To Be Scanned Bin | Splice 3-2-16 | / | 7/6/2016 | | MINDY | Location = To Be Scanned Bin by MINDY | | To Be Scanned Bin | 885092 |
CO Springs Fire | Splice 3-2-16 | A | 3/7/2016 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 852662 |
Mechanical | Splice 3-2-16 | A | 3/2/2016 | DALEH | DALEH | revised to resize duct | | Mechanical | 851767 |
Construction | Splice 3-2-16 | A | 3/2/2016 | DANM | DANM | Swapping changing/lockerrooms and staff toilet | | Construction | 851759 |
Plumbing | Splice 3-2-16 | A | 3/2/2016 | TCRIPPEN | TCRIPPEN | New splice pages remove and reroute drain line due thick concrete | | Plumbing | 851737 |
Electrical | Splice 3-2-16 | A | 3/2/2016 | SHELBY | SHELBY | | | Electrical | 851722 |
Out to Review | Splice 3-2-16 | / | 3/2/2016 | REBECCA | REBECCA | walking | | Out to Review | 851691 |
Electrical | Splice 5/6/15 | A | 5/21/2015 | SHELBY | SHELBY | To reflect mechanical changes | | Electrical | 786408 |
Mechanical | Splice 5/6/15 | A | 5/21/2015 | RUSSELL | RUSSELL | | | Mechanical | 786381 |
Out to Review | Splice 5/6/15 | / | 5/11/2015 | JANE | JANE | hUNG | | Out to Review | 783647 |
Finished Bin | Splice 5/6/15 | / | 5/8/2015 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 783015 |
Plan Coordinator | Splice 5/6/15 | / | 5/8/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 783011 |
Mechanical | Splice 5/6/15 | D | 5/8/2015 | RUSSELL | RUSSELL | EF-1 & LVR-1 are both scheduled at 1000 cfm exhaust, but the 2 exhaust grilles on sheet M201 are scheduled at 525 cfm exhaust for a total of 1050? coordinate which is suppose to be the correct cfm, damper duct according to smoke barrier penetrations in multiple location adn where serving on both sides of the smoke barrier, similar where penetrating an incidental use wall | | Mechanical | 783010 |
Mechanical | Splice 5/6/15 | / | 5/8/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 782962 |
Mechanical | Splice 5/6/15 | / | 5/8/2015 | | KENYATTA | Location = Mechanical by KENYATTA | | Mechanical | 782869 |
Plan Coordinator | Splice 5/6/15 | / | 5/8/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 782856 |
Plumbing | Splice 5/6/15 | A | 5/8/2015 | TCRIPPEN | TCRIPPEN | new splice pages see clouds | | Plumbing | 782855 |
Plumbing | Splice 5/6/15 | / | 5/8/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 782837 |
Plumbing | Splice 5/6/15 | / | 5/7/2015 | | RITA | Location = Plumbing by RITA | | Plumbing | 782810 |
Plan Coordinator | Splice 5/6/15 | / | 5/7/2015 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 782795 |
Electrical | Splice 5/6/15 | A | 5/7/2015 | SHELBY | SHELBY | | | Electrical | 782794 |
Electrical | Splice 5/6/15 | / | 5/7/2015 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 782683 |
Electrical | Splice 5/6/15 | / | 5/7/2015 | | RITA | Location = Electrical by RITA | | Electrical | 782671 |
Plan Coordinator | Splice 5/6/15 | / | 5/7/2015 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 782668 |
Construction | Splice 5/6/15 | A | 5/7/2015 | MICHAELA | MICHAELA | | | Construction | 782667 |
Construction | Splice 5/6/15 | / | 5/7/2015 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 782610 |
Construction | Splice 5/6/15 | / | 5/6/2015 | | RITA | Location = Construction by RITA | | Construction | 782471 |
Out to Review | Splice 5/6/15 | / | 5/6/2015 | MINDY | MINDY | | | Out to Review | 782427 |
Scanned/Finished Bin | Original | / | 4/9/2015 | | RITA | Location = Scanned/Finished Bin by RITA | | Scanned/Finished Bin | 775089 |
To Be Scanned Bin | Original | / | 4/9/2015 | | MINDY | Location = To Be Scanned Bin by MINDY | | To Be Scanned Bin | 775010 |
Plan Coordinator | Original | / | 4/9/2015 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 774991 |
Electrical | Original | A | 4/9/2015 | DOUG | DOUG | | | Electrical | 774990 |
Electrical | Original | / | 4/9/2015 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 774950 |
Electrical | Original | / | 4/8/2015 | | RITA | Location = Electrical by RITA | | Electrical | 774775 |
Finished Bin | Original | / | 4/8/2015 | | REBECCA | Location = Finished Bin by REBECCA. waiting for aditional pages before routing to electrical | | Finished Bin | 774758 |
Resubmittal 2 | Original | / | 4/8/2015 | REBECCA | REBECCA | Resubmittal #2 | | Resubmittal 2 | 774757 |
Out to Review | Original | / | 4/2/2015 | MINDY | MINDY | John 491 4527 | | Out to Review | 773249 |
Finished Bin | Original | / | 4/1/2015 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 772808 |
Hazmat | Original | A | 4/1/2015 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 772710 |
Hazmat | Original | / | 3/26/2015 | | RITA | Location = Hazmat by RITA | | Hazmat | 771323 |
Plan Coordinator | Original | / | 3/26/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 771307 |
Mechanical | Original | A | 3/26/2015 | RUSSELL | RUSSELL | | | Mechanical | 771305 |
Mechanical | Original | / | 3/26/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 771292 |
Mechanical | Original | / | 3/25/2015 | | RITA | Location = Mechanical by RITA | | Mechanical | 771128 |
Plan Coordinator | Original | / | 3/25/2015 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 771119 |
Electrical | Original | D | 3/25/2015 | DOUG | DOUG | In general lighting is unclear. The plan is difficult to read (poor resolution) as well. The lighting note directs that the shaded fixtures must be on the emergency system. The code is more specific limiting egress and exit to life safety branches and task illumination in critical care areas to the critical branches.
