Health Dept. | Original | A | 9/9/2010 | HEALTHDEPT | HEALTHDEPT | Final inspection approved 9/9/10 MYM 578-3140 | Michelle Martinez | Health Dept. | 474521 |
Scanned/Finished Bin | Original | / | 8/2/2010 | | REBECCA | Location = Scanned/Finished Bin by REBECCA | | Scanned/Finished Bin | 469334 |
To Be Scanned Bin | Original | / | 8/2/2010 | | REBECCA | Location = To Be Scanned Bin by REBECCA | | To Be Scanned Bin | 469325 |
Plan Coordinator | Original | / | 8/2/2010 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 469311 |
Mechanical | Original | A | 8/2/2010 | RUSSELL | RUSSELL | Splice for all mechanical sheets | | Mechanical | 469310 |
Mechanical | Original | / | 8/2/2010 | REBECCA | REBECCA | Plan Reviewer = RUSSELL by REBECCA | | Mechanical | 469302 |
Mechanical | Original | / | 8/2/2010 | REBECCA | REBECCA | Plan Reviewer = DALEH by REBECCA | | Mechanical | 469301 |
Mechanical | Original | / | 8/2/2010 | REBECCA | REBECCA | Plan Reviewer = RUSSELL by REBECCA | | Mechanical | 469300 |
Mechanical | Original | / | 7/30/2010 | | NELIDA | Location = Mechanical by NELIDA - splice | | Mechanical | 469295 |
Construction | Original | A | 7/23/2010 | JOHNJ | JOHNJ | PAID (REC#921919) ADDITIONAL PLAN REVIEW TIME: $50 From: JOHNJ splice is for not breaching the existing demising wall for bathroom entry, keeping existing ext walls intact added interior wall for existing bathroom entry, no other changes at all, 2 pgs total a103 & a104 | | Construction | 468189 |
Out to Review | Original | / | 6/17/2010 | JAN | JAN | Stan 491-6510 | | Out to Review | 462489 |
To Be Scanned Bin | Original | / | 6/15/2010 | | REBECCA | Location = To Be Scanned Bin by REBECCA | | To Be Scanned Bin | 462051 |
Finished Bin | Original | / | 5/21/2010 | | NELIDA | Location = Finished Bin by NELIDA | | Finished Bin | 458641 |
Water Division | Original | A | 5/21/2010 | NELIDA | NELIDA | MW 5/21/10 | | Water Division | 458638 |
Waste Water Div | Original | A | 5/21/2010 | NELIDA | NELIDA | MW 5/21/10 | | Waste Water Div | 458637 |
Plumbing | Original | A | 5/21/2010 | RUSSELL | RUSSELL | | | Plumbing | 458625 |
Mechanical | Original | A | 5/21/2010 | RUSSELL | RUSSELL | | | Mechanical | 458624 |
Out to Review | Original | / | 5/19/2010 | SHELBY | SHELBY | Tom 648 7722 | | Out to Review | 458203 |
Electrical | Original | A | 5/19/2010 | SHELBY | SHELBY | | | Electrical | 458201 |
Out to Review | Original | / | 3/24/2010 | MINDY | MINDY | Paisley 573 2277 | | Out to Review | 450503 |
Water Division | Original | D | 3/23/2010 | MINDY | MINDY | 03/12/10 amw | | Water Division | 450107 |
Finished Bin | Original | / | 3/23/2010 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 450106 |
Waste Water Div | Original | D | 3/23/2010 | MINDY | MINDY | 03/12/10 amw | | Waste Water Div | 450105 |
Fire | Original | A | 3/22/2010 | CSFIRE | CSFIRE | SUBMITTED BY: COOPER, KRISTOPHER D | csfdit | Fire | 450020 |
Fire | Original | / | 3/22/2010 | | MINDY | Location = Fire by MINDY | | Fire | 449943 |
Plan Coordinator | Original | / | 3/22/2010 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 449934 |
Electrical | Original | D | 3/22/2010 | SHELBY | SHELBY | Provide complete one line (from utility transformer to branch circuit panel boards) | | Electrical | 449933 |
Electrical | Original | / | 3/22/2010 | MINDY | MINDY | Plan Reviewer = SHELBY by MINDY | | Electrical | 449909 |
Electrical | Original | / | 3/18/2010 | | SHARON | Location = Electrical by SHARON | | Electrical | 449591 |
Plan Coordinator | Original | / | 3/18/2010 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 449587 |
Plumbing | Original | D | 3/18/2010 | TCRIPPEN | TCRIPPEN | need waste water approvals | | Plumbing | 449586 |
Plumbing | Original | / | 3/18/2010 | SHARON | SHARON | Plan Reviewer = TCRIPPEN by SHARON | | Plumbing | 449584 |
