Mechanical | Splice 2/23/2016 | A | 2/23/2016 | JUSTINC | JUSTINC | | | Mechanical | 849931 |
Electrical | Splice 2/23/2016 | A | 2/23/2016 | BRIAN | BRIAN | relocate unit heater---- | | Electrical | 849911 |
Out to Review | Splice 2/23/2016 | / | 2/23/2016 | MINDY | MINDY | walking splice | | Out to Review | 849904 |
Electrical | Splice 11-20-15 | A | 12/2/2015 | DOUG | DOUG | revised to minimal work | | Electrical | 833693 |
Resubmittal 1 | Splice 11-20-15 | / | 12/2/2015 | REBECCA | REBECCA | Resubmittal #1 | | Resubmittal 1 | 833684 |
Electrical | Splice 11-20-15 | D | 11/20/2015 | DOUG | DOUG | Need information from panels(s) to receive 18-20KVA of new load. Show panel and circuit numbers on plan. May need one line information as well. | | Electrical | 831547 |
Out to Review | Splice 11-20-15 | / | 11/20/2015 | REBECCA | REBECCA | walking | | Out to Review | 831524 |
Mechanical | Splice 11/6/2015 | A | 11/6/2015 | JUSTINC | JUSTINC | | | Mechanical | 828784 |
Plumbing | Splice 11/6/2015 | A | 11/6/2015 | TCRIPPEN | TCRIPPEN | new splice see clouded are wall change and engineer name. | | Plumbing | 828778 |
Electrical | Splice 11/6/2015 | A | 11/6/2015 | DOUG | DOUG | New title block for new architect | | Electrical | 828759 |
Construction | Splice 11/6/2015 | A | 11/6/2015 | MICHAELA | MICHAELA | | | Construction | 828749 |
Out to Review | Splice 11/6/2015 | / | 11/6/2015 | MINDY | MINDY | walking splice | | Out to Review | 828733 |
CSU Contract Admin. | Original | N | 8/14/2015 | CSUAPPSPRM | CSUAPPSPRM | | mkluke | CSU Contract Admin. | 807975 |
Enumeration | Original | A | 6/30/2015 | BPHILLIPS | BPHILLIPS | AV 4/9/15 | | Enumeration | 795200 |
Electrical | Original | A | 6/29/2015 | DOUG | DOUG | | | Electrical | 795045 |
Resubmittal 3 | Original | / | 6/29/2015 | DOUG | DOUG | Resubmittal #3 Electrical Only | | Resubmittal 3 | 795044 |
Scanned/Finished Bin | Original | / | 6/25/2015 | | RITA | Location = Scanned/Finished Bin by RITA | | Scanned/Finished Bin | 794621 |
To Be Scanned Bin | Original | / | 6/25/2015 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 794610 |
Construction | Original | A | 6/25/2015 | JAY | JAY | Previously approved for Open Hole inspection in lieu of Soils Report - See Plan Tracking Notes. Updated details added to plan set via email from Curtis at Hauser Arch | | Construction | 794595 |
Finished Bin | Original | / | 6/18/2015 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 792913 |
Plan Coordinator | Original | / | 6/18/2015 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 792912 |
Electrical | Original | A | 6/18/2015 | SHELBY | SHELBY | | | Electrical | 792911 |
Electrical | Original | / | 6/18/2015 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 792886 |
Electrical | Original | / | 6/16/2015 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 792408 |
Plan Coordinator | Original | / | 6/16/2015 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 792398 |
Construction | Original | D | 6/16/2015 | MICHAELA | MICHAELA | Provide soils report - must be re-certified, stamp may not be older than 12 mos. Clarify support for existing roof structure adjacent to new fire wall Walk-through with Michael only or re-submit | | Construction | 792397 |
Construction | Original | / | 6/16/2015 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 792321 |
Construction | Original | / | 6/12/2015 | | JANE | Location = Construction by JANE | | Construction | 791649 |
Resubmittal 2 | Original | / | 6/12/2015 | JANE | JANE | Resubmittal #2 | | Resubmittal 2 | 791648 |
Out to Review | Original | / | 6/10/2015 | REBECCA | REBECCA | RANDY MAXWELL 719-246-4256 | | Out to Review | 791044 |
Finished Bin | Original | / | 4/23/2015 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 778824 |
CO Springs Fire | Original | A | 4/22/2015 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 778501 |
Fire | Original | / | 4/21/2015 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 777826 |
