Out to Review | Original | / | 11/19/2010 | SHELBY | SHELBY | Tom 471 2708 | | Out to Review | 484767 |
Electrical | Original | A | 11/19/2010 | SHELBY | SHELBY | | | Electrical | 484766 |
Plumbing | Original | A | 11/19/2010 | TCRIPPEN | TCRIPPEN | | | Plumbing | 484755 |
Construction | Original | A | 11/19/2010 | JAY | JAY | OK | | Construction | 484723 |
Waste Water Div | Original | A | 11/16/2010 | CSUREVIEW | CSUREVIEW | | mtroche | Waste Water Div | 484176 |
Mechanical | Original | N | 11/16/2010 | RUSSELL | RUSSELL | | | Mechanical | 484041 |
Out to Review | Original | / | 11/16/2010 | NELIDA | NELIDA | jTom 972-358-8595 | | Out to Review | 484020 |
Finished Bin | Original | / | 11/15/2010 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 483848 |
Health Dept. | Original | A | 11/10/2010 | HEALTHDEPT | HEALTHDEPT | Plans are approved. A KW rating of at least 6 or a recovery rate of 24 GPH @ 100 F rise. | mayescr | Health Dept. | 483525 |
Health Dept. | Original | / | 11/10/2010 | | MINDY | Location = Health Dept. by MINDY | | Health Dept. | 483313 |
Waste Water Div | Original | D | 11/10/2010 | CSUREVIEW | CSUREVIEW | Attached copy of the variance to have a minimum 150 pound / 50 GPM grease trap instead of an external grease interceptor, and connect the hand wash sink to the grease trap, too, as per variance dated on November 08, 2010. | mtroche | Waste Water Div | 483246 |
Water Division | Original | A | 11/10/2010 | CSUREVIEW | CSUREVIEW | | mtroche | Water Division | 483243 |
Hazmat | Original | N | 11/8/2010 | CSFIRE | CSFIRE | | csfirehp | Hazmat | 482922 |
Fire | Original | A | 11/8/2010 | CSFIRE | CSFIRE | Forwarded to CSU. 11/8/10 SDS | csfirehp | Fire | 482921 |
Fire | Original | / | 11/5/2010 | | CSZONING | Location = Fire by CSZONING | bveltman | Fire | 482770 |
Out to Review | Original | / | 11/5/2010 | | CSZONING | Location = Out to Review by CSZONING | bveltman | Out to Review | 482768 |
Zoning/Planning | Original | / | 11/5/2010 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 482735 |
Plan Coordinator | Original | / | 11/5/2010 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 482734 |
Mechanical | Original | D | 11/5/2010 | RUSSELL | RUSSELL | Provide a mechanical page showing how mechanical ventilation met (O.A.) for this tenant remodel | | Mechanical | 482733 |
Mechanical | Original | / | 11/5/2010 | MINDY | MINDY | Plan Reviewer = RUSSELL by MINDY | | Mechanical | 482730 |
CO Springs DRE | Original | A | 11/5/2010 | CSZONING | CSZONING | Baskin Robbins Kiosk | bveltman | CO Springs DRE | 482767 |
Mechanical | Original | / | 11/4/2010 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 482491 |
Plan Coordinator | Original | / | 11/4/2010 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 482490 |
Electrical | Original | D | 11/4/2010 | SHELBY | SHELBY | 1. Provide lighting plan. 2. Provide IECC calculation.(2003) 3. Label all Electrical Equipment with panel and circuit number. 4. Provide complete one line. 5. Provide Light Fixture Schedule. 6. Show all equipment shown on wiring diagram on floor plan. 7. Complete re review. | | Electrical | 482489 |
Electrical | Original | / | 11/3/2010 | MINDY | MINDY | Plan Reviewer = SHELBY by MINDY | | Electrical | 482485 |
Electrical | Original | / | 11/3/2010 | | JANE | Location = Electrical by JANE | | Electrical | 482413 |
Plan Coordinator | Original | / | 11/3/2010 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 482402 |
Plumbing | Original | D | 11/3/2010 | TCRIPPEN | TCRIPPEN | need variance letter from waste water for inside grease interceptor all drain lines need to go to the interceptor need water pipe size analysis on plans provide cut sheets for interceptor need waste water and health approvals water heater will need drain pan and drain | | Plumbing | 482401 |
Plumbing | Original | / | 11/3/2010 | MINDY | MINDY | Plan Reviewer = TCRIPPEN by MINDY | | Plumbing | 482361 |
Plumbing | Original | / | 11/3/2010 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 482333 |
Plan Coordinator | Original | / | 11/3/2010 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 482325 |
Floodplain | Original | N | 11/3/2010 | JEANNINE | JEANNINE | | | Floodplain | 482322 |
Floodplain | Original | / | 11/3/2010 | | JEANNINE | Location = Floodplain by JEANNINE | | Floodplain | 482321 |
Enumeration | Original | A | 11/3/2010 | JEANNINE | JEANNINE | | | Enumeration | 482320 |
Enumeration | Original | / | 11/3/2010 | | JAY | Location = Enumeration by JAY | | Enumeration | 482286 |
Construction | Original | D | 11/3/2010 | JAY | JAY | Per previous conversation with Tom Loscheider, this is to be a pre-fabricated kiosk unit, however that is not stated on the plans. Please provide General Note stating this is a pre-fabricated unit . . OR . . Provide door schedule, construction details for walls and floor, etc. WALK OK | | Construction | 482285 |
Construction | Original | / | 11/3/2010 | JAY | JAY | Plan Reviewer = JAY by JAY | | Construction | 482284 |
Construction | Original | / | 11/3/2010 | | JAY | Location = Construction by JAY | | Construction | 482283 |
Plumbing | Original | / | 11/2/2010 | KIM | KIM | Overtime approved for Plumbing by JOHN CHOI | | Plumbing | 482233 |
Mechanical | Original | / | 11/2/2010 | KIM | KIM | Overtime approved for Mechanical by JOHN CHOI | | Mechanical | 482232 |
Electrical | Original | / | 11/2/2010 | KIM | KIM | Overtime approved for Electrical by JOHN CHOI | | Electrical | 482231 |
Construction | Original | / | 11/2/2010 | KIM | KIM | Overtime approved for Construction by JOHN CHOI | | Construction | 482230 |