In general the plan is difficult to follow as the branch circuits to not follow the naming convention of the panels. For example on plan the circuits are called SCL1A-##, or SL1A4-## while on the one line and panel schedules the convention is SC-L1A-## or S-L1A-## respectively.
1. Indicate what fixtures are on each respective system. 2. Door openers are shown on critical power and code limits these to life safety. 3. Fan coils and exhaust fans are shown on critical branch and are limited to the equipment branch. 4. Receptacles for the nurse area coffee bar is shown on the critical branch. For greater clarity refer to NEC 517.30 (B) 2&3. 5. Life Safety Branch is not identified on the one-line. Assumed panel named CL-###-## or SL-###-##? | | Electrical | 771118 |
Electrical | Original | / | 3/25/2015 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 770900 |
Electrical | Original | / | 3/24/2015 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 770656 |
Plan Coordinator | Original | / | 3/24/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 770645 |
Plumbing | Original | A | 3/24/2015 | TCRIPPEN | TCRIPPEN | | | Plumbing | 770644 |
Plumbing | Original | / | 3/24/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 770617 |
Plumbing | Original | / | 3/24/2015 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 770558 |
Plan Coordinator | Original | / | 3/24/2015 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 770544 |
Construction | Original | A | 3/24/2015 | MICHAELA | MICHAELA | | | Construction | 770543 |
Construction | Original | / | 3/24/2015 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 770490 |
Construction | Original | / | 3/20/2015 | | JANE | Location = Construction by JANE | | Construction | 769994 |
Resubmittal 1 | Original | / | 3/20/2015 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 769993 |
Out to Review | Original | / | 3/9/2015 | MINDY | MINDY | Ryan 720 271 2884 | | Out to Review | 766899 |
Finished Bin | Original | / | 3/9/2015 | | KENYATTA | Location = Finished Bin by KENYATTA | | Finished Bin | 766872 |
Hazmat | Original | D | 3/9/2015 | CSFIRE | CSFIRE | Submitted By: Yeager, Kay A (see full review) | csfirehm | Hazmat | 766689 |
Hazmat | Original | / | 2/27/2015 | | CSFIRE | Location = Hazmat by CSFIRE | csfdit | Hazmat | 765071 |
CO Springs Fire | Original | A | 2/27/2015 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 765070 |
Fire | Original | / | 2/23/2015 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 763968 |
CO Springs DRE | Original | N | 2/23/2015 | DTORTORICE | DTORTORICE | Interior Remodel - installation of a new catherization laboratory and other room in existing hospital. (see full review) | | CO Springs DRE | 763967 |
Zoning/Planning | Original | / | 2/17/2015 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 762713 |
Plan Coordinator | Original | / | 2/17/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 762669 |
Plumbing | Original | D | 2/17/2015 | TCRIPPEN | TCRIPPEN | Provide square footage at each roof drain | | Plumbing | 762667 |
Plumbing | Original | / | 2/17/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 762561 |
Plumbing | Original | / | 2/17/2015 | | KENYATTA | Location = Plumbing by KENYATTA | | Plumbing | 762516 |
Plan Coordinator | Original | / | 2/17/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 762506 |
Mechanical | Original | D | 2/17/2015 | RUSSELL | RUSSELL | Remove item if not associated with this permit package, sheet M103, sheet M201, for all areas of work, provide a ventilation table per '09 IMC Table 403.3 to verify O.A. ventilation and schedule AHU that serves area of work, NO WALK, return comments | | Mechanical | 762505 |
Mechanical | Original | / | 2/17/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 762438 |
Mechanical | Original | / | 2/12/2015 | | RITA | Location = Mechanical by RITA | | Mechanical | 761884 |
Plan Coordinator | Original | / | 2/12/2015 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 761876 |
Electrical | Original | D | 2/12/2015 | SHELBY | SHELBY | 1. Please provide one line. 2. Comply with 517.32 and 517.33 NEC. | | Electrical | 761875 |
Electrical | Original | / | 2/11/2015 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 761817 |
Electrical | Original | / | 2/11/2015 | | RITA | Location = Electrical by RITA | | Electrical | 761778 |
Plan Coordinator | Original | / | 2/11/2015 | | MICHAELA | Location = Plan Coordinator by MICHAEL | | Plan Coordinator | 761770 |
Construction | Original | D | 2/11/2015 | MICHAELA | MICHAELA | Locate all smoke barriers in the scope of work Provide listed assemblies for all rated walls Label all new walls for type Show new doors in smoke barriers as rated assemblies and indicate required hardware Walk-through OK | | Construction | 761768 |
Construction | Original | / | 2/11/2015 | MICHAELA | MICHAELA | In Current Review by MICHAEL | | Construction | 761434 |
Construction | Original | / | 2/11/2015 | | RITA | Location = Construction by RITA | | Construction | 761425 |
Floodplain | Original | N | 2/11/2015 | AMY | AMY | | | Floodplain | 761408 |
Enumeration | Original | A | 2/11/2015 | AMY | AMY | | | Enumeration | 761407 |
Enumeration | Original | / | 2/11/2015 | AMY | AMY | In Current Review by AMY | | Enumeration | 761405 |