CO Springs Fire | Splice 8/14/12 | A | 8/20/2012 | CSFIRE | CSFIRE | | dwithee | CO Springs Fire | 581344 |
Mechanical | Splice 8/14/12 | A | 8/17/2012 | DALEH | DALEH | | | Mechanical | 581063 |
Resubmittal 2 | Splice 8/14/12 | / | 8/17/2012 | MINDY | MINDY | Resubmittal #2 | | Resubmittal 2 | 581047 |
Construction | Splice 8/14/12 | A | 8/16/2012 | SHELLEY | SHELLEY | added locker rooms and work rooms | | Construction | 580799 |
Plumbing | Splice 8/14/12 | A | 8/16/2012 | TCRIPPEN | TCRIPPEN | new splice adding bath room | | Plumbing | 580796 |
Mechanical | Splice 8/14/12 | D | 8/16/2012 | DALEH | DALEH | see green lines | | Mechanical | 580793 |
Electrical | Splice 8/14/12 | A | 8/16/2012 | SHELBY | SHELBY | | | Electrical | 580771 |
Out to Review | Splice 8/14/12 | / | 8/16/2012 | MINDY | MINDY | walking | | Out to Review | 580752 |
Resubmittal 1 | Splice 8/14/12 | / | 8/16/2012 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 580751 |
Plumbing | Splice 8/14/12 | D | 8/14/2012 | TCRIPPEN | TCRIPPEN | need full size sheets | | Plumbing | 580385 |
Electrical | Splice 8/14/12 | D | 8/14/2012 | SHELBY | SHELBY | 1. Submit changes on full size complete sheets. 2. Provide panel schedules | | Electrical | 580376 |
Mechanical | Splice 8/14/12 | D | 8/14/2012 | DALEH | DALEH | show chws/r piping and tie ins | | Mechanical | 580372 |
Construction | Splice 8/14/12 | D | 8/14/2012 | SHELLEY | SHELLEY | provide revised door schedule and revised code study form for expanded scope of work. | | Construction | 580364 |
Scanned/Finished Bin | Original | / | 2/21/2012 | | SHARON | Location = Scanned/Finished Bin by SHARON | | Scanned/Finished Bin | 549801 |
To Be Scanned Bin | Original | / | 2/21/2012 | | MINDY | Location = To Be Scanned Bin by MINDY | | To Be Scanned Bin | 549779 |
Mechanical | Original | A | 2/21/2012 | RUSSELL | RUSSELL | | | Mechanical | 549778 |
Construction | Original | A | 2/21/2012 | JAY | JAY | resubmittal; OK | | Construction | 549767 |
Electrical | Original | A | 2/21/2012 | SHELBY | SHELBY | | | Electrical | 549756 |
Plumbing | Original | A | 2/21/2012 | TCRIPPEN | TCRIPPEN | | | Plumbing | 549750 |
Out to Review | Original | / | 2/21/2012 | BPHILLIPS | BPHILLIPS | Paul Reu 867-7038 | | Out to Review | 549589 |
CO Springs DRE | Original | N | 2/21/2012 | BPHILLIPS | BPHILLIPS | dmt 2/8/12 | | CO Springs DRE | 549588 |
Hazmat | Original | A | 2/17/2012 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 549539 |
CO Springs Fire | Original | A | 2/9/2012 | CSFIRE | CSFIRE | Submitted By: Embres, Rhonda C
routed to hazmat (see full review) | csfdit | CO Springs Fire | 548015 |
Zoning/Planning | Original | / | 2/3/2012 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 547263 |
Plan Coordinator | Original | / | 2/3/2012 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 547261 |
Mechanical | Original | D | 2/3/2012 | RUSSELL | RUSSELL | Main duct serves not only the corridor, but adjacent rooms, ie: clean supply OR's, soiled, pump room, but not showing dampers on walls, but on ceiling diffuser and grille ?, don't walls go to deck ? as indicated on other green hi-lited walls ?, purple hi-lited walls are smoke partitions, where ducts penetrate smoke partition, need to resist the passage of smoke by providing a smoke damper unless part of the smoke control system, are you missing a duct connection where indicated ? move damper into wall on sheet M120, see note 4 on sheet M121, Cu-1 and Cu-2 on roof are over 300 #'s but aren't indicated on the structural sheet S102, either indicate on the structural sheet that they've been accounted for or provide a structural letter to verify the structure is adequate to support the additional 800#'s on sheet M230, CRAC units scheduled on sheet M700 missing what the amount and type of refrigerant serving these units to verify compliance with 2009 IMC Table 1103.1, also see note 3. | | Mechanical | 547260 |
Mechanical | Original | / | 2/3/2012 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 547169 |
Mechanical | Original | / | 2/2/2012 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 547012 |
Electrical | Original | D | 2/2/2012 | SHELBY | SHELBY | 1. Provide NRTL listing for booms per 90.7, 100I, and110.3 NEC. 2. Clearly indicate Life Safety VS Critical Branch for Emergency System per 517.31 NEC. 3. Show conductor and raceway size, type, and quantity for battery conductors on one line. 4. Alternates are not allowed (note 6 on E600 etc.) 5. Label all electrical equipment/devices with panel and circuit number.(Keynote 5 sheet E 120). | | Electrical | 547002 |
Electrical | Original | / | 1/31/2012 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 546521 |
Electrical | Original | / | 1/31/2012 | | MINDY | Location = Electrical by MINDY | | Electrical | 546486 |
Plan Coordinator | Original | / | 1/31/2012 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 546480 |
Plumbing | Original | D | 1/31/2012 | TCRIPPEN | TCRIPPEN | provide square footage at each drain and each roof drain | | Plumbing | 546479 |
Plumbing | Original | / | 1/31/2012 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 546443 |
Plumbing | Original | / | 1/30/2012 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 546417 |
Plan Coordinator | Original | / | 1/30/2012 | | JAY | Location = Plan Coordinator by JAY | | Plan Coordinator | 546414 |
Construction | Original | D | 1/30/2012 | JAY | JAY | Clarify rated wall between electrical rooms 200A and 200B with non-rated door (200B). See sheets A112 and A600. WALK OK | | Construction | 546413 |
Construction | Original | / | 1/30/2012 | JAY | JAY | In Current Review by JAY | | Construction | 546359 |
Construction | Original | / | 1/30/2012 | | MINDY | Location = Construction by MINDY | | Construction | 546352 |
Enumeration | Original | A | 1/30/2012 | AMY | AMY | see site plan included. | | Enumeration | 546347 |
Out to Review | Original | / | 1/30/2012 | MINDY | MINDY | walking to enumeration | | Out to Review | 546339 |
Floodplain | Original | N | 1/30/2012 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 546337 |