Finished Bin | Original | / | 3/28/2014 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 696798 |
CO Springs Fire | Original | N | 3/27/2014 | CSFIRE | CSFIRE | | csfdit | CO Springs Fire | 696785 |
Fire | Original | / | 3/26/2014 | | REBECCA | Location = Fire by REBECCA | | Fire | 696255 |
Mechanical | Original | D | 3/26/2014 | DALEH | DALEH | need construction comments addressed prior to mechanical review | | Mechanical | 696214 |
Mechanical | Original | / | 3/26/2014 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 696195 |
Mechanical | Original | / | 3/25/2014 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 696001 |
Plan Coordinator | Original | / | 3/25/2014 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 695991 |
Construction | Original | D | 3/25/2014 | MICHAELA | MICHAELA | The room with new boilers with over 400,000 BTU's constitutes incidental use - the room must either be fully sprinkllered or separated from the adjacent area by 1-hour construction Walk-through OK | | Construction | 695990 |
Construction | Original | / | 3/25/2014 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 695956 |
Construction | Original | / | 3/24/2014 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 695760 |
Floodplain | Original | N | 3/24/2014 | KENYATTA | KENYATTA | PER JKL 3/24/14 | | Floodplain | 695759 |