Mechanical | 5/28/14 | A | 6/9/2014 | DALEH | DALEH | | | Mechanical | 712688 |
Resubmittal 1 | 5/28/14 | / | 6/9/2014 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 712682 |
Out to Review | 5/28/14 | / | 5/28/2014 | NELIDA | NELIDA | Jim walking 720-355-1349 | | Out to Review | 710142 |
Scanned/Finished Bin | 4/16/14 Access Controls | / | 5/28/2014 | | RITA | Location = Scanned/Finished Bin by RITA | | Scanned/Finished Bin | 710090 |
To Be Scanned Bin | 4/16/14 Access Controls | / | 5/28/2014 | | JANE | Location = To Be Scanned Bin by JANE | | To Be Scanned Bin | 710046 |
CO Springs Fire | 4/16/14 Access Controls | A | 5/27/2014 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 709875 |
CO Springs DRE | 4/16/14 Access Controls | A | 5/22/2014 | RITA | RITA | approved 05/21/14 per LJT | | CO Springs DRE | 709149 |
Fire | 4/16/14 Access Controls | / | 5/20/2014 | | KENYATTA | Location = Fire by KENYATTA | | Fire | 708362 |
Plan Coordinator | 4/16/14 Access Controls | / | 5/20/2014 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 708356 |
Construction | 4/16/14 Access Controls | A | 5/20/2014 | MICHAELA | MICHAELA | | | Construction | 708355 |
Construction | 4/16/14 Access Controls | / | 5/20/2014 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 708351 |
Construction | 4/16/14 Access Controls | / | 5/20/2014 | | REBECCA | Location = Construction by REBECCA | | Construction | 708346 |
Resubmittal 1 | 4/16/14 Access Controls | / | 5/20/2014 | REBECCA | REBECCA | Resubmittal #1 | | Resubmittal 1 | 708345 |
Finished Bin | 4/16/14 Access Controls | / | 5/7/2014 | | MICHAELA | Location = Finished Bin by MICHAEL | | Finished Bin | 705741 |
Construction | 4/16/14 Access Controls | / | 5/2/2014 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 704808 |
Finished Bin | 4/16/14 Access Controls | / | 4/24/2014 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 703040 |
CO Springs Fire | 4/16/14 Access Controls | D | 4/23/2014 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 702591 |
Fire | 4/16/14 Access Controls | / | 4/16/2014 | | RITA | Location = Fire by RITA | | Fire | 700802 |
Plan Coordinator | 4/16/14 Access Controls | / | 4/16/2014 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 700794 |
Construction | 4/16/14 Access Controls | D | 4/16/2014 | MICHAELA | MICHAELA | Insufficient information provided to document code compliant means of egress and accessibility No walk-through | | Construction | 700793 |
Construction | 4/16/14 Access Controls | / | 4/16/2014 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 700772 |
Construction | 4/16/14 Access Controls | / | 4/16/2014 | | BPHILLIPS | Location = Construction by BPHILLIPS | | Construction | 700763 |
- Not Set - | Original | / | 4/15/2014 | | NELIDA | Location = - Not Set - by NELIDA | | - Not Set - | 700479 |
Scanned/Finished Bin | Original | / | 1/7/2014 | | KENYATTA | Location = Scanned/Finished Bin by KENYATTA | | Scanned/Finished Bin | 680583 |
To Be Scanned Bin | Original | / | 1/6/2014 | | KENYATTA | Location = To Be Scanned Bin by KENYATTA | | To Be Scanned Bin | 680306 |
Plan Coordinator | Original | / | 1/6/2014 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 680302 |
Mechanical | Original | A | 1/6/2014 | RUSSELL | RUSSELL | | | Mechanical | 680301 |
Mechanical | Original | / | 1/6/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 680261 |
Mechanical | Original | / | 1/3/2014 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 680219 |
Plan Coordinator | Original | / | 1/3/2014 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 680215 |
Electrical | Original | A | 1/3/2014 | SHELBY | SHELBY | | | Electrical | 680214 |
Electrical | Original | / | 1/3/2014 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 680200 |
Electrical | Original | / | 1/3/2014 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 680159 |
Plan Coordinator | Original | / | 1/3/2014 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 680154 |
Construction | Original | A | 1/3/2014 | MICHAELA | MICHAELA | | | Construction | 680153 |
CSU Contract Admin. | Original | / | 1/3/2014 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | CSU Contract Admin. | 680149 |
CSU Contract Admin. | Original | / | 1/3/2014 | | JANE | Location = CSU Contract Admin. by JANE | | CSU Contract Admin. | 680111 |
Resubmittal 2 | Original | / | 1/3/2014 | JANE | JANE | Resubmittal #2 | | Resubmittal 2 | 680110 |
Out to Review | Original | / | 12/26/2013 | MINDY | MINDY | Mike 303 753 9600 | | Out to Review | 679218 |
Finished Bin | Original | / | 12/24/2013 | | REBECCA | Location = Finished Bin by REBECCA | | Finished Bin | 679011 |
CO Springs Fire | Original | A | 12/24/2013 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 678998 |
Fire | Original | / | 12/20/2013 | | KENYATTA | Location = Fire by KENYATTA | | Fire | 678306 |
Plan Coordinator | Original | / | 12/20/2013 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 678292 |
Mechanical | Original | D | 12/20/2013 | RUSSELL | RUSSELL | Still unable to complete mechanical review until architect provides a plan at a large enough scale so that the construction reviewer is able to determine wall ratings and likewise for mechanical to verify correct damper in rated walls, also, size of duct where new VAV-51 is connecting to existing duct, shown connecting to ceiling tile, also need to schedule existing RTU-2 to verify 50% O.A. based on VAV-51 schedule and note 21 on sheet M121, need to remove old sheets when submitting revised drawings, leave loose on top of set, label and schedule existing units on sheet M122, assume served by same RTU-2 so that O.A> can be verified, remove old M121 & M122 sheets, Sheet M401, need to darken background, to light and won't scan into RBD Data base, sheet M411, is work on 1 st floor served by same RTU-2 or by a different RTU?, need to be able to verify O.A. cfms in area of new work, similar for sheet M412 NO WALK | | Mechanical | 678279 |