Plumbing | Original | / | 3/18/2010 | | SHARON | Location = Plumbing by SHARON | | Plumbing | 449549 |
Plan Coordinator | Original | / | 3/18/2010 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 449545 |
Mechanical | Original | D | 3/18/2010 | RUSSELL | RUSSELL | Still need cut sheets on tortilla machine (in ENGLISH), to verfiy exhaust outlet size, btuh input and if Type I hood req'd over machine, still need letter from structural engineer to verify structure adequate to support weight of new MUA or engineering on structure, is exhaust outlet to be 8" or 18", see P2.0 for gas piping comments based on what appears to be actual length versus length provided, gas pipe blocking height shall be minimum 3 1/2" on roof for new piping, | | Mechanical | 449544 |
Mechanical | Original | / | 3/17/2010 | MINDY | MINDY | Plan Reviewer = RUSSELL by MINDY | | Mechanical | 449489 |
Mechanical | Original | / | 3/17/2010 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 449486 |
Resubmittal 1 | Original | / | 3/17/2010 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 449485 |
Health Dept. | Original | A | 3/17/2010 | HEALTHDEPT | HEALTHDEPT | Plan set signed off by Lee Griffen for Tara Strachan. Mike McCarthy. | mmccarthy | Health Dept. | 449474 |
Plumbing | Original | D | 3/17/2010 | TCRIPPEN | TCRIPPEN | NEED WASTE WATER AND HEALTH | | Plumbing | 449450 |
Construction | Original | A | 3/17/2010 | MICHAELA | MICHAELA | | | Construction | 449439 |
Out to Review | Original | / | 3/15/2010 | JAN | JAN | Tom Duke 719-648-7722 | | Out to Review | 448963 |
Finished Bin | Original | / | 3/15/2010 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 448923 |
Plumbing | Original | D | 3/15/2010 | TCRIPPEN | TCRIPPEN | restroom shall not not be through kitchen , provide water pipe size analysis on plans , plans not stamped by health , still need waste water approval | | Plumbing | 448914 |
Plan Coordinator | Original | / | 3/15/2010 | MINDY | MINDY | Plan Reviewer = TCRIPPEN by MINDY | | Plan Coordinator | 448901 |
Plumbing | Original | / | 3/15/2010 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 448897 |
Construction | Original | D | 3/15/2010 | MICHAELA | MICHAELA | | | Construction | 448896 |
Plan Coordinator | Original | / | 3/15/2010 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 448895 |
Construction | Original | / | 3/15/2010 | MINDY | MINDY | Plan Reviewer = MICHAEL by MINDY | | Construction | 448894 |
Water Division | Original | D | 3/15/2010 | MINDY | MINDY | 03/12/10 mlw | | Water Division | 448890 |
Waste Water Div | Original | D | 3/15/2010 | MINDY | MINDY | 03/12/10 mlw | | Waste Water Div | 448889 |
Construction | Original | / | 3/15/2010 | | MINDY | Location = Construction by MINDY | | Construction | 448888 |
Hazmat | Original | N | 3/15/2010 | MINDY | MINDY | 02/26/10 dew | | Hazmat | 448887 |
Health Dept. | Original | A | 3/10/2010 | HEALTHDEPT | HEALTHDEPT | Minimum hot water requirements: 94GPH recovery rate at a 100 degree F rise or 104,402.66 BTUS. Facility increased hot water heater size to Rheem GP100-150 150,000 BTUS and a recovery rate of 146 GPH at a 100 degree F rise. TS 3/10/10 | TaraStrachan | Health Dept. | 448444 |
CSU Utilities | Original | / | 2/26/2010 | | CSFIRE | Location = CSU Utilities by CSFIRE | csfdit | CSU Utilities | 446998 |
Fire | Original | D | 2/26/2010 | CSFIRE | CSFIRE | NEED RBD STICKED FILLED OUT TO PERFORM COMPLETE REVIEW | csfdit | Fire | 446997 |
Fire | Original | / | 2/22/2010 | | CSZONING | Location = Fire by CSZONING | Dtortorice | Fire | 446447 |
Zoning/Planning | Original | A | 2/22/2010 | CSZONING | CSZONING | INT REM TO RESTAURANT. COMM CENTER. | Dtortorice | Zoning/Planning | 446446 |
Zoning/Planning | Original | / | 2/16/2010 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 445696 |
