Scanned/Finished Bin | Original | / | 7/12/2013 | | SHARON | Location = Scanned/Finished Bin by SHARON | | Scanned/Finished Bin | 644262 |
To Be Scanned Bin | Original | / | 7/11/2013 | | REBECCA | Location = To Be Scanned Bin by REBECCA | | To Be Scanned Bin | 644163 |
Hazmat | Original | N | 7/11/2013 | REBECCA | REBECCA | dew 6/3/13 | | Hazmat | 644161 |
CO Springs DRE | Original | A | 7/11/2013 | RDCUSER | RDCUSER | APPROVED FOR MEDICAL OFFICE USE PER APPROVED AMENDED DEVELOPMENT PLAN NO. AR DP 06-00092-A4MN08-MM01. | | CO Springs DRE | 644152 |
Plumbing | Original | A | 7/11/2013 | TCRIPPEN | TCRIPPEN | | | Plumbing | 644120 |
Mechanical | Original | A | 7/9/2013 | DALEH | DALEH | | | Mechanical | 643561 |
Construction | Original | A | 7/9/2013 | JIMA | JIMA | | | Construction | 643555 |
Electrical | Original | A | 7/9/2013 | SHELBY | SHELBY | | | Electrical | 643529 |
Resubmittal 1 | Original | / | 7/2/2013 | REBECCA | REBECCA | Resubmittal #1 | | Resubmittal 1 | 642483 |
Hazmat | Original | A | 6/3/2013 | CSFIRE | CSFIRE | | csfdit | Hazmat | 635344 |
CO Springs Fire | Original | A | 6/3/2013 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 635343 |
Out to Review | Original | / | 5/30/2013 | RDCUSER | RDCUSER | TENTANT FIT-OUT FOR BONFILS BLOOD DONOR CENTER WITHIN EXISTING RETAIL CENTER. NEED TO AMEND THE DEVELOPMENT PLAN TO REFLECT THE CHANGE OF USE NOT LISTED ON THE APPROVED DEVELOPMENT PLAN (AR DP 06-00092-A3MM08). | | Out to Review | 634536 |
CO Springs DRE | Original | D | 5/30/2013 | RDCUSER | RDCUSER | TENTANT FIT-OUT FOR BONFILS BLOOD DONOR CENTER WITHIN EXISTING RETAIL CENTER. NEED TO AMEND THE DEVELOPMENT PLAN TO REFLECT THE CHANGE OF USE NOT LISTED ON THE APPROVED DEVELOPMENT PLAN (AR DP 06-00092-A3MM08). | | CO Springs DRE | 634535 |
Mechanical | Original | D | 5/29/2013 | DALEH | DALEH | size of duct to ex. fan 1 ? provide ventilation schedule for all rooms schedule existing rtu provide structural letter | | Mechanical | 634312 |
Enumeration | Original | A | 5/29/2013 | JEANNINE | JEANNINE | | | Enumeration | 634279 |
Electrical | Original | D | 5/29/2013 | SHELBY | SHELBY | 1. Comply 517.13 NEC for the phlebotomy area ( conduit and boxes must be metal). 2. Provide complete one line. 3. Provide building load calculation. | | Electrical | 634265 |
Plumbing | Original | D | 5/29/2013 | TCRIPPEN | TCRIPPEN | plumbing to be on p- pages , if your occupant load is more then 15 2- rest rooms required , provide water pipe size analysis data on plans | | Plumbing | 634252 |
Construction | Original | D | 5/29/2013 | JEFFREY | JEFFREY | Occupancy classification for proposed use is Group B, Business - revise code study form and code review on plans accordingly. Occupant load calculation is not based on functions of spaces within the facility - revise occupant load calculations accordingly. See plans for comments. Walk o.k. | | Construction | 634249 |
Out to Review | Original | / | 5/29/2013 | BPHILLIPS | BPHILLIPS | walking | | Out to Review | 633992 |
Floodplain | Original | N | 5/28/2013 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 633930 |