for gross square footage per table 1004.1.2; rated wall missing from wall legend; no UL listings for rated walls provided (need to review all walls once this is provided); no walk. | | Construction | 437647 |
Construction | Original | / | 11/30/2009 | SHARON | SHARON | Plan Reviewer = SHELLEY by SHARON | | Construction | 437636 |
Construction | Original | / | 11/23/2009 | | SHARON | Location = Construction by SHARON | | Construction | 437180 |
Plan Coordinator | Original | / | 11/23/2009 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 437174 |
Enumeration | Original | A | 11/23/2009 | TIMC | TIMC | | | Enumeration | 437173 |
Floodplain | Original | N | 11/23/2009 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 437168 |