Scanned/Finished Bin | Original | / | 1/21/2014 | | KENYATTA | Location = Scanned/Finished Bin by KENYATTA | | Scanned/Finished Bin | 682575 |
To Be Scanned Bin | Original | / | 1/17/2014 | | JANE | Location = To Be Scanned Bin by JANE | | To Be Scanned Bin | 682427 |
Hazmat | Original | A | 1/17/2014 | JANE | JANE | | | Hazmat | 682426 |
Mechanical | Original | A | 1/17/2014 | DALEH | DALEH | Per Russ no ventilation schedule is required due to the amount and percentage of o.s.a. provided through the existing rtus | | Mechanical | 682409 |
Plumbing | Original | A | 1/17/2014 | TCRIPPEN | TCRIPPEN | | | Plumbing | 682392 |
Out to Review | Original | / | 1/7/2014 | BPHILLIPS | BPHILLIPS | Jessica 471 7566 | | Out to Review | 680443 |
Finished Bin | Original | / | 12/20/2013 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 678405 |
Waste Water Div | Original | A | 12/20/2013 | CSUREVIEW | CSUREVIEW | Approved for interior finish only. Plans left with Chris Quinn from Contract Administration for his review. (mt_12/20/2013) | mtroche | Waste Water Div | 678317 |
Water Division | Original | A | 12/20/2013 | CSUREVIEW | CSUREVIEW | Approved for interior finish only. Plans left with Chris Quinn from Contract Administration for his review. (mt_12/20/2013) | mtroche | Water Division | 678318 |
Hazmat | Original | D | 12/19/2013 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 678090 |
Hazmat | Original | D | 12/19/2013 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 678089 |
Hazmat | Original | / | 12/18/2013 | | CSFIRE | Location = Hazmat by CSFIRE | csfdit | Hazmat | 677986 |
CO Springs Fire | Original | A | 12/18/2013 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 677985 |
Fire | Original | / | 12/11/2013 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 676854 |
CO Springs DRE | Original | A | 12/11/2013 | DTORTORICE | DTORTORICE | interior finish - medical (see full review) | | CO Springs DRE | 676853 |
Zoning/Planning | Original | / | 12/10/2013 | DTORTORICE | DTORTORICE | In Current Review by DTORTORICE | | Zoning/Planning | 676441 |
Zoning/Planning | Original | / | 12/10/2013 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 676363 |
Plan Coordinator | Original | / | 12/10/2013 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 676348 |
Plumbing | Original | D | 12/10/2013 | TCRIPPEN | TCRIPPEN | provide a water pipe size analysis data on plans , provide DFUS at drain line, note that there is a hot water circulating line or that no fixture is more than 100 feet from a water heater | | Plumbing | 676346 |
Plumbing | Original | / | 12/9/2013 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 676263 |
Plan Coordinator | Original | / | 12/9/2013 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 676237 |
Mechanical | Original | D | 12/9/2013 | RUSSELL | RUSSELL | Sheet M406, missing grille,register & diffuser designations throughout the plan as indicated, under you "KEY" notes, please add the labeling of the ducts in the shafts, ie: S.A., E.A.., R.A. etc, along with the size and if up &/or down, is any of the negative air in the ISO Rooms to be made up with door undercut or only when doors get opened ?, add scheduling of the existing AHU's that pertain to this finish only, add note: Provide a test and balance report to the mechanical inspector at time of the heating final inspection. | | Mechanical | 676236 |
Mechanical | Original | / | 12/9/2013 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 676179 |
Mechanical | Original | / | 12/9/2013 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 676178 |
Plumbing | Original | / | 12/9/2013 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 676175 |
Plan Coordinator | Original | / | 12/9/2013 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 676169 |
Electrical | Original | A | 12/9/2013 | SHELBY | SHELBY | | | Electrical | 676168 |
Electrical | Original | / | 12/5/2013 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 675528 |
Electrical | Original | / | 12/4/2013 | | RITA | Location = Electrical by RITA | | Electrical | 675318 |
Plan Coordinator | Original | / | 12/4/2013 | | JIMA | Location = Plan Coordinator by JIMA | | Plan Coordinator | 675307 |
Construction | Original | A | 12/4/2013 | JIMA | JIMA | | | Construction | 675306 |
Construction | Original | / | 12/3/2013 | JIMA | JIMA | In Current Review by JIMA | | Construction | 675172 |
Construction | Original | / | 12/3/2013 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 675147 |
Plan Coordinator | Original | / | 12/3/2013 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 675136 |
Enumeration | Original | A | 12/3/2013 | AMY | AMY | This is the Hospital side not the doctors office side. | | Enumeration | 675135 |
Floodplain | Original | N | 12/2/2013 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 674907 |