Finished Bin | Original | / | 2/22/2012 | | NELIDA | Location = Finished Bin by NELIDA | | Finished Bin | 550040 |
To Be Scanned Bin | Original | / | 2/22/2012 | | NELIDA | Location = To Be Scanned Bin by NELIDA | | To Be Scanned Bin | 549943 |
Mechanical | Original | A | 2/21/2012 | DALEH | DALEH | | | Mechanical | 549719 |
Out to Review | Original | / | 2/21/2012 | NELIDA | NELIDA | Jack Paulson 475-1727 | | Out to Review | 549716 |
Finished Bin | Original | / | 2/16/2012 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 549256 |
Plan Coordinator | Original | / | 2/16/2012 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 549252 |
Mechanical | Original | D | 2/16/2012 | RUSSELL | RUSSELL | Still need to move wall off ductwork that is going up in a shaft. Wall needs to slide back to allow wall up to underside of deck above without interference from wall. | | Mechanical | 549250 |
Mechanical | Original | / | 2/16/2012 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 549240 |
Mechanical | Original | / | 2/16/2012 | | NELIDA | Location = Mechanical by NELIDA | | Mechanical | 549115 |
Resubmittal 1 | Original | / | 2/16/2012 | NELIDA | NELIDA | Resubmittal #1 2/16/12 | | Resubmittal 1 | 549114 |
Out to Review | Original | / | 2/16/2012 | JAY | JAY | Erin walking: | | Out to Review | 549102 |
Construction | Original | A | 2/16/2012 | JAY | JAY | resubmittal: OK | | Construction | 549099 |
CO Springs Fire | Original | A | 2/7/2012 | CSFIRE | CSFIRE | Submitted By: Embres, Rhonda C
contractor picking up at Fire 2/2/12 (see full review) | csfdit | CO Springs Fire | 547508 |
Fire | Original | / | 2/2/2012 | | MINDY | Location = Fire by MINDY | | Fire | 546876 |
Plan Coordinator | Original | / | 2/1/2012 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 546872 |
Mechanical | Original | D | 2/1/2012 | RUSSELL | RUSSELL | Sheet M0.1, make reference to correct Codes, currently schools are on the 2006 "I" Codes,sheet M0.2, verify ventilation rates per the 2006 IMC Table 403.3 and the correct version and year of ASHRAE, it would appear that the ventilation rate per the 2006 IMC could be less,sheet M1.1, Storage Rm 131, verify location of wall since it needs to go to deck to resist the passage of smoke, coordinate with the Architect the wall location with transfer duct and ducts up, building contractor and mechanical contractor to coordinate the sealing of shaft openings and providing access to dampers located in the floor space above, sheet M1.2, verify if ventilation is required in Storage Rm 115, all other storage rooms are provided with ventilation, verify adequate amount of S.A./O.A. is being provided in Storage Rm 101, | | Mechanical | 546871 |
Mechanical | Original | / | 2/1/2012 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 546811 |
Mechanical | Original | / | 1/24/2012 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 545387 |
Plan Coordinator | Original | / | 1/24/2012 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 545380 |
Construction | Original | D | 1/24/2012 | SHELLEY | SHELLEY | Revise code cycle; gym is not considered separate occupancy per 508.3.1; Ansi requirements not met in change rooms; exit sign locations added; no design match for UL number on 2 hour barrier; see plans; walk ok. | | Construction | 545379 |
Construction | Original | / | 1/24/2012 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 545331 |
Construction | Original | / | 1/24/2012 | | KIM | Location = Construction by KIM | | Construction | 545320 |
Floodplain | Original | N | 1/24/2012 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 545308 |
Floodplain | Original | N | 1/24/2012 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 545307 |