Mechanical | Original | A | 1/24/2012 | DALEH | DALEH | | | Mechanical | 545471 |
Enumeration | Original | A | 1/24/2012 | AMY | AMY | Secondary addresses to be removed prior to Final Inspection: suite 150- second from the north end & 700- third from the north end of the buildings. Agreement with YOW Architects & Liz Seeger Property Manager. | | Enumeration | 545458 |
Out to Review | Original | / | 1/24/2012 | KIM | KIM | JERRY 475-8123 | | Out to Review | 545306 |
Enumeration | Original | D | 1/23/2012 | AMY | AMY | Contact this office please- Amy 327-2930 or amy@pprbd.org | | Enumeration | 545252 |
Finished Bin | Original | / | 1/23/2012 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 545128 |
Plan Coordinator | Original | / | 1/20/2012 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 545127 |
Mechanical | Original | D | 1/20/2012 | RUSSELL | RUSSELL | Large training room/conference room is short O.A. based on % of O.A. shown in RTU schedule, Per key note P1, it appears new gas piping is medium pressure, is so, field label all medium pressure gas piping every 6 feet, support gas piping as required per code, verify gas pressure regulators are installed as indicated at all appliances as required. | | Mechanical | 545126 |
Mechanical | Original | / | 1/20/2012 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 545111 |
Resubmittal 1 | Original | / | 1/18/2012 | NELIDA | NELIDA | Resubmittal #1 1/18/12 | | Resubmittal 1 | 544654 |
Mechanical | Original | / | 1/18/2012 | | NELIDA | Location = Mechanical by NELIDA | | Mechanical | 544652 |
Plumbing | Original | A | 1/18/2012 | TCRIPPEN | TCRIPPEN | | | Plumbing | 544649 |
CO Springs Fire | Original | A | 1/18/2012 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 544558 |
Enumeration | Original | A | 1/18/2012 | AMY | AMY | There is not more then one floor in this building, permit history for 600 & 700 were done in error. Per site check by DRL 1-23-12, Suite numbering was not done prior by this office. This office will assign the the secondary suite numbers in the future. | | Enumeration | 544450 |
Plumbing | Original | D | 1/17/2012 | TCRIPPEN | TCRIPPEN | still need water pipe size analysis data on plans | | Plumbing | 544390 |
Construction | Original | A | 1/17/2012 | SHELLEY | SHELLEY | | | Construction | 544382 |
Electrical | Original | A | 1/17/2012 | SHELBY | SHELBY | JW 475 8133 | | Electrical | 544371 |
Out to Review | Original | / | 1/9/2012 | BPHILLIPS | BPHILLIPS | Stacie Gray 520-1234 | | Out to Review | 543098 |
Finished Bin | Original | / | 1/6/2012 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 542818 |
CO Springs DRE | Original | N | 1/6/2012 | MINDY | MINDY | | | CO Springs DRE | 542817 |
Hazmat | Original | N | 1/4/2012 | CSFIRE | CSFIRE | | csfdit | Hazmat | 542627 |
CO Springs Fire | Original | D | 1/4/2012 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 542626 |
Zoning/Planning | Original | / | 12/30/2011 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 542265 |
Plan Coordinator | Original | / | 12/30/2011 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 542262 |
Electrical | Original | D | 12/30/2011 | SHELBY | SHELBY | 1. Provide complete one line. 2. Clearly indicate change in load. | | Electrical | 542260 |
Electrical | Original | / | 12/30/2011 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 542245 |
Mechanical | Original | D | 12/30/2011 | RUSSELL | RUSSELL | See plans for comments | | Mechanical | 542194 |
Electrical | Original | / | 12/30/2011 | | MINDY | Location = Electrical by MINDY | | Electrical | 542188 |
Mechanical | Original | / | 12/30/2011 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 542176 |
Plan Coordinator | Original | / | 12/30/2011 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 542175 |
Plumbing | Original | D | 12/30/2011 | TCRIPPEN | TCRIPPEN | gas piping to be on M pages or G pages schedule all fixtures and materials with manufacture and model numbers provide water pipe size analysis data on plans | | Plumbing | 542174 |
Plumbing | Original | / | 12/30/2011 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 542171 |
Plumbing | Original | / | 12/30/2011 | | RUSSELL | Location = Plumbing by RUSSELL | | Plumbing | 542170 |
Mechanical | Original | / | 12/29/2011 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 542080 |
Mechanical | Original | / | 12/29/2011 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 542028 |
Plan Coordinator | Original | / | 12/29/2011 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 542022 |
Construction | Original | D | 12/29/2011 | MICHAELA | MICHAELA | Clarify wall partition types for fire-resistance rating - provide listed assemblies if required Clarify separated/non-separated use on code study form Code study form requires a seal Walk-through OK | | Construction | 542021 |
Construction | Original | / | 12/29/2011 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 542004 |
Construction | Original | / | 12/29/2011 | | MINDY | Location = Construction by MINDY | | Construction | 541987 |
Plan Coordinator | Original | / | 12/29/2011 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 541986 |
Enumeration | Original | D | 12/29/2011 | AMY | AMY | Require: Floor plans showing all floors of this building with suite numbers labeled, showing separation of space.If suite numbering has not be done by this office in some areas leave blank. This office will assign the suite numbering to this building. Please submitted floor plans asap. | | Enumeration | 541985 |
Floodplain | Original | N | 12/28/2011 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 541954 |