Plumbing | 12/31/13 Plbg | A | 12/31/2013 | DALEH | DALEH | | | Plumbing | 679787 |
Out to Review | 12/31/13 Plbg | / | 12/31/2013 | BPHILLIPS | BPHILLIPS | walking | | Out to Review | 679771 |
Scanned/Finished Bin | Original | / | 8/28/2013 | | RITA | Location = Scanned/Finished Bin by RITA | | Scanned/Finished Bin | 654193 |
To Be Scanned Bin | Original | / | 8/26/2013 | | KENYATTA | Location = To Be Scanned Bin by KENYATTA | | To Be Scanned Bin | 653831 |
Plan Coordinator | Original | / | 8/26/2013 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 653823 |
Electrical | Original | A | 8/26/2013 | SHELBY | SHELBY | Provide plan revision to include 30 day metering as a splice prior to electrical final. | | Electrical | 653815 |
Out to Review | Original | / | 8/22/2013 | REBECCA | REBECCA | mike 719-471-7566 | | Out to Review | 653284 |
Finished Bin | Original | / | 8/21/2013 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 652938 |
Plan Coordinator | Original | / | 8/21/2013 | | MATTHEW | Location = Plan Coordinator by MATTHEW | | Plan Coordinator | 652920 |
Electrical | Original | D | 8/21/2013 | MATTHEW | MATTHEW | bold line weight showing new work does not exist (see E301 and E302) I can't tell if panels are existing or new work, provide panel schedule for panel UPS2LE and UPS2L (note referring to another project has been removed) | | Electrical | 652919 |
Electrical | Original | / | 8/21/2013 | MATTHEW | MATTHEW | In Current Review by MATTHEW | | Electrical | 652878 |
Electrical | Original | / | 8/21/2013 | | NELIDA | Location = Electrical by NELIDA | | Electrical | 652807 |
Mechanical | Original | A | 8/21/2013 | RUSSELL | RUSSELL | | | Mechanical | 652805 |
Resubmittal 1 | Original | / | 8/21/2013 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 652733 |
Hazmat | Original | A | 8/19/2013 | CSFIRE | CSFIRE | | dwithee | Hazmat | 652335 |
Hazmat | Original | A | 8/19/2013 | CSFIRE | CSFIRE | | dwithee | Hazmat | 652334 |
Out to Review | Original | / | 8/13/2013 | MINDY | MINDY | Jennifer 303 394 0211 | | Out to Review | 651079 |
Finished Bin | Original | / | 8/5/2013 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 649528 |
Hazmat | Original | D | 8/5/2013 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 649486 |
Hazmat | Original | A | 8/5/2013 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 649457 |
Hazmat | Original | / | 7/31/2013 | | CSFIRE | Location = Hazmat by CSFIRE | csfdit | Hazmat | 648604 |
CO Springs Fire | Original | A | 7/31/2013 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 648603 |
Fire | Original | / | 7/22/2013 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 646430 |
CO Springs DRE | Original | A | 7/22/2013 | DTORTORICE | DTORTORICE | Interior Finish - remodel - first floor St Francis Medical Center (see full review) | | CO Springs DRE | 646429 |
Zoning/Planning | Original | / | 7/22/2013 | | SHARON | Location = Zoning/Planning by SHARON | | Zoning/Planning | 646337 |
Plan Coordinator | Original | / | 7/22/2013 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 646330 |
Electrical | Original | D | 7/22/2013 | SHELBY | SHELBY | 1. Clarify labeling of feeder for panel UPS2LE at bottom of sheet E302. 2. Show DP1A and NL1A1 on NL1A panel schedule. 3. Provide results of 30 day metering prior to plan submittal or add a note requiring a plan revision prior to first electrical inspection to add the metering results. The note must make clear that the responsibility for any additional work that the metering makes necessary belongs to the design professional. All metering must be conducted per 220.87 NEC. 4. Provide panel schedules for panels CH2A, CL2H, CL20R5, and CL20R6. | | Electrical | 646329 |
Electrical | Original | / | 7/18/2013 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 645969 |
Electrical | Original | / | 7/16/2013 | | MINDY | Location = Electrical by MINDY | | Electrical | 645007 |
Plan Coordinator | Original | / | 7/16/2013 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 645004 |
Mechanical | Original | D | 7/16/2013 | RUSSELL | RUSSELL | Hi-lited walls as indicated are either "fire barrier", "smoke barrier" or "smoke partition", ducts penetrating those walls shall either be protect by a fire damper or smoke damper unless the requirements of section 607.5.2 & 607.5.4 are met, unable to determine since only a partial plan is being provided and unable to determine if serving a single smoke compartment, also verify is duct marked is located over fire barrier wall as shown, please provide clarification on drawing M401.3A for comments above | | Mechanical | 645003 |
Mechanical | Original | / | 7/16/2013 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 644960 |
Mechanical | Original | / | 7/15/2013 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 644885 |
Plan Coordinator | Original | / | 7/15/2013 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 644857 |
Plumbing | Original | A | 7/15/2013 | TCRIPPEN | TCRIPPEN | | | Plumbing | 644853 |
Plumbing | Original | / | 7/15/2013 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 644704 |
Plumbing | Original | / | 7/15/2013 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 644636 |
Plan Coordinator | Original | / | 7/15/2013 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 644611 |
Construction | Original | A | 7/15/2013 | MICHAELA | MICHAELA | | | Construction | 644608 |
Construction | Original | / | 7/12/2013 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 644546 |
Construction | Original | / | 7/12/2013 | | SHARON | Location = Construction by SHARON | | Construction | 644519 |
Plan Coordinator | Original | / | 7/12/2013 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 644517 |
Enumeration | Original | A | 7/12/2013 | AMY | AMY | fist floor | | Enumeration | 644516 |
Floodplain | Original | N | 7/12/2013 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 644377 |