Out to Review | Original | / | 3/5/2014 | RDCUSER | RDCUSER | Plans given to Applicant. | | Out to Review | 691424 |
CO Springs DRE | Original | A | 3/5/2014 | RDCUSER | RDCUSER | Looked at Parking…. All ok approx 100,000 square feet of medical left. Will look at parking with construction of new buildings in Phase 1 (MLH) copied and pasted from PlanTrac to RBD by CLO. Stamped plans. (see full review) | | CO Springs DRE | 691423 |
Plumbing | 2/24/14 Plbg | A | 2/24/2014 | TCRIPPEN | TCRIPPEN | new splice pages see clouds | | Plumbing | 689007 |
Out to Review | 2/24/14 Plbg | / | 2/24/2014 | BPHILLIPS | BPHILLIPS | walking | | Out to Review | 688997 |
Electrical | 1/24/14 | A | 1/28/2014 | DOUG | DOUG | | | Electrical | 684084 |
Mechanical | 1/24/14 | A | 1/28/2014 | DALEH | DALEH | | | Mechanical | 684078 |
Construction | 1/24/14 | A | 1/28/2014 | MICHAELA | MICHAELA | | | Construction | 684074 |
Construction | 1/24/14 | D | 1/24/2014 | SHELLEY | SHELLEY | Add note clarifying that rated assemblies are not required per IBC...otherwise, supporting construction is an issue. | | Construction | 683524 |
Out to Review | 1/24/14 | / | 1/24/2014 | JANE | JANE | ERic walking | | Out to Review | 683521 |
Scanned/Finished Bin | 1/3/14 | / | 1/6/2014 | | KENYATTA | Location = Scanned/Finished Bin by KENYATTA | | Scanned/Finished Bin | 680232 |
Plumbing | 1/3/14 | A | 1/3/2014 | TCRIPPEN | TCRIPPEN | | | Plumbing | 680155 |
Electrical | 1/3/14 | A | 1/3/2014 | SHELBY | SHELBY | | | Electrical | 680152 |
Plumbing | 10/14/13 | A | 1/3/2014 | TCRIPPEN | TCRIPPEN | new splice pages see clouds | | Plumbing | 680109 |
Electrical | 1/3/14 | D | 1/3/2014 | SHELBY | SHELBY | Cloud changes throughout | | Electrical | 680103 |
Mechanical | 1/3/14 | A | 1/3/2014 | RUSSELL | RUSSELL | | | Mechanical | 680099 |
Out to Review | 1/3/14 | / | 1/3/2014 | NELIDA | NELIDA | Eric walking 200-5569 | | Out to Review | 680098 |
Mechanical | 10/14/13 | A | 10/14/2013 | DALEH | DALEH | | | Mechanical | 664260 |
Electrical | 10/14/13 | A | 10/14/2013 | SHELBY | SHELBY | | | Electrical | 664249 |
Construction | 10/14/13 | A | 10/14/2013 | MICHAELA | MICHAELA | | | Construction | 664244 |
Out to Review | 10/14/13 | / | 10/14/2013 | NELIDA | NELIDA | Chris walking 719-492-0805 | | Out to Review | 664233 |
Construction | Original | A | 7/17/2013 | JIMA | JIMA | | | Construction | 645544 |
Mechanical | Original | A | 7/17/2013 | DALEH | DALEH | | | Mechanical | 645449 |
Plumbing | Original | A | 7/17/2013 | TCRIPPEN | TCRIPPEN | | | Plumbing | 645415 |
Out to Review | Original | / | 7/17/2013 | JANE | JANE | Vince | | Out to Review | 645328 |
Finished Bin | Original | / | 7/16/2013 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 645238 |
Hazmat | Original | N | 7/16/2013 | CSFIRE | CSFIRE | No med gases or generator apparent | csfdit | Hazmat | 645162 |
CO Springs Fire | Original | A | 7/16/2013 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 645161 |
CO Springs DRE | Original | A | 7/12/2013 | MHERINGTON | MHERINGTON | parking ok approx 100,000 square feet of medical space remaining. Will check overall parking with final construction of new buildings | | CO Springs DRE | 644357 |
Fire | Original | / | 7/10/2013 | | CSZONING | Location = Fire by CSZONING | Dtortorice | Fire | 643829 |
CO Springs DRE | Original | D | 7/10/2013 | DTORTORICE | DTORTORICE | Tenant Finish to medical office - 9272 sq ft. Please provide an accurate account of each, general office and medical office permitted square footage to include what will be left over after each of the permit requests RBD Plan Track numbers 70038 and 70038. Original approved development plan figures were: Medical office = 136,998 sq ft and General Office = 45,666 sq ft. Resubmittal to be logged into Meggan Herington. (see full review) | | CO Springs DRE | 643828 |
