Electrical | Original | A | 5/25/2010 | SHELBY | SHELBY | Splice | | Electrical | 459080 |
Mechanical | Original | A | 5/25/2010 | DALEH | DALEH | splice for new mechanical sheets | | Mechanical | 459062 |
Out to Review | Original | / | 3/26/2010 | KIM | KIM | SEAN 200-6510 | | Out to Review | 450761 |
Scanned/Finished Bin | Original | / | 3/25/2010 | | REBECCA | Location = Scanned/Finished Bin by REBECCA | | Scanned/Finished Bin | 450708 |
To Be Scanned Bin | Original | / | 3/25/2010 | | KIM | Location = To Be Scanned Bin by KIM | | To Be Scanned Bin | 450699 |
Mechanical | Original | A | 3/25/2010 | RUSSELL | RUSSELL | | | Mechanical | 450696 |
Out to Review | Original | / | 3/25/2010 | KIM | KIM | SEAN 200-6510 | | Out to Review | 450694 |
Finished Bin | Original | / | 3/24/2010 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 450432 |
Plan Coordinator | Original | / | 3/24/2010 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 450424 |
Mechanical | Original | D | 3/24/2010 | RUSSELL | RUSSELL | Need new mechanical pages inserted into field set and voided sheets removed from permit set prior to approval of mechanical | | Mechanical | 450423 |
Mechanical | Original | / | 3/22/2010 | MINDY | MINDY | Plan Reviewer = RUSSELL by MINDY | | Mechanical | 449979 |
Mechanical | Original | / | 3/22/2010 | | KIM | Location = Mechanical by KIM | | Mechanical | 449969 |
Resubmittal 1 | Original | / | 3/22/2010 | KIM | KIM | Resubmittal #1 | | Resubmittal 1 | 449968 |
Construction | Original | A | 3/22/2010 | MICHAELA | MICHAELA | | | Construction | 449967 |
Out to Review | Original | / | 3/9/2010 | KIM | KIM | sean 200-6510 | | Out to Review | 448186 |
Finished Bin | Original | / | 2/22/2010 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 446341 |
Zoning/Planning | Original | N | 2/22/2010 | MINDY | MINDY | 02/18/10 mm | | Zoning/Planning | 446340 |
Fire | Original | A | 2/19/2010 | CSFIRE | CSFIRE | SUBMITTED BY: EMBRES, RHONDA C
02/19/10 Approved rce | csfdit | Fire | 446199 |
Zoning/Planning | Original | / | 2/17/2010 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 445859 |
Plan Coordinator | Original | / | 2/17/2010 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 445849 |
Plumbing | Original | N | 2/17/2010 | TCRIPPEN | TCRIPPEN | NO PLUMBING WORK | | Plumbing | 445848 |
Plumbing | Original | / | 2/17/2010 | MINDY | MINDY | Plan Reviewer = TCRIPPEN by MINDY | | Plumbing | 445836 |
Plumbing | Original | / | 2/17/2010 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 445824 |
Plan Coordinator | Original | / | 2/17/2010 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 445818 |
Mechanical | Original | D | 2/17/2010 | RUSSELL | RUSSELL | All references to 2006 need to be changed to 2003, need to schedule existing air handler unit serving this area to provide what the O.A. % is to verify O.A. adequate to all spaces per '03 IMC Table 403.3 or per '05 RBC amendments, are CRAH -1 -3 provided with only CWS and CWR, or are they provided with refrigerant ? if refrigerant provided, provide type and amount for compliance with '03 IMC table 1103.1, unable to complete review until O.A. % provided | | Mechanical | 445817 |
Mechanical | Original | / | 2/17/2010 | MINDY | MINDY | Plan Reviewer = RUSSELL by MINDY | | Mechanical | 445762 |
Mechanical | Original | / | 2/17/2010 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 445749 |
Plan Coordinator | Original | / | 2/17/2010 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 445740 |
Electrical | Original | A | 2/17/2010 | SHELBY | SHELBY | | | Electrical | 445739 |
Electrical | Original | / | 2/16/2010 | MINDY | MINDY | Plan Reviewer = SHELBY by MINDY | | Electrical | 445632 |
Electrical | Original | / | 2/16/2010 | | MINDY | Location = Electrical by MINDY | | Electrical | 445620 |
Plan Coordinator | Original | / | 2/16/2010 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 445618 |
Construction | Original | D | 2/16/2010 | SHELLEY | SHELLEY | Rated partition not required - either remove rating from wall or provide listed assembly to be used. Walk ok. Reviewer note: Partition will need to be highlighted if rating remains. | | Construction | 445617 |
Construction | Original | / | 2/16/2010 | MINDY | MINDY | Plan Reviewer = SHELLEY by MINDY | | Construction | 445606 |
Construction | Original | / | 2/12/2010 | | MINDY | Location = Construction by MINDY | | Construction | 445450 |
Plan Coordinator | Original | / | 2/12/2010 | | TIMC | Location = Plan Coordinator by TIMC | | Plan Coordinator | 445446 |
Enumeration | Original | A | 2/12/2010 | TIMC | TIMC | | | Enumeration | 445445 |
Floodplain | Original | N | 2/12/2010 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 445442 |