CO Springs DRE | Original | A | 4/21/2015 | DTORTORICE | DTORTORICE | CREATE NEW SUITE (443) AND 580 SQ FT. ADDITION. OK TO PERMIT PER CPC DP 01-00134-A9MJ14-MM01 (see full review) | | CO Springs DRE | 777825 |
Zoning/Planning | Original | / | 4/14/2015 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 776398 |
Plan Coordinator | Original | / | 4/14/2015 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 776381 |
Electrical | Original | D | 4/14/2015 | DOUG | DOUG | 1. Show transformer size. 2. Comply NEC 250.6 Do not use ground conductor between Utility connection and service disconnect(s) in a parallel path with the neutral. | | Electrical | 776380 |
Electrical | Original | / | 4/13/2015 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 775778 |
Electrical | Original | / | 4/10/2015 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 775412 |
Plan Coordinator | Original | / | 4/10/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 775389 |
Mechanical | Original | A | 4/10/2015 | RUSSELL | RUSSELL | | | Mechanical | 775388 |
Mechanical | Original | / | 4/10/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 775365 |
Mechanical | Original | / | 4/10/2015 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 775328 |
Plan Coordinator | Original | / | 4/10/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 775321 |
Plumbing | Original | A | 4/10/2015 | TCRIPPEN | TCRIPPEN | | | Plumbing | 775320 |
Plumbing | Original | / | 4/10/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 775311 |
Plumbing | Original | / | 4/10/2015 | | REBECCA | Location = Plumbing by REBECCA | | Plumbing | 775304 |
Plan Coordinator | Original | / | 4/10/2015 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 775302 |
Construction | Original | D | 4/10/2015 | SHELLEY | SHELLEY | Unlimited area has not been proven - verify complete compliance with 507.3 - it appears that suite 403 is A-2, how are provisions of 507.3.1 being met?; provide IECC for envelope; provide soils report referenced soils report with update letter dated within last twelve months; see plans; no walk. | | Construction | 775300 |
Construction | Original | / | 4/10/2015 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 775253 |
Construction | Original | / | 4/9/2015 | | MINDY | Location = Construction by MINDY | | Construction | 775094 |
Plan Coordinator | Original | / | 4/9/2015 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 775059 |
Enumeration | Original | A | 4/9/2015 | AMY | AMY | See page AO for suite numbering for 1845 Briargate Pkwy-this space is suite 443 | | Enumeration | 775058 |
Enumeration | Original | / | 4/9/2015 | AMY | AMY | In Current Review by AMY | | Enumeration | 775057 |
Enumeration | Original | / | 4/8/2015 | | BPHILLIPS | Location = Enumeration by BPHILLIPS | | Enumeration | 774613 |
Resubmittal 1 | Original | / | 4/8/2015 | BPHILLIPS | BPHILLIPS | Resubmittal #1 4/8/15 | | Resubmittal 1 | 774612 |
Out to Review | Original | / | 3/12/2015 | NELIDA | NELIDA | Joe Scheiner 719-492-8780 | | Out to Review | 767826 |
Finished Bin | Original | / | 2/27/2015 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 765080 |
City Engr (SERT) | Original | N | 2/27/2015 | CSENGINEER | CSENGINEER | Plan routed to RBD. pvm | csengineer | City Engr (SERT) | 765057 |
Water Division | Original | N | 2/27/2015 | CSUREVIEW | CSUREVIEW | No conflicts shown. (mt_02/27/2015) | mtroche | Water Division | 764848 |
Waste Water Div | Original | N | 2/27/2015 | CSUREVIEW | CSUREVIEW | No conflicts shown. (mt_02/27/2015) | mtroche | Waste Water Div | 764846 |
Gas/Elec. Utils | Original | N | 2/27/2015 | CSUREVIEW | CSUREVIEW | No conflicts shown. (mt_02/27/2015) | mtroche | Gas/Elec. Utils | 764845 |
CSU Utilities | Original | / | 2/25/2015 | | CSFIRE | Location = CSU Utilities by CSFIRE | csfdit | CSU Utilities | 764303 |
Hazmat | Original | N | 2/25/2015 | CSFIRE | CSFIRE | | csfdit | Hazmat | 764302 |
CO Springs Fire | Original | D | 2/25/2015 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 764301 |
