Scanned/Finished Bin | Original | / | 4/24/2015 | | KENYATTA | Location = Scanned/Finished Bin by KENYATTA | | Scanned/Finished Bin | 779141 |
To Be Scanned Bin | Original | / | 4/24/2015 | | REBECCA | Location = To Be Scanned Bin by REBECCA | | To Be Scanned Bin | 779120 |
Construction | Original | A | 4/24/2015 | MICHAELA | MICHAELA | | | Construction | 779119 |
CO Springs Fire | Original | A | 4/24/2015 | CSFIRE | CSFIRE | Submitted By: Embres, Rhonda C
WALK THRU (see full review) | csfdit | CO Springs Fire | 779108 |
Enumeration | Original | A | 4/24/2015 | AMY | AMY | 363 | | Enumeration | 779089 |
Electrical | Original | A | 4/24/2015 | DOUG | DOUG | | | Electrical | 779079 |
Mechanical | Original | A | 4/24/2015 | DALEH | DALEH | | | Mechanical | 779068 |
Out to Review | Original | / | 4/22/2015 | REBECCA | REBECCA | norm 303-385-1203 | | Out to Review | 778355 |
Hazmat | Original | N | 4/22/2015 | CSFIRE | CSFIRE | rce
walk thru | csfdit | Hazmat | 778339 |
CO Springs Fire | Original | D | 4/22/2015 | CSFIRE | CSFIRE | Submitted By: Embres, Rhonda C
walk thru (see full review) | csfdit | CO Springs Fire | 778338 |
Fire | Original | / | 4/16/2015 | | DTORTORICE | Location = Fire by DTORTORICE | | Fire | 776875 |
CO Springs DRE | Original | N | 4/16/2015 | DTORTORICE | DTORTORICE | Interior Remodel of lease spaces 363 and 371 in mall for the retail shop " Maurices". (see full review) | | CO Springs DRE | 776874 |
Zoning/Planning | Original | / | 4/14/2015 | | RDCUSER | Location = Zoning/Planning by RDCUSER | | Zoning/Planning | 776136 |
Out to Review | Original | / | 4/14/2015 | RDCUSER | RDCUSER | Norm Herman took plans at 10:51 on 4/14/15 | | Out to Review | 776117 |
Zoning/Planning | Original | / | 4/13/2015 | | KENYATTA | Location = Zoning/Planning by KENYATTA | | Zoning/Planning | 775714 |
Plan Coordinator | Original | / | 4/13/2015 | | DOUG | Location = Plan Coordinator by DOUG | | Plan Coordinator | 775667 |
Electrical | Original | D | 4/13/2015 | DOUG | DOUG | 1. Comply NEC 250.102 Supply side bonding jumpers for separately derived systems sized and installed per NEC 250.30 and Table 250.66. 2. Comply Check List requirements for calculated fault currents on one line shown as Short Circuit Current Available (SCA). Required at all major components typically with a fault current withstand rating. http://goo.gl/6J5cXj 3. Comply 220.87 Existing Load determination. If exception for 30 day metering is to be used and provided as a deferred submittal the demand metering must be provided as a plan splice to plan review prior to final electrical inspection. This metering may require additional work and upgrade to service and is done at own risk. 4. Comply Check List requirements for Complete One line included existing equipment at service. http://goo.gl/6J5cXj | | Electrical | 775666 |
Electrical | Original | / | 4/9/2015 | DOUG | DOUG | In Current Review by DOUG | | Electrical | 775055 |
Electrical | Original | / | 4/8/2015 | | RITA | Location = Electrical by RITA | | Electrical | 774754 |
Plan Coordinator | Original | / | 4/8/2015 | | RUSSELL | Location = Plan Coordinator by RUSSELL | | Plan Coordinator | 774751 |
Mechanical | Original | D | 4/8/2015 | RUSSELL | RUSSELL | Dressing Room ventilation/exhaust per '09 IMC Table 403.3 ? dressing room wall heights? how ventilating with where diffusers are shown on the plan?, separate the plumbing and mechanical, ventilation appears to be short, see my comments versus your ventilation on sheet M-2? provide a letter from a structural engineer verifying structure is adequate to support new unit or a structural sheet showing what modifications are necessary to support new 1360# unit, add note: Provide a test and balance report to the mechanical inspector at time of the heating final inspection, is the toilet room door under cut to allow for makeup air path?, verify square footages on your ventilation table versus the code study form | | Mechanical | 774750 |
Mechanical | Original | / | 4/8/2015 | RUSSELL | RUSSELL | In Current Review by RUSSELL | | Mechanical | 774687 |
Mechanical | Original | / | 4/8/2015 | | RITA | Location = Mechanical by RITA | | Mechanical | 774561 |
Plan Coordinator | Original | / | 4/8/2015 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 774540 |
Plumbing | Original | A | 4/8/2015 | TCRIPPEN | TCRIPPEN | We will allow the plumbing to be on the mechanical page this time but in the future plumbing is to be on separate pages. | | Plumbing | 774537 |
Plumbing | Original | / | 4/8/2015 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 774500 |
Plumbing | Original | / | 4/8/2015 | | RITA | Location = Plumbing by RITA | | Plumbing | 774499 |
Electrical | Original | / | 4/6/2015 | | KENYATTA | Location = Electrical by KENYATTA | | Electrical | 774035 |
Plan Coordinator | Original | / | 4/6/2015 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 774008 |
Construction | Original | D | 4/6/2015 | SHELLEY | SHELLEY | Clarify what blank space is - if a separate tenant, separation is required and listed assembly is required for door infill; see plans; walk ok. | | Construction | 774007 |
Construction | Original | / | 4/6/2015 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 773964 |
Construction | Original | / | 4/6/2015 | | KENYATTA | Location = Construction by KENYATTA | | Construction | 773907 |
Floodplain | Original | N | 4/6/2015 | AMY | AMY | | | Floodplain | 773897 |
Plan Coordinator | Original | / | 4/6/2015 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 773896 |
Enumeration | Original | D | 4/6/2015 | AMY | AMY | Based on our records this area is a combination of 371, 361, 358 and common space. Please clarify. What suite number will this space use for their address? This suite number show be the only suite number on the plan submittal pages. | | Enumeration | 773895 |
Enumeration | Original | / | 4/6/2015 | AMY | AMY | In Current Review by AMY | | Enumeration | 773892 |