Construction | 8/29/12 | A | 8/29/2012 | MICHAELA | MICHAELA | | | Construction | 583464 |
Mechanical | 7/18/12 | A | 7/19/2012 | DALEH | DALEH | | | Mechanical | 575522 |
Electrical | 7/18/12 | A | 7/18/2012 | SHELBY | SHELBY | | | Electrical | 575357 |
Plumbing | 7/18/12 | A | 7/18/2012 | TCRIPPEN | TCRIPPEN | new splice pages see clouds | | Plumbing | 575321 |
Mechanical | 7/18/12 | D | 7/18/2012 | DALEH | DALEH | all ok pending combustion air for brewing equipment | | Mechanical | 575317 |
Out to Review | 7/18/12 | / | 7/18/2012 | BPHILLIPS | BPHILLIPS | walking | | Out to Review | 575312 |
Scanned/Finished Bin | 6/5/12 | / | 6/5/2012 | | REBECCA | Location = Scanned/Finished Bin by REBECCA | | Scanned/Finished Bin | 568653 |
Construction | 6/5/12 | A | 6/5/2012 | MICHAELA | MICHAELA | | | Construction | 568612 |
Mechanical | 6/5/12 | A | 6/5/2012 | DALEH | DALEH | | | Mechanical | 568609 |
Out to Review | 6/5/12 | / | 6/5/2012 | NELIDA | NELIDA | Chris walking | | Out to Review | 568601 |
Elevators | Original | A | 5/30/2012 | ERIC | ERIC | Plans not reviewed at initial plan check. added plan check in wrong department on 5/17. corrected on 5/30 err | | Elevators | 567679 |
Construction | 5/18/12 | A | 5/18/2012 | SHELLEY | SHELLEY | revised tank catwalk | | Construction | 565936 |
Out to Review | 5/18/12 | / | 5/18/2012 | NELIDA | NELIDA | Chris walking | | Out to Review | 565933 |
Scanned/Finished Bin | Original | / | 3/19/2012 | | JANE | Location = Scanned/Finished Bin by JANE | | Scanned/Finished Bin | 554492 |
To Be Scanned Bin | Original | / | 3/19/2012 | | BPHILLIPS | Location = To Be Scanned Bin by BPHILLIPS | | To Be Scanned Bin | 554419 |
Water Division | Original | N | 3/19/2012 | CSUREVIEW | CSUREVIEW | No new service lines are proposed. plan given to customer. | awerner | Water Division | 554415 |
Waste Water Div | Original | N | 3/19/2012 | CSUREVIEW | CSUREVIEW | No new service lines are proposed. | awerner | Waste Water Div | 554414 |
CSU Utilities | Original | / | 3/16/2012 | | MINDY | Location = CSU Utilities by MINDY | | CSU Utilities | 554302 |
Hazmat | Original | A | 3/16/2012 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 554265 |
CO Springs Fire | Original | A | 3/14/2012 | CSFIRE | CSFIRE | Submitted By: Embres, Rhonda C
ROUTED TO HAZMAT (see full review) | csfdit | CO Springs Fire | 553879 |
Health Dept. | Original | A | 3/13/2012 | HEALTHDEPT | HEALTHDEPT | Plans are approved. A BTU rating of at least 716,658 or a recovery rate of 645 GPH @ 100 degree rise is required. A storage tank of at least 161 gallons is required. NM 3/13/2012 719-575-8967 | mayescr | Health Dept. | 553311 |
Plumbing | Original | A | 3/9/2012 | DALEH | DALEH | | | Plumbing | 552889 |
Plumbing | Original | D | 3/9/2012 | RUSSELL | RUSSELL | Missing 2 and 3 comp. sink scheduling on architectural | | Plumbing | 552865 |
Mechanical | Original | A | 3/9/2012 | RUSSELL | RUSSELL | | | Mechanical | 552864 |
Construction | Original | A | 3/9/2012 | SHELLEY | SHELLEY | | | Construction | 552804 |
Out to Review | Original | / | 3/8/2012 | | CSZONING | Location = Out to Review by CSZONING | Dtortorice | Out to Review | 552688 |
Out to Review | Original | / | 3/8/2012 | | CSZONING | Location = Out to Review by CSZONING | Dtortorice | Out to Review | 552687 |
Fire | Original | / | 3/8/2012 | | CSZONING | Location = Fire by CSZONING | Dtortorice | Fire | 552629 |
Fire | Original | / | 3/8/2012 | | CSZONING | Location = Fire by CSZONING | Dtortorice | Fire | 552628 |
Fire | Original | / | 3/8/2012 | | CSZONING | Location = Fire by CSZONING | Dtortorice | Fire | 552627 |
