Electrical | 8/22/16 | A | 8/22/2016 | BERTHA | BERTHA | Changed service later to 500CU rather than AL. Revised upper level restroom and corridor. | | Electrical | 897037 |
Out to Review | 8/22/16 | / | 8/22/2016 | GITA | GITA | | | Out to Review | 897019 |
Out to Review | 7/15/16 | / | 7/18/2016 | SHELBY | SHELBY | | | Out to Review | 888335 |
Electrical | 7/15/16 | A | 7/18/2016 | SHELBY | SHELBY | | | Electrical | 888332 |
Construction | Original | A | 9/24/2015 | JIMA | JIMA | engineering letter for roof top units only | | Construction | 818355 |
Mechanical | 9/21/2015 | A | 9/21/2015 | RUSSELL | RUSSELL | Need structural letter for construction sign off for new RTU's | | Mechanical | 817400 |
Plumbing | 9/21/2015 | A | 9/21/2015 | TCRIPPEN | TCRIPPEN | New splice pages moving bath rooms has changed engineers. | | Plumbing | 817387 |
Out to Review | 9/21/2015 | / | 9/21/2015 | DOUG | DOUG | | | Out to Review | 817366 |
Electrical | 9/21/2015 | A | 9/21/2015 | DOUG | DOUG | New engineering firm Redraw. | | Electrical | 817365 |
Construction | 9/21/2015 | A | 9/21/2015 | MICHAELA | MICHAELA | | | Construction | 817351 |
Out to Review | 1/30/15 Trusses | / | 2/13/2015 | MINDY | MINDY | | | Out to Review | 762133 |
Plumbing | 1/30/15 Trusses | / | 2/5/2015 | | RITA | Location = Plumbing by RITA | | Plumbing | 760312 |
To Be Scanned Bin | 1/30/15 Trusses | / | 2/5/2015 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 760296 |
Plan Coordinator | 1/30/15 Trusses | / | 2/5/2015 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 760266 |
Construction | 1/30/15 Trusses | A | 2/5/2015 | MICHAELA | MICHAELA | Trusses | | Construction | 760265 |
Construction | 1/30/15 Trusses | / | 2/5/2015 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 760262 |
Construction | 1/30/15 Trusses | / | 2/5/2015 | | NELIDA | Location = Construction by NELIDA | | Construction | 760231 |
Finished Bin | 1/30/15 Trusses | / | 2/4/2015 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 759795 |
Plan Coordinator | 1/30/15 Trusses | / | 2/4/2015 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 759778 |
Construction | 1/30/15 Trusses | D | 2/4/2015 | MICHAELA | MICHAELA | Layout says "Not for Construction" | | Construction | 759773 |
Construction | 1/30/15 Trusses | / | 2/4/2015 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 759769 |
Construction | 1/30/15 Trusses | / | 2/3/2015 | | NELIDA | Location = Construction by NELIDA | | Construction | 759709 |
Finished Bin | 1/30/15 Trusses | / | 1/30/2015 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 759140 |
Plan Coordinator | 1/30/15 Trusses | / | 1/30/2015 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 759134 |
Construction | 1/30/15 Trusses | D | 1/30/2015 | MICHAELA | MICHAELA | Trusses Pending Truss engineering must be submitted a minimum of one week prior to frame inspection and cannot be walked through. The truss package must include a signed and dated “Shop Drawing Review” stamp from the design professional of record that verifies conformance with the approved construction design documents. Unless previously shown on the approved structural framing plans, the truss layout must show all necessary truss connection hardware including hangers, uplift connectors, and truss bearing enhancers. | | Construction | 759131 |
Construction | 1/30/15 Trusses | / | 1/30/2015 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 759124 |
Construction | 1/30/15 Trusses | / | 1/30/2015 | | NELIDA | Location = Construction by NELIDA | | Construction | 758969 |
CSU Contract Admin. | Original | A | 10/27/2014 | CSUAPPSPRM | CSUAPPSPRM | See paid utility receipt - Fees paid 10/27/2014 Bill id#366134052901 MKL | mkluke | CSU Contract Admin. | 741973 |
Out to Review | Original | / | 10/27/2014 | NELIDA | NELIDA | Rowell 719-659-4100 | | Out to Review | 741968 |
Scanned/Finished Bin | Original | / | 10/13/2014 | | RITA | Location = Scanned/Finished Bin by RITA | | Scanned/Finished Bin | 738947 |
To Be Scanned Bin | Original | / | 10/10/2014 | | KENYATTA | Location = To Be Scanned Bin by KENYATTA | | To Be Scanned Bin | 738919 |
CO Springs Fire | Original | A | 10/10/2014 | KENYATTA | KENYATTA | per dew | | CO Springs Fire | 738918 |
Fire | Original | / | 10/2/2014 | | RITA | Location = Fire by RITA | | Fire | 737072 |
Plan Coordinator | Original | / | 10/2/2014 | | NELIDA | Location = Plan Coordinator by NELIDA | | Plan Coordinator | 737048 |
Water Division | Original | A | 10/2/2014 | CSUREVIEW | CSUREVIEW | All comments addressed. Approved Utility Service Plan attached to planset | cquinn_ds | Water Division | 737034 |
Waste Water Div | Original | A | 10/2/2014 | CSUREVIEW | CSUREVIEW | All comments addressed. | cquinn_ds | Waste Water Div | 737032 |