Mechanical | Original | / | 12/19/2013 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 678215 |
Mechanical | Original | / | 12/19/2013 | | RITA | Location = Mechanical by RITA | | Mechanical | 678213 |
Plan Coordinator | Original | / | 12/19/2013 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 678188 |
Electrical | Original | D | 12/19/2013 | SHELBY | SHELBY | 1. Show/ include panels ME3P3A-4 and MEP4B-4 on one line. 2. Panel UP-ADMIN-A schedule shows no load VS sheets E 113 and E 114 where load is shown ( ckt's 1-3-5-7-14 etc ). | | Electrical | 678187 |
Electrical | Original | / | 12/18/2013 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 677902 |
Electrical | Original | / | 12/17/2013 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 677689 |
Plan Coordinator | Original | / | 12/17/2013 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 677686 |
Construction | Original | D | 12/17/2013 | MICHAELA | MICHAELA | Code analysis on G005 is not legible - please enlarge only the scope of work and clearly indicated existing rated assemblies Please provide an enlarged drawing of the new showers showing all ANSI compliant grab bars, clear floor space, etc. Indicate on floor plan pages all walls required to comply with 2/A502 Code study form is now missing. Walk-through OK | | Construction | 677685 |
Construction | Original | / | 12/17/2013 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 677680 |
Construction | Original | / | 12/17/2013 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 677658 |
Resubmittal 1 | Original | / | 12/17/2013 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 677656 |
Out to Review | Original | / | 12/6/2013 | REBECCA | REBECCA | mike barbee 970-391-0447 | | Out to Review | 675865 |
Finished Bin | Original | / | 12/5/2013 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 675652 |
Hazmat | Original | A | 12/5/2013 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 675588 |
Hazmat | Original | A | 12/5/2013 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 675587 |
Hazmat | Original | / | 12/4/2013 | | CSFIRE | Location = Hazmat by CSFIRE | csfdit | Hazmat | 675298 |
CO Springs Fire | Original | D | 12/4/2013 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 675297 |
Fire | Original | / | 11/26/2013 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 674328 |
CO Springs DRE | Original | A | 11/26/2013 | RDCUSER | RDCUSER | APPROVED FOR INTERIOR REMODEL - OFFICE USE. (see full review) | | CO Springs DRE | 674327 |
Zoning/Planning | Original | / | 11/22/2013 | RTEIXEIRA2 | RTEIXEIRA2 | In Current Review by RTEIXEIRA | | Zoning/Planning | 673798 |
Zoning/Planning | Original | / | 11/21/2013 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 673515 |
Plan Coordinator | Original | / | 11/21/2013 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 673292 |
Mechanical | Original | D | 11/21/2013 | RUSSELL | RUSSELL | Need construction review comment addressed regarding where the rated wall assemblies are and type of assembly on the first and second floor, to be able to determine damper requirements at duct penetrations, ie: fire barrier, fire partition, smoke barrier, smoke partition, rated corridor, etc.no mechanical review. Also provide a ventilation table for areas/rooms of new ductwork to show how ventilation is met, using a spread sheet based on Table 403.3 or ASHRAE Standard 62.1 2007, or schedule out existing RTU's serving these areas so ventilation can be verified based 2009 IMC Table 403.3 to verify O.A. | | Mechanical | 673291 |
Mechanical | Original | / | 11/21/2013 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 673241 |
Mechanical | Original | / | 11/18/2013 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 672457 |
Plan Coordinator | Original | / | 11/18/2013 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 672440 |
Plumbing | Original | N | 11/18/2013 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit | | Plumbing | 672439 |
Plumbing | Original | / | 11/18/2013 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 672424 |
Plumbing | Original | / | 11/18/2013 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 672395 |
Plan Coordinator | Original | / | 11/18/2013 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 672387 |
Electrical | Original | D | 11/18/2013 | DOUG | DOUG | 1 Clarify scope of work of one line diagram changes and verify use of notes. | | Electrical | 672386 |
Electrical | Original | / | 11/18/2013 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 672362 |
Electrical | Original | / | 11/14/2013 | | RITA | Location = Electrical by RITA | | Electrical | 671669 |
Plan Coordinator | Original | / | 11/14/2013 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 671642 |
Construction | Original | D | 11/14/2013 | MICHAELA | MICHAELA | Provide code plan showing existing rated assemblies located at scope of work Reference locations of rated wall assemblies being re-constructed Walk-through OK | | Construction | 671641 |
Construction | Original | / | 11/14/2013 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 671605 |
Construction | Original | / | 11/13/2013 | | RITA | Location = Construction by RITA | | Construction | 671457 |
Plan Coordinator | Original | / | 11/13/2013 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 671419 |
Enumeration | Original | A | 11/13/2013 | JEANNINE | JEANNINE | Single tenant building | | Enumeration | 671418 |
Floodplain | Original | N | 11/12/2013 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 670902 |