Mechanical | Splice 4-3-14 | A | 4/3/2014 | DALEH | DALEH | fire smoke damper that was shown on original approval was actual installed under another permit duct was already across corridor and into this suite. | | Mechanical | 698207 |
Out to Review | Splice 4-3-14 | / | 4/3/2014 | REBECCA | REBECCA | walking | | Out to Review | 698196 |
Scanned/Finished Bin | Original | / | 1/15/2014 | | RITA | Location = Scanned/Finished Bin by RITA | | Scanned/Finished Bin | 681736 |
To Be Scanned Bin | Original | / | 1/14/2014 | | KENYATTA | Location = To Be Scanned Bin by KENYATTA | | To Be Scanned Bin | 681494 |
Plan Coordinator | Original | / | 1/14/2014 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 681491 |
Mechanical | Original | A | 1/14/2014 | RUSSELL | RUSSELL | | | Mechanical | 681490 |
Mechanical | Original | / | 1/13/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 681432 |
Mechanical | Original | / | 1/13/2014 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 681398 |
Resubmittal 1 | Original | / | 1/13/2014 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 681384 |
Electrical | Original | A | 1/13/2014 | SHELBY | SHELBY | | | Electrical | 681373 |
Plumbing | Original | A | 1/13/2014 | TCRIPPEN | TCRIPPEN | | | Plumbing | 681364 |
CO Springs Fire | Original | A | 1/10/2014 | CSFIRE | CSFIRE | Submitted By: Embres, Rhonda C
contractor carried (see full review) | csfdit | CO Springs Fire | 681064 |
Enumeration | Original | A | 1/10/2014 | JEANNINE | JEANNINE | See G0.02 for site plan included | | Enumeration | 681060 |
Out to Review | Original | / | 12/26/2013 | NELIDA | NELIDA | Tom Elder 471-2708 | | Out to Review | 679197 |
Finished Bin | Original | / | 12/11/2013 | | MINDY | Location = Finished Bin by MINDY | | Finished Bin | 676849 |
Hazmat | Original | N | 12/10/2013 | CSFIRE | CSFIRE | | csfdit | Hazmat | 676514 |
CO Springs Fire | Original | D | 12/10/2013 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 676513 |
Out to Review | Original | / | 12/5/2013 | | DOUG | Location = Out to Review by DOUG | | Out to Review | 675782 |
Fire | Original | / | 12/5/2013 | | RDCUSER | Location = Fire by RDCUSER | | Fire | 675758 |
CO Springs DRE | Original | A | 12/5/2013 | RDCUSER | RDCUSER | APPROVED (PER RBT) FOR INTERIOR REMODEL ONLY. (see full review) | | CO Springs DRE | 675757 |
Zoning/Planning | Original | / | 12/5/2013 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 675725 |
Plan Coordinator | Original | / | 12/5/2013 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 675720 |
Electrical | Original | D | 12/5/2013 | DOUG | DOUG | 1. Key note 1 E0.01 does not match breaker size shown on IL-19,21,23 E0.02. 2. Remove extra sheets from set. 3. Fixed space heating demand to be 125% ckt IL-25,27 and etc. NEC 424.3(B) 4. GFI in break room behind REFER to be readily accessible. 5. Fixture types on plan not legible and will not scan. 6. Add to general note 2 E1.00 and E2.00 to provide full size plan spliced at PPRBD with revised circuits and panel schedules prior to final electrical inspection. NEC 408.4 | | Electrical | 675719 |
Electrical | Original | / | 12/5/2013 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 675527 |
Electrical | Original | / | 12/4/2013 | | RITA | Location = Electrical by RITA | | Electrical | 675211 |
Plan Coordinator | Original | / | 12/4/2013 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 675208 |
Mechanical | Original | D | 12/4/2013 | RUSSELL | RUSSELL | Separate plbg. & mech., need to schedule out the existing RTU/AHU to be able to verify O.A. cfms within space, need to schedule out the existing FPB's, background line need to be a solid line so that it will scan into out data base, and you can remove the wall in-fill dots, remove the demo work from the new work plan, if you need to provide a demo plan, provide it, is other existing dictwork also part of the base medium pressure duct system that isn't identified?, schedule all new grilles, registers and diffusers, size all new ductwork, label all new grilles registers, etc. NO WALK, return red line comment sheets with re-submittal, | | Mechanical | 675207 |
Mechanical | Original | / | 12/3/2013 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 675197 |
Mechanical | Original | / | 12/3/2013 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 675196 |
Electrical | Original | / | 12/3/2013 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 675187 |
Plan Coordinator | Original | / | 12/3/2013 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 675184 |
Plumbing | Original | D | 12/3/2013 | TCRIPPEN | TCRIPPEN | plumbing and mechanical to be on separate pages, see red lines | | Plumbing | 675183 |
Plumbing | Original | / | 12/3/2013 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 675111 |
Plumbing | Original | / | 12/3/2013 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 675082 |
Plan Coordinator | Original | / | 12/3/2013 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 675075 |
Construction | Original | A | 12/3/2013 | SHELLEY | SHELLEY | | | Construction | 675074 |
Construction | Original | / | 12/3/2013 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 675070 |
Construction | Original | / | 12/3/2013 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 675061 |
Plan Coordinator | Original | / | 12/3/2013 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 675039 |
Enumeration | Original | D | 12/3/2013 | JEANNINE | JEANNINE | Refer to AO.01 -- This structure has 3 different possible addresses; indicators are that the address per access is on the Pikes Peak side of the structure (please clarify). Provide site plan showing parcel, structure location, label street names, provide north arrow, show all tenant spaces and current addresses in use. | | Enumeration | 675038 |
Floodplain | Original | N | 12/2/2013 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 674845 |