Out to Review | Original | / | 10/1/2014 | REBECCA | REBECCA | bruce 337-6564 | | Out to Review | 736484 |
Health Dept. | Original | N | 10/1/2014 | REBECCA | REBECCA | 7-30-14 | | Health Dept. | 736483 |
Finished Bin | Original | / | 8/15/2014 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 727007 |
Water Division | Original | D | 8/15/2014 | CSUREVIEW | CSUREVIEW | Comments not addressed, yet. (mt_08/15/2012) | mtroche | Water Division | 726920 |
Waste Water Div | Original | D | 8/15/2014 | CSUREVIEW | CSUREVIEW | Comments not addressed, yet. (mt_08/15/2012) | mtroche | Waste Water Div | 726919 |
CSU Utilities | Original | / | 8/13/2014 | | CSFIRE | Location = CSU Utilities by CSFIRE | csfdit | CSU Utilities | 726438 |
CO Springs Fire | Original | D | 8/13/2014 | CSFIRE | CSFIRE | still need approved water plans attached (see full review) | csfdit | CO Springs Fire | 726437 |
Fire | Original | / | 8/6/2014 | | BPHILLIPS | Location = Fire by BPHILLIPS | | Fire | 725269 |
Mechanical | Original | A | 8/6/2014 | BPHILLIPS | BPHILLIPS | 8-6-14 rk | | Mechanical | 725268 |
Mechanical | Original | / | 8/6/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 725196 |
Mechanical | Original | / | 8/6/2014 | | BPHILLIPS | Location = Mechanical by BPHILLIPS | | Mechanical | 725138 |
Resubmittal 1 | Original | / | 8/6/2014 | NELIDA | NELIDA | Resubmittal #1 8/6/14 MECHANICAL ONLY. Place in FINISHED BIN after mech review | | Resubmittal 1 | 725137 |
Elevators | Original | A | 8/1/2014 | JOHNW | JOHNW | COMPLETE | | Elevators | 724190 |
Construction | Original | A | 7/31/2014 | DANM | DANM | | | Construction | 724152 |
Out to Review | Original | / | 7/29/2014 | JANE | JANE | Bruce 337 6564 | | Out to Review | 723487 |
Health Dept. | Original | / | 7/21/2014 | | KENYATTA | Location = Health Dept. by KENYATTA | | Health Dept. | 721634 |
Plan Coordinator | Original | / | 7/21/2014 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 721628 |
Mechanical | Original | D | 7/21/2014 | RUSSELL | RUSSELL | Duct that penetrates the lid of the elevator equipment room and the wall have the same rating as the elevator shaft, therefore requiring a fire/smoke damper, walls indicated as incidental use at the toilet room at the exhaust require a fire damper, ducts that penetrate the toilet room from the corridor as supply, have to be protected by a fire/smoke damper, these are typical at both levels, coordinate location of AC units and duct drops with the rated walls hat are to go to deck, add note that all medium pressure gas piping shall be labeled every 6 feet, support within structure per code and similar on roof, coordinate damper requirements with comments on sheet M2 versus schedule on sheet M3, O.A. will not be verified until the tenant finish, to verify occupancy and occupant load of each space served by AC, NO WALK | | Mechanical | 721627 |
Mechanical | Original | / | 7/21/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 721593 |
Mechanical | Original | / | 7/21/2014 | | RUSSELL | Location = Mechanical by RUSSELL | | Mechanical | 721592 |
Plan Coordinator | Original | / | 7/21/2014 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 721586 |
Construction | Original | D | 7/21/2014 | MICHAELA | MICHAELA | Non-sprinklered shell building - Corridors must be rated at all areas, exiting cannot be verified so worst case must be addressed Still missing listings for some rated assemblies Show locations of required draft stopping on framing pages Walk-through OK | | Construction | 721585 |
Construction | Original | / | 7/21/2014 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 721583 |
Mechanical | Original | / | 7/21/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 721534 |
Mechanical | Original | / | 7/18/2014 | | BPHILLIPS | Location = Mechanical by BPHILLIPS | | Mechanical | 721422 |
Out to Review | Original | / | 7/17/2014 | MINDY | MINDY | Lisa 630 3757 | | Out to Review | 721137 |
Finished Bin | Original | / | 7/15/2014 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 720615 |
Scanned/Finished Bin | Original | / | 7/15/2014 | | JOHNW | Location = Scanned/Finished Bin by JOHNW | | Scanned/Finished Bin | 720597 |
Elevators | Original | D | 7/15/2014 | JOHNW | JOHNW | PROVIDE ELEVATOR EQUIPMENT DETAILS, MACHINE ROOM AND PIT DETAILS ( ELEVATOR CONSTRUCTION NOTES ATTACHED TO BACK OF PLANS) | | Elevators | 720596 |
Elevators | Original | / | 7/14/2014 | | MINDY | Location = Elevators by MINDY | | Elevators | 720399 |
Water Division | Original | D | 7/14/2014 | CSUREVIEW | CSUREVIEW | Provide the approved Utility Service Plan(USP). Contact Utilities Development Services at 668-8259 with questions. plan to rbd. | awerner | Water Division | 720396 |
