Scanned | Original | / | 12/2/2010 | | JANE | Location = Scanned by JANE | | Scanned | 486063 |
To Be Scanned Bin | Original | / | 12/1/2010 | | MINDY | Location = To Be Scanned Bin by MINDY | | To Be Scanned Bin | 485934 |
Hazmat | Original | A | 12/1/2010 | MINDY | MINDY | 11/30/10 kay | | Hazmat | 485933 |
Finished Bin | Original | / | 12/1/2010 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 485932 |
Construction | Original | A | 11/29/2010 | JAY | JAY | Comments addressed. OK | | Construction | 485481 |
Enumeration | Original | A | 11/29/2010 | JEANNINE | JEANNINE | See site plan included. Single tenant building. | | Enumeration | 485480 |
Plumbing | Original | A | 11/23/2010 | TCRIPPEN | TCRIPPEN | | | Plumbing | 485062 |
Mechanical | Original | A | 11/17/2010 | DALEH | DALEH | | | Mechanical | 484410 |
Out to Review | Original | / | 11/17/2010 | KIM | KIM | SEAN 719-200-6510 | | Out to Review | 484407 |
Finished Bin | Original | / | 11/17/2010 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 484219 |
Hazmat | Original | D | 11/17/2010 | MINDY | MINDY | 11/16/10 kay | | Hazmat | 484218 |
Hazmat | Original | / | 11/3/2010 | | CSFIRE | Location = Hazmat by CSFIRE | csfdit | Hazmat | 482469 |
CO Springs Fire | Original | A | 11/3/2010 | CSFIRE | CSFIRE | | csfdit | CO Springs Fire | 482467 |
Fire | Original | / | 10/29/2010 | | CSZONING | Location = Fire by CSZONING | bveltman | Fire | 481795 |
CO Springs DRE | Original | A | 10/29/2010 | CSZONING | CSZONING | Convert office to reliability lab | bveltman | CO Springs DRE | 481794 |
Zoning/Planning | Original | / | 10/26/2010 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 481228 |
Plan Coordinator | Original | / | 10/26/2010 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 481225 |
Electrical | Original | A | 10/26/2010 | SHELBY | SHELBY | | | Electrical | 481224 |
Electrical | Original | / | 10/25/2010 | MINDY | MINDY | Plan Reviewer = SHELBY by MINDY | | Electrical | 481044 |
Electrical | Original | / | 10/22/2010 | | MINDY | Location = Electrical by MINDY | | Electrical | 480743 |
Plan Coordinator | Original | / | 10/22/2010 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 480738 |
Plumbing | Original | D | 10/22/2010 | TCRIPPEN | TCRIPPEN | floor drain required for back flow device , provide labeling for non potable water | | Plumbing | 480737 |
Plumbing | Original | / | 10/22/2010 | MINDY | MINDY | Plan Reviewer = TCRIPPEN by MINDY | | Plumbing | 480718 |
Plumbing | Original | / | 10/21/2010 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 480629 |
Plan Coordinator | Original | / | 10/21/2010 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 480618 |
Mechanical | Original | D | 10/21/2010 | RUSSELL | RUSSELL | NITROGEN CLOSET, exhaust air , how providing makeup air into space, verify with fire/hazmat reqmts, occupant load for laboratories and o.a. reqmts. and makeup air for EF-9 (2600 cfm exhaust) | | Mechanical | 480617 |
Mechanical | Original | / | 10/21/2010 | MINDY | MINDY | Plan Reviewer = RUSSELL by MINDY | | Mechanical | 480463 |
Mechanical | Original | / | 10/21/2010 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 480433 |
Plan Coordinator | Original | / | 10/20/2010 | | JAY | Location = Plan Coordinator by JAY | | Plan Coordinator | 480432 |
Construction | Original | D | 10/20/2010 | JAY | JAY | Provide ICC / UL Assembly for construction of rated wall "1HR1A3A". Revise code study to clarify callout of "No Mixed Occupancies" while area tabulation includes A-2, A-3, B, and S-1. See plans for any additional comments. WALK OK | | Construction | 480429 |
Construction | Original | / | 10/20/2010 | MINDY | MINDY | Plan Reviewer = JAY by MINDY | | Construction | 480300 |
Construction | Original | / | 10/18/2010 | | MINDY | Location = Construction by MINDY | | Construction | 479981 |
Plan Coordinator | Original | / | 10/18/2010 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 479980 |
Enumeration | Original | D | 10/18/2010 | JEANNINE | JEANNINE | REQUIRES SITE MAP OF AREA HP BUILDINGS W/ADDRESSES LABELED | | Enumeration | 479979 |
Floodplain | Original | N | 10/18/2010 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 479952 |