Fire | Original | / | 7/10/2013 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 643827 |
CO Springs DRE | Original | D | 7/10/2013 | DTORTORICE | DTORTORICE | Tenant Finish to medical office - 9272 sq ft. Please provide an accurate account of each, General office and medical office permitted square footage to include what will be left over after each of the permit requests RBD Plan Track numbers 70038 and 70038. Original approved development plan figures were: Medical office = 136,998 sq ft and General Office = 45,666 sq ft. Rsubmittal to be logged into Meggan Herington. (see full review) | | CO Springs DRE | 643826 |
Zoning/Planning | Original | / | 7/2/2013 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 642261 |
Plan Coordinator | Original | / | 7/2/2013 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 642257 |
Mechanical | Original | D | 7/2/2013 | RUSSELL | RUSSELL | Hi-lited walls are per architectural sheets which is for occupancy separation for other than IBC purposes and to achieve that fire barrier rating, all duct penetrations when serving both sides requires to be protected with a fire damper, change EF-3 to a tranfsfer fan, exhaust fans per the 2009 IMC Section 501.2 are to discharge to the outdoors, a transfer fan can discharge to the plenum,verify concern of O.A. available to this space, if unit is producing 8000 cfm total, then it'll be a percentage of that to this finish unless this RTU serves only this tenant space | | Mechanical | 642256 |
Mechanical | Original | / | 7/2/2013 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 642232 |
Mechanical | Original | / | 7/1/2013 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 642088 |
Plan Coordinator | Original | / | 7/1/2013 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 642055 |
Plumbing | Original | D | 7/1/2013 | TCRIPPEN | TCRIPPEN | need to sign seal on P0.00 | | Plumbing | 642054 |
Plumbing | Original | / | 7/1/2013 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 642031 |
Plumbing | Original | / | 6/28/2013 | | MINDY | Location = Plumbing by MINDY | | Plumbing | 641856 |
Construction | Original | D | 6/28/2013 | MICHAELA | MICHAELA | Label wall types Show door ratings 1-hr. wall diagram misses wall assembly Walk-through OK | | Construction | 641764 |
Plan Coordinator | Original | / | 6/28/2013 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Plan Coordinator | 641748 |
Construction | Original | / | 6/28/2013 | | MINDY | Location = Construction by MINDY | | Construction | 641549 |
Plan Coordinator | Original | / | 6/28/2013 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 641538 |
Electrical | Original | A | 6/28/2013 | SHELBY | SHELBY | | | Electrical | 641536 |
Construction | Original | / | 6/28/2013 | SHELBY | SHELBY | In Current Review by SHELBY | | Construction | 641523 |
Construction | Original | / | 6/27/2013 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 641391 |
Plan Coordinator | Original | / | 6/27/2013 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 641366 |
Enumeration | Original | A | 6/27/2013 | JEANNINE | JEANNINE | See site plan included for location and suite numbers (Is combination of 200, 210, 220, & 230--using 200). | | Enumeration | 641365 |
Floodplain | Original | N | 6/25/2013 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 640664 |