Out to Review | Original | / | 8/26/2011 | | CSZONING | Location = Out to Review by CSZONING | Dtortorice | Out to Review | 523524 |
Out to Review | Original | / | 8/26/2011 | | CSZONING | Location = Out to Review by CSZONING | Dtortorice | Out to Review | 523523 |
CO Springs DRE | Original | A | 8/26/2011 | CSZONING | CSZONING | Interior Remodel to existing McDonalds Restaurant. Per EKM no amendment is needed, ok to permit. North arrow reoriented. | Dtortorice | CO Springs DRE | 523522 |
Electrical | Original | A | 8/23/2011 | SHELBY | SHELBY | Craig 499 0571 | | Electrical | 522772 |
Health Dept. | Original | N | 8/19/2011 | HEALTHDEPT | HEALTHDEPT | No plan review is required. Only rotating the self-service line 90 degrees and making restrooms more handicap accessible. NM 8/19/2011 | mayescr | Health Dept. | 522300 |
Plumbing | Original | A | 8/16/2011 | RUSSELL | RUSSELL | | | Plumbing | 521719 |
Mechanical | Original | A | 8/10/2011 | DALEH | DALEH | | | Mechanical | 520757 |
Out to Review | Original | / | 8/10/2011 | MINDY | MINDY | Curt 499 0571 | | Out to Review | 520693 |
Finished Bin | Original | / | 8/9/2011 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 520344 |
Water Division | Original | N | 8/9/2011 | CSUREVIEW | CSUREVIEW | | mtroche | Water Division | 520293 |
Waste Water Div | Original | N | 8/9/2011 | CSUREVIEW | CSUREVIEW | | mtroche | Waste Water Div | 520292 |
Hazmat | Original | N | 8/8/2011 | CSFIRE | CSFIRE | | csfdit | Hazmat | 520078 |
CO Springs Fire | Original | N | 8/8/2011 | CSFIRE | CSFIRE | no fire final | csfdit | CO Springs Fire | 520077 |
Fire | Original | / | 8/4/2011 | | CSZONING | Location = Fire by CSZONING | bveltman | Fire | 519666 |
Fire | Original | / | 8/4/2011 | | CSZONING | Location = Fire by CSZONING | bveltman | Fire | 519665 |
Fire | Original | / | 8/4/2011 | | CSZONING | Location = Fire by CSZONING | bveltman | Fire | 519663 |
CO Springs DRE | Original | D | 8/4/2011 | CSZONING | CSZONING | Provide a City Planning stamped approved amendment to development plan no. AR DP 06-904 to be included with the construction set showing the exterior modifications to the site. A pre-application meeting request form has been included with set. This should be faxed to 385-5167 for a planner to contact you to discuss update to plan. North Arrow on plans provided appears to be incorrectly oriented. | bveltman | CO Springs DRE | 519662 |
Zoning/Planning | Original | / | 7/29/2011 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 518932 |
Plan Coordinator | Original | / | 7/29/2011 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 518859 |
Electrical | Original | D | 7/29/2011 | SHELBY | SHELBY | 1. For panel schedule note sheet E-1.0 verify existing panel connections and loads prior to review. 2. label all new and relocated electrical equipment/devices with panel and circuit designation. 3. Provide IECC calculation. | | Electrical | 518858 |
Electrical | Original | / | 7/29/2011 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 518847 |
Electrical | Original | / | 7/28/2011 | | MINDY | Location = Electrical by MINDY | | Electrical | 518488 |
Plan Coordinator | Original | / | 7/28/2011 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 518483 |
Plumbing | Original | D | 7/28/2011 | TCRIPPEN | TCRIPPEN | need to schedule new grease interceptor and show location on plans | | Plumbing | 518482 |
Plumbing | Original | / | 7/28/2011 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 518461 |
Plumbing | Original | / | 7/28/2011 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 518457 |
Plan Coordinator | Original | / | 7/28/2011 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 518452 |
Mechanical | Original | D | 7/28/2011 | RUSSELL | RUSSELL | Exhaust cfms in Mens toilet room is inadequate, needs to be a minimum of 225 cfm exhaust, 75 cfm for each toilet fixture, how providing makeup air into toilet rooms, door undercut or transfer grilles in door ? balance system to supply cfms indicated on plan | | Mechanical | 518450 |
Mechanical | Original | / | 7/27/2011 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 518361 |
Construction | Original | A | 7/19/2011 | JAY | JAY | OK | | Construction | 516642 |
Mechanical | Original | / | 7/19/2011 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 516640 |
Construction | Original | A | 7/19/2011 | MINDY | MINDY | 07/19/11 aje | | Construction | 516639 |
Construction | Original | / | 7/19/2011 | JAY | JAY | In Current Review by JAY | | Construction | 516614 |
Construction | Original | / | 7/15/2011 | | MINDY | Location = Construction by MINDY | | Construction | 516271 |
Plan Coordinator | Original | / | 7/15/2011 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 516268 |
Enumeration | Original | A | 7/15/2011 | AMY | AMY | | | Enumeration | 516267 |
Floodplain | Original | N | 7/15/2011 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 516118 |