Out to Review | Original | / | 4/27/2011 | | JAN | Location = Out to Review by JAN Bobby Hill | | Out to Review | 504542 |
Finished Bin | Original | / | 4/26/2011 | | JANE | Location = Finished Bin by JANE | | Finished Bin | 504254 |
Health Dept. | Original | D | 4/26/2011 | JANE | JANE | | | Health Dept. | 504253 |
Health Dept. | Original | / | 4/21/2011 | | JANE | Location = Health Dept. by JANE | | Health Dept. | 503762 |
Water Division | Original | N | 4/21/2011 | JANE | JANE | | | Water Division | 503761 |
Waste Water Div | Original | N | 4/21/2011 | JANE | JANE | | | Waste Water Div | 503760 |
Waste Water Div | Original | A | 4/21/2011 | JANE | JANE | | | Waste Water Div | 503758 |
Scanned/Finished Bin | Original | / | 4/21/2011 | | JANE | Location = Scanned/Finished Bin by JANE | | Scanned/Finished Bin | 503757 |
CO Springs DRE | Original | A | 4/21/2011 | JANE | JANE | dmt | | CO Springs DRE | 503756 |
Hazmat | Original | D | 4/19/2011 | CSFIRE | CSFIRE | | csfdit | Hazmat | 503166 |
CO Springs Fire | Original | D | 4/19/2011 | CSFIRE | CSFIRE | | csfdit | CO Springs Fire | 503165 |
Zoning/Planning | Original | / | 4/11/2011 | | JANE | Location = Zoning/Planning by JANE | | Zoning/Planning | 502086 |
Plan Coordinator | Original | / | 4/11/2011 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 502076 |
Plumbing | Original | D | 4/11/2011 | TCRIPPEN | TCRIPPEN | provide plumbing pages | | Plumbing | 502075 |
Plumbing | Original | / | 4/11/2011 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 502023 |
Plumbing | Original | / | 4/11/2011 | | JANE | Location = Plumbing by JANE | | Plumbing | 501927 |
Plan Coordinator | Original | / | 4/11/2011 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 501923 |
Electrical | Original | D | 4/11/2011 | SHELBY | SHELBY | 1. Show feeder size for panel R-4. 2. Feeder for RTU 2 incorrect(250.122(g)). 3. Comply 240.21(B)(4) NEC for tap conductors. 4. Provide SCCR and SCA for all new panels. 5. Provide elevator pit detail. 6. Provide 2003 IECC the 2009 has not been adopted. 7. Comply 310.15(B)(2)(c) NEC. | | Electrical | 501922 |
Electrical | Original | / | 4/8/2011 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 501796 |
Electrical | Original | / | 4/8/2011 | | JANE | Location = Electrical by JANE | | Electrical | 501776 |
Plan Coordinator | Original | / | 4/8/2011 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 501762 |
Mechanical | Original | D | 4/8/2011 | RUSSELL | RUSSELL | See shaft note on sheet M1.01 and duct opening size and sealing duct with approved material, F/S/ dampers to be installed at flr/clg assembly, S.A. diffusers don't match MAU-1 schedule, verify discharge height above grade for KEF-2, coordinate exhaust duct sizes since same exhaust cfms, but different duct sizes on sheet M1.01, but the same size on sheet M1.02, change elevator alignment with architectural sheets on all levels, coordinate exhaust outlets on each floor level and total exhaust vfms,shaft indicated on sheet M1.02 not required since duct is serving one level, which also eliminates the F/S damper, coordinate duct locations as indicated on this sheet, same on sheet M1.03, verify duct alignment below,verify indoor PRV's have limited orifices or are they vented to the exterior ?, gas piping to existing RTU-1 ?, gas loads don't match on M2.02,on sheet M3.01, put all the captive-aire hood details on this sheet, see sheet M3.01 for detailed information | | Mechanical | 501761 |
Mechanical | Original | / | 4/7/2011 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 501599 |
Mechanical | Original | / | 4/7/2011 | | JANE | Location = Mechanical by JANE | | Mechanical | 501598 |
Electrical | Original | / | 4/5/2011 | | JANE | Location = Electrical by JANE | | Electrical | 501177 |
Plan Coordinator | Original | / | 4/5/2011 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 501160 |
Construction | Original | D | 4/5/2011 | SHELLEY | SHELLEY | Several issues with ratings, wall types, UL listings. Architectural and structural don't match. Too much to list individually. See plans for all comments. No walk. | | Construction | 501158 |
Construction | Original | / | 4/4/2011 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 501003 |
Construction | Original | / | 4/1/2011 | | JANE | Location = Construction by JANE | | Construction | 500607 |
Plan Coordinator | Original | / | 4/1/2011 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 500595 |
Enumeration | Original | D | 4/1/2011 | JEANNINE | JEANNINE | Site plan required showing building footprint, tax ID number, and legal description. What floors are involved & how many tenants. | | Enumeration | 500593 |
Floodplain | Original | N | 3/31/2011 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 500528 |