Fire | Original | / | 2/19/2015 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 763468 |
CO Springs DRE | Original | D | 2/19/2015 | DTORTORICE | DTORTORICE | Interior Remodel and addition suite 443. the code study appears to conflict indicating this is core and shell modification to the existing structure and that a tenant finish will come under a separate submittal. this submittal resembles the submittal 80035 at the same address but under suite 435 whereby I indicated that the 580 sq ft addition to the front of the existing store front, (formerly Coldwater Creek) - proposed to be Go Calendars requires that you fill out the attached pre-application request form and fax to 719-385-5167, as this project may require a development plan amendment to CPC DP 01-00134-A9MN14 to address the 580 sq ft addition. (see full review) | | CO Springs DRE | 763467 |
Zoning/Planning | Original | / | 2/11/2015 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 761642 |
Plan Coordinator | Original | / | 2/11/2015 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 761621 |
Electrical | Original | D | 2/11/2015 | SHELBY | SHELBY | 1. Options are not allowed. 2. Feeder 4N supply side bonding jumper is incorrect. 3. Remove parallel neutral from feeder 2E. | | Electrical | 761620 |
Electrical | Original | / | 2/11/2015 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 761565 |
Electrical | Original | / | 2/11/2015 | | RITA | Location = Electrical by RITA | | Electrical | 761430 |
Plumbing | Original | D | 2/11/2015 | TCRIPPEN | TCRIPPEN | See Plan Track # 80035 & 80036 for similar comments this set. | | Plumbing | 761406 |
Plumbing | Original | / | 2/11/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 761404 |
Plumbing | Original | / | 2/11/2015 | | RITA | Location = Plumbing by RITA | | Plumbing | 761378 |
Plan Coordinator | Original | / | 2/11/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 761375 |
Mechanical | Original | D | 2/11/2015 | RUSSELL | RUSSELL | See Plan Track # 80035 & 80036 for similar comments this set. | | Mechanical | 761373 |
Mechanical | Original | / | 2/10/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 761324 |
Mechanical | Original | / | 2/10/2015 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 761189 |
Plan Coordinator | Original | / | 2/10/2015 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 761141 |
Construction | Original | D | 2/10/2015 | MICHAELA | MICHAELA | Provide current soils report or re-certification letter for report provided (SEE PLAN NOTES ADDED BY AJE) This is a finish - provide occupant load Provide a site plan with dimensions and to scale Clarify description of scope of work on plan and code study Complete all sections of code study - plan reference is not acceptable Remove all references to "optional/alternate" - not permitted Remove duplicate structural pages See plan No walk-through | | Construction | 761140 |
Construction | Original | / | 2/6/2015 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 760626 |
Construction | Original | / | 2/6/2015 | | MINDY | Location = Construction by MINDY | | Construction | 760462 |
Plan Coordinator | Original | / | 2/6/2015 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 760457 |
Enumeration | Original | D | 2/6/2015 | AMY | AMY | This building address is 1845 Briargate Pkwy suite 443 interior finish & addition. Suite numbering and all addressing is assigned and approved by the Enumerations Department.
Code Study Form and each and every page of this plan should reflect the correct address along with suite number.
Label the address of the building on the vicinity map along with all current suite numbers for this building 1845. | | Enumeration | 760456 |
Enumeration | Original | / | 2/6/2015 | AMY | AMY | In Current Review by AMY | | Enumeration | 760455 |
Floodplain | Original | N | 2/5/2015 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 760290 |
Floodplain | Original | N | 2/5/2015 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain | | Floodplain | 760289 |