CO Springs DRE | Original | A | 3/8/2012 | CSZONING | CSZONING | Interior finish for COLORADO MOUNTAIN BREWERY. Per AR DP 08-61-A2MN12. (see full review) | Dtortorice | CO Springs DRE | 552626 |
Zoning/Planning | Original | / | 3/6/2012 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 552131 |
Plan Coordinator | Original | / | 3/6/2012 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 552127 |
Plumbing | Original | D | 3/6/2012 | TCRIPPEN | TCRIPPEN | missing key note 16 on P-3 need to schedule kitchen fixtures not all are scheduled on A-pages provide cut sheets for bath room sinks | | Plumbing | 552126 |
Plumbing | Original | / | 3/6/2012 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 552108 |
Plumbing | Original | / | 3/5/2012 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 552070 |
Plan Coordinator | Original | / | 3/5/2012 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 552055 |
Mechanical | Original | D | 3/5/2012 | RUSSELL | RUSSELL | Sheet M-1 note for pizza oven, note 7, doesn't match up with the note reference on sheet M-2, note 4, sheet M-3, needs to make reference that all the RTU's required to be interlocked with the KEF's, they cannot be referenced to run during occupied hours, structural sheet S2A is missing the condenser CU-1 and MAU-1 is located in a different location that what's shown on M-2, also RTU's shown on S2A aren't rotated the same as what's shown on M-2 ? sheet A-2.2 indicates the pizza oven as gas-fired, but per engineer, it's wood/solid fuel | | Mechanical | 552054 |
Mechanical | Original | / | 3/2/2012 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 551831 |
Mechanical | Original | / | 3/2/2012 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 551619 |
Plan Coordinator | Original | / | 3/2/2012 | | JAY | Location = Plan Coordinator by JAY | | Plan Coordinator | 551611 |
Construction | Original | D | 3/2/2012 | JAY | JAY | Provide architectural stamp/signature on all "A" sheets. Verify changes made to structural sheets (addition of sheets S2A and S3A for roof framing and roof details. Structural General Notes to reference ASCE 7-05 (not ASCE 7-02). See plans for any additional comments. WALK OK | | Construction | 551607 |
Construction | Original | / | 3/2/2012 | | KIM | Location = Construction by KIM | | Construction | 551566 |
Resubmittal 1 | Original | / | 3/2/2012 | KIM | KIM | Resubmittal #1 | | Resubmittal 1 | 551565 |
Out to Review | Original | / | 2/27/2012 | MINDY | MINDY | Tom Martin | | Out to Review | 550569 |
Zoning/Planning | Original | / | 2/17/2012 | | MINDY | Location = Zoning/Planning by MINDY | | Zoning/Planning | 549475 |
Plan Coordinator | Original | / | 2/17/2012 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 549458 |
Mechanical | Original | D | 2/17/2012 | RUSSELL | RUSSELL | Need additional information provided on drawings indicates sizes of ducts, etc., that are going up or down or when changing from round to square, need sizes shown, mitigate, to make less severe ?? need to protect any and all ducts from damage, provide notation of drawing as to how you are doing so, gas pressure regulators, are they vented to the exterior or are they provided with limiting orifices ?, outdoor buried gas piping to be sleeved with open ended sleeve to terminate above grade on both ends per 2009 IFGC, cannot locate remote condensers on roof for walk-in coolers and freezer as indicated on the architectural sheet, single condenser shown would appear to be used for the 3 Ac units, please indicate which appliance is the water heater and coordinate with the plumbing sheet,all duct work exposed shall either be insulated with minimum R-8 and jacketed or internally lined with minimum R-8, please indicate which, size all gas piping down stream of the regulators on sheet M-2, verify structural has been notified of the weights for the RTU's, MAU and condensing unit, RBD requires structure to be verified with any new added weights over 300#'s on any piece of equipment, verify all RTU's are provided with an economizer per 2009 IECC Table 503.3.1(1),.total O.A. is 10,105 total exhaust is 11,210, how providing makeup air that is currently short, need cut sheets on all hoods, fans, pizza oven etc., provided on full size sheets, show discharge height on type I hood exhaust discharge, show insulation on grease duct to verify clearances to combustibles, verify mesh size, field label all medium pressure gas piping, plus more, see plans for additional comments | | Mechanical | 549456 |
Mechanical | Original | / | 2/16/2012 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 549278 |
Mechanical | Original | / | 2/15/2012 | | MINDY | Location = Mechanical by MINDY | | Mechanical | 548817 |
Plan Coordinator | Original | / | 2/15/2012 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 548797 |
Electrical | Original | A | 2/15/2012 | SHELBY | SHELBY | | | Electrical | 548796 |
Electrical | Original | / | 2/15/2012 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 548765 |
Electrical | Original | / | 2/9/2012 | | TCRIPPEN | Location = Electrical by TCRIPPEN | | Electrical | 547973 |
Plumbing | Original | D | 2/9/2012 | TCRIPPEN | TCRIPPEN | remove mechanical from P pages put on M pages , A pages do not show urinal in men`s room upper level need ANSI clearances, and calls for through concrete sink , upper and lower bars to be on grease waste , schedule all fixture and materials with manufacture and model numbers no kitchen schedule provided | | Plumbing | 547970 |
Plumbing | Original | / | 2/9/2012 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 547903 |
Plumbing | Original | / | 2/9/2012 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 547902 |
Electrical | Original | / | 2/7/2012 | | MINDY | Location = Electrical by MINDY | | Electrical | 547531 |
Plan Coordinator | Original | / | 2/7/2012 | | JAY | Location = Plan Coordinator by JAY | | Plan Coordinator | 547524 |
Construction | Original | D | 2/7/2012 | JAY | JAY | Clarify Separated / non-separated uses and adjust height and area calculations as required (see sheet A1.0). Include exterior patio in total occupant count as this may affect number of plumbing fixtures. Adjust Mezz area calculation to not include enclosed portion of floor below. Clarify if shaft construction required at locations noted or if noted exceptions apply (no exceptions as dumbwaiter shaft). Specify minimum dimensions between walls at mens restroom 108 (see sheet A-2.2). No structural details included for main bar as noted on detail 3/A-2.2. Show directional exit sign locations on reflected ceiling plans. Updated soils report required for new foundation elements. See plans for any additional comments. NO WALK. | | Construction | 547523 |
Construction | Original | / | 2/7/2012 | JAY | JAY | In Current Review by JAY | | Construction | 547433 |
Construction | Original | / | 2/6/2012 | | BPHILLIPS | Location = Construction by BPHILLIPS | | Construction | 547426 |
Floodplain | Original | N | 2/6/2012 | JEANNINE | JEANNINE | per LOMR 04-08-0314P | | Floodplain | 547425 |
Enumeration | Original | A | 2/6/2012 | JEANNINE | JEANNINE | See interior site plan on A-1.0 | | Enumeration | 547424 |
Out to Review | Original | / | 2/6/2012 | BPHILLIPS | BPHILLIPS | Larry Whittaker walking | | Out to Review | 547418 |