Plan Coordinator | Original | / | 2/16/2010 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 445692 |
Plumbing | Original | D | 2/16/2010 | TCRIPPEN | TCRIPPEN | REVIEW STOPPED NEED APPROVED CODY STUDY FROM CONSTRUCTION | | Plumbing | 445691 |
Plumbing | Original | / | 2/16/2010 | MINDY | MINDY | Plan Reviewer = TCRIPPEN by MINDY | | Plumbing | 445653 |
Plumbing | Original | / | 2/16/2010 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 445635 |
Plan Coordinator | Original | / | 2/16/2010 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 445628 |
Mechanical | Original | D | 2/16/2010 | RUSSELL | RUSSELL | Indicate if ventilation Table provide is per ASHRAE Standard 62-2001 as adopted per RBC amendments ?, unable to verify O.A. ventilation correct until construction review is statisfied with occupancy classification, verify gas summary table with notes on sheet P2.0, provide manufacturers installation instructions and cut sheets to verify ehaust vnet, if Type I hood required, btuh input, provide S.A. cfms at all S.A. registers, provide weight of MUA, if over 300#'s provide letter from structural engineer to verify structure adequate or engineering on structure, minimum velocity not met with exhaust cfms provide and size of grease duct, shwo section through hood to show relationship with ceiling, if ceiling abutts hood, must also protect top of hood, using rated shaft for grease duct or approved 1 hour wrap ?, coordinate exhaust cfms between sheets, gas missing to RTU, Mua and future tortilla machine ? + more, see plans for additional comments | | Mechanical | 445626 |
Mechanical | Original | / | 2/16/2010 | MINDY | MINDY | Plan Reviewer = RUSSELL by MINDY | | Mechanical | 445469 |
Mechanical | Original | / | 2/12/2010 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 445460 |
Plan Coordinator | Original | / | 2/12/2010 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 445430 |
Electrical | Original | D | 2/12/2010 | SHELBY | SHELBY | Provide SCA piont to point method based on utility information. Show size of conductor between new panel and transformer. Show SCCR of new panel. Provide IECC calculation (2003). | | Electrical | 445429 |
Electrical | Original | / | 2/12/2010 | MINDY | MINDY | Plan Reviewer = SHELBY by MINDY | | Electrical | 445336 |
Electrical | Original | / | 2/12/2010 | | MINDY | Location = Electrical by MINDY | | Electrical | 445311 |
Plan Coordinator | Original | / | 2/12/2010 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 445307 |
Construction | Original | D | 2/12/2010 | MICHAELA | MICHAELA | RBD records indicate this building was constructed as type IV-1 hr. - this corresponds with type II-A construction under current codes - provide documentation to revise type of construction Provide current occupancies on either side of suite N Use table 302.3.2 for required occupancy separation If change of occupancy, provide allowable area calculations for entire building with sum of the ratios Verify metal stud construction adjacent to type 1 grease hood Missing 18" vertical grab bar at toilet room per ANSI 117.7 Indicate compliance with IBC sect. 1210 for floor and wall finish at toilet room, RESTROOM MUST BE ON ACCESSIBLE ROUTE NOT THROUGH KITCHEN No walk-through | | Construction | 445306 |
Construction | Original | / | 2/11/2010 | MINDY | MINDY | Plan Reviewer = MICHAEL by MINDY | | Construction | 445261 |
Construction | Original | / | 2/11/2010 | | MINDY | Location = Construction by MINDY | | Construction | 445141 |
Plan Coordinator | Original | / | 2/10/2010 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 445139 |
Floodplain | Original | A | 2/10/2010 | TIMC | TIMC | | | Floodplain | 445138 |
Enumeration | Original | A | 2/10/2010 | TIMC | TIMC | | | Enumeration | 445137 |