WP Fire | Original | A | 8/18/2014 | TWALLER | TWALLER | Signed off per Vernon Champlain 8/18/14 NOTE: No final fire inspection required. | | WP Fire | 727301 |
Water Division | Original | N | 8/12/2014 | DBURGESS | DBURGESS | Per Sally Riley 8/12/2014 | | Water Division | 726260 |
Waste Water Div | Original | N | 8/12/2014 | DBURGESS | DBURGESS | Per Sally Riley 8/12/2014 | | Waste Water Div | 726259 |
WP Zoning | Original | A | 8/12/2014 | DBURGESS | DBURGESS | Per Sally Riley 8/12/2014 | | WP Zoning | 726258 |
WP Floodplain | Original | N | 8/12/2014 | DBURGESS | DBURGESS | Per Sally Riley 8/12/2014 | | WP Floodplain | 726257 |
Woodland Park | Original | / | 8/12/2014 | | DBURGESS | Location = Woodland Park by DBURGESS | | Woodland Park | 726256 |
Out to Review | Original | / | 8/12/2014 | RUSSELL | RUSSELL | Jon Dickey | | Out to Review | 726043 |
Mechanical | Original | N | 8/12/2014 | RUSSELL | RUSSELL | | | Mechanical | 726042 |
WP Enumeration | Original | A | 8/12/2014 | JIMA | JIMA | re stamp of lost plans | | WP Enumeration | 726036 |
Woodland Park | Original | / | 8/8/2014 | | TWALLER | Location = Woodland Park by TWALLER | | Woodland Park | 725758 |
Out to Review | Original | / | 7/17/2014 | SHELBY | SHELBY | Keith 641 0871 | | Out to Review | 721087 |
Electrical | Original | N | 7/17/2014 | SHELBY | SHELBY | | | Electrical | 721086 |
Woodland Park Bin | Original | / | 7/11/2014 | | KENYATTA | Location = Woodland Park Bin by KENYATTA | | Woodland Park Bin | 720008 |
Plan Coordinator | Original | / | 7/11/2014 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 719986 |
Electrical | Original | D | 7/11/2014 | DOUG | DOUG | 1. Provide circuit numbers for relocated existing or new electrical. 2. Provide panel schedule if more than 5% added load on panel. 3. Provide one-line. | | Electrical | 719985 |
Electrical | Original | / | 7/10/2014 | | RITA | Location = Electrical by RITA | | Electrical | 719620 |
Plan Coordinator | Original | / | 7/10/2014 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 719611 |
Mechanical | Original | D | 7/10/2014 | RUSSELL | RUSSELL | Space created between the office and storage doesn't have any opening to the exterior for natural ventilation, therefore, need to know space usage in order to figure out how much mechanical ventilation and O.A. is required, if there's a supply register and a return air grille in this space, indicate such on this drawing or a mechanical drawing, also indicate furnace cfm along with O.A cfm to verify space meets ventilation requirements per '09 IMC Table 403.3 | | Mechanical | 719600 |
Mechanical | Original | / | 7/10/2014 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 719585 |
Mechanical | Original | / | 7/10/2014 | | RITA | Location = Mechanical by RITA | | Mechanical | 719571 |
Plan Coordinator | Original | / | 7/10/2014 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 719551 |
Plumbing | Original | N | 7/10/2014 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit | | Plumbing | 719547 |
Plumbing | Original | / | 7/10/2014 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 719518 |
Plumbing | Original | / | 7/10/2014 | | RITA | Location = Plumbing by RITA | | Plumbing | 719508 |
Plan Coordinator | Original | / | 7/10/2014 | | JIMA | Location = Plan Coordinator by JIMA | | Plan Coordinator | 719507 |
Construction | Original | A | 7/10/2014 | JIMA | JIMA | | | Construction | 719505 |
Construction | Original | / | 7/10/2014 | JIMA | JIMA | In Current Review by JIMA | | Construction | 719470 |
Construction | Original | / | 7/9/2014 | | REBECCA | Location = Construction by REBECCA | | Construction | 719369 |