Waste Water Div | Original | D | 7/14/2014 | CSUREVIEW | CSUREVIEW | Provide the approved Utility Service Plan(USP). Contact Utilities Development Services at 668-8259 with questions. | awerner | Waste Water Div | 720394 |
Gas/Elec. Utils | Original | A | 7/14/2014 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final meter/service/transformer/etc locations. | awerner | Gas/Elec. Utils | 720393 |
City Engr (SERT) | Original | A | 7/10/2014 | CSENGINEER | CSENGINEER | Plan routed to CSU at RBD. | csengineer | City Engr (SERT) | 719705 |
CSU Utilities | Original | / | 7/10/2014 | | CSFIRE | Location = CSU Utilities by CSFIRE | csfdit | CSU Utilities | 719400 |
Hazmat | Original | N | 7/10/2014 | CSFIRE | CSFIRE | | csfdit | Hazmat | 719399 |
CO Springs Fire | Original | D | 7/10/2014 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 719397 |
CO Springs DRE | Original | A | 6/27/2014 | COLMEDO | COLMEDO | Per approved development plan. (see full review) | | CO Springs DRE | 717207 |
CSU Contract Admin. | Original | D | 6/26/2014 | CSUAPPSPRM | CSUAPPSPRM | Requires Approved Commercial Water Meter Sizing Form and Paid Utility Receipt - Plan to DRE MKL | mkluke | CSU Contract Admin. | 716671 |
CSU Contract Admin. | Original | / | 6/25/2014 | | RITA | Location = CSU Contract Admin. by RITA | | CSU Contract Admin. | 716558 |
Plan Coordinator | Original | / | 6/25/2014 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 716551 |
Mechanical | Original | N | 6/25/2014 | RUSSELL | RUSSELL | No mechanical or gas piping provided for core & shell, issue not mechanical permit | | Mechanical | 716549 |
Mechanical | Original | / | 6/25/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 716535 |
Mechanical | Original | / | 6/25/2014 | | RITA | Location = Mechanical by RITA | | Mechanical | 716523 |
Plan Coordinator | Original | / | 6/25/2014 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 716514 |
Electrical | Original | A | 6/25/2014 | SHELBY | SHELBY | | | Electrical | 716513 |
Electrical | Original | / | 6/23/2014 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 715955 |
Electrical | Original | / | 6/23/2014 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 715928 |
Plumbing | Original | A | 6/23/2014 | TCRIPPEN | TCRIPPEN | Plans approved as noted on plans shut off valve and check valve for elevator sump to be above and outside pit see red lines .Rest rooms at tenant finishes proceed at own risk. Occupant load may increase resorting in more rest room fixtures | | Plumbing | 715918 |
Plan Coordinator | Original | / | 6/23/2014 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plan Coordinator | 715901 |
Plan Coordinator | Original | / | 6/23/2014 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 715885 |
Construction | Original | D | 6/23/2014 | MICHAELA | MICHAELA | Trusses Pending - Truss engineering must be submitted a minimum of one week prior to frame inspection and cannot be walked through. The truss package must include a signed and dated “Shop Drawing Review” stamp from the design professional of record that verifies conformance with the approved construction design documents. Unless previously shown on the approved structural framing plans, the truss layout must show all necessary truss connection hardware including hangers, uplift connectors, and truss bearing enhancers. Missing IECC certificate - must be done for core and shell Soils report is older than 12 mos. - provide new report or re-certify Corridor cannot be partially rated - door in corridor must be eliminated to prevent travel into a less protected exit access Doors in exit enclosures and elevator equipment room must be 1-hr. Elevator equipment room needs a 1-hr ceiling Walls around exit enclosure and elevator equipment room must be rated Storage rooms are not permitted in exit enclosures Locate draftstopping in floors, ceiling and trusses See plan for additional comments No walk-through | | Construction | 715884 |
Construction | Original | / | 6/23/2014 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 715743 |
Construction | Original | / | 6/20/2014 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 715715 |
Plan Coordinator | Original | / | 6/20/2014 | | JEANNINE | Location = Plan Coordinator by JEANNINE | | Plan Coordinator | 715685 |
Enumeration | Original | A | 6/20/2014 | JEANNINE | JEANNINE | Site plan is DP-1; lot is platted. Suites numbers to be assigned at interior finishes by Enumerations. | | Enumeration | 715684 |
Floodplain | Original | N | 6/20/2014 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 715435 |
Floodplain | Original | N | 6/20/2014 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 715434 |