Required Departments: 9
|
|
|
Log Entries: 12
|
|
Scanned/Finished Bin | Original | / | 2/1/2013 | | KIM | Location = Scanned/Finished Bin by KIM | | Scanned/Finished Bin | 610461 | Hazmat | Original | N | 2/1/2013 | CSFIRE | CSFIRE | | csfdit | Hazmat | 610456 | CO Springs Fire | Original | N | 2/1/2013 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 610455 | CO Springs DRE | Original | N | 2/1/2013 | RDCUSER | RDCUSER | Interior remodel - medical to medical, cath lab retool. (see full review) | | CO Springs DRE | 610452 | Electrical | Original | A | 1/30/2013 | MATTHEW | MATTHEW | mark 473-7077 | | Electrical | 609971 | Mechanical | Original | A | 1/29/2013 | DALEH | DALEH | | | Mechanical | 609855 | Electrical | Original | D | 1/25/2013 | SHELBY | SHELBY | 1. show voltage of battery system and comply 480.5 NEC if applicable. 2. Show insulation type of battery cables. 3. Show over current protection for ups out put conductors. 4. Identify UPS as separately derived or not and modify panel UPS-DP over current protection according to NEC | | Electrical | 609251 | Construction | Original | A | 1/25/2013 | SHELLEY | SHELLEY | | | Construction | 609218 | Out to Review | Original | / | 1/25/2013 | AMY | AMY | | | Out to Review | 609216 | Enumeration | Original | A | 1/25/2013 | AMY | AMY | work is on the 3rd floor south west end of the hospital-see key plan. | | Enumeration | 609215 | Plumbing | Original | N | 1/25/2013 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit | | Plumbing | 609213 | Floodplain | Original | N | 1/25/2013 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 609209 